IL PB BK DI8 DO4/EF-PAC 2692322 PHOENIX CONTACT Inline Modular PROFIBUS bus coupler DP/V1, 8 inputs: 24 V DC.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

IL PB BK DI8 DO4/EF-PAC 2692322 PHOENIX CONTACT Inline Modular PROFIBUS bus coupler DP/V1, 8 inputs: 24 V DC..

IL PB BK DI8 DO4/EF-PAC

2692322

PHOENIX_CONTACT

Available

Ship on today

Inline Modular PROFIBUS bus coupler DP/V1, 8 inputs: 24 V DC, 4 outputs: 24 V DC, 500 mA, 2, 3-conductor connection method

More details


AUTOMATION Industrial Automation - PHOENIX CONTACT

I/O systems - PHOENIX CONTACT

* Brand new produt in its original packing covered by the warranties and certifications provided by PHOENIX_CONTACT

*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Product description

The bus coupler for the PROFIBUS has 4 digital outputs and 8 digital inputs. This package contains all the necessary Inline connectors for connecting the supply and the I/Os.

For project planning, the relevant GSD (device master data) file can be downloaded in the download area of Phoenixcontact.com.

The Inline terminals can be labeled using pull-out labeling fields. The fields have insert cards that can be labeled individually to suit the application. Additionally, there is the ZBFM-6... Zack marker strip for labeling the terminal points.

Dimensions

Width80 mm
Height119.8 mm
Depth71.5 mm
Note on dimensionsSpecfications with connectors

Ambient conditions

Ambient temperature (operation)-25 °C ... 60 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Permissible humidity (operation)10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport)10 % ... 95 % (according to DIN EN 61131-2)
Air pressure (operation)70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protectionIP20

General

Net weight320 g
Note on weight specificationswith connectors
Mounting typeDIN rail
Diagnostics messagesShort-circuit / overload of the digital outputs Yes
Sensor supply failure Yes
Failure of the actuator supply Yes

Interfaces

Fieldbus systemPROFIBUS DP
DesignationPROFIBUS DP
Connection methodD-SUB-9 female connector
Transmission speed9,6 kBit/s ... 12 MBit/s
Number of positions9
Fieldbus systemLokalbus
DesignationInline local bus
Connection methodInline data jumper
Transmission speed500 kBit/s / 2 MBit/s (Automatic detection, no combined system)

System limits of the bus coupler

DesignationSystem limits of the bus coupler
Amount of process datamax. 488 Byte (per station)
max. 244 Byte (Input)
max. 244 Byte (Output)
Number of parameter datamax. 244 Byte (including 14 bytes for the bus coupler, DP/V1, and the local inputs and outputs)
Number of configuration datamax. 244 Byte (including 5 bytes for the local inputs and outputs)
Number of supported devicesmax. 63 (per station)
Number of local bus devices that can be connectedmax. 61 (on board I/Os are two devices)
Number of devices with parameter channelmax. 16
Number of supported branch terminals with remote bus branch0
Response time of I/Ostyp. 4 ms (aligned I/Os; transmission speed: PROFIBUS 1.5 Mbps, local bus 500 kbps)

Power supply for module electronics

Connection methodSpring-cage connection
DesignationBus coupler supply UBC; Communications power UL (7.5 V) and the analog supply UANA (24 V) are generated from the bus coupler supply.
Supply voltage24 V DC (via Inline connector)
Supply voltage range19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current consumptionmax. 0.98 A (from UBK)
Power losstyp. 1.7 W (entire device)
Communications power UL7.5 V DC
Current consumption0.8 A
Power consumptiontyp. 1.7 W

Inline potentials

Communications power UL7.5 V DC ±5 %
Power supply at ULmax. 0.8 A DC
Main circuit supply UM24 V DC
Supply voltage range UM19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply at UMmax. 8 A DC (Sum of UM + US)
Current consumption from UMmax. 8 A DC
Segment supply voltage US24 V DC
Supply voltage range US19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply at USmax. 8 A DC (Sum of UM + US)
Current consumption from USmax. 8 A DC
I/O supply voltage UANA24 V DC
Supply voltage range UANA19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply at UANAmax. 0.5 A DC

Digital inputs

Input nameDigital inputs
Connection methodInline connector
2, 3-wire
Number of inputs8 (EN 61131-2 type 1)
Typical response timeapprox. 500 µs
Protective circuitProtection against polarity reversal Suppressor diode
Input characteristic curveIEC 61131-2 type 1
Input voltage24 V DC
Input voltage range "0" signal-30 V DC ... 5 V DC
Input voltage range "1" signal15 V DC ... 30 V DC
Nominal input current at UINtyp. 3 mA
Typical input current per channeltyp. 3 mA
Delay at signal change from 0 to 12.9 ms
Delay at signal change from 1 to 02.9 ms

Digital outputs

Output nameDigital outputs
Connection methodInline connector
2, 3-wire
Number of outputs4
Protective circuitShort-circuit and overload protection Free running circuit
Output voltage24 V DC -1 V (At nominal current)
Nominal output voltage24 V DC
Maximum output current per channel500 mA
Maximum output current per module / terminal block2 A
Maximum output current per module2 A
Nominal load, inductive12 VA (1.2 H; 48 Ω)
Nominal load, lamp12 W
Nominal load, ohmic12 W

Datasheet - PDF

Title:Language:Size:Type:
PHOENIX CONTACT-2692322-IL PB BK DI8 DO4/EF-PACEnglish165 KbytesPHOENIX CONTACT-2692322-IL PB BK DI8 DO4/EF-PAC

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields

or