NLC-050-024D-06I-04QTP-00A 2701027 PHOENIX CONTACT 24 V DC Nanoline base unit. Equipped with 6 digital input.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

NLC-050-024D-06I-04QTP-00A 2701027 PHOENIX CONTACT 24 V DC Nanoline base unit. Equipped with 6 digital input..

NLC-050-024D-06I-04QTP-00A

2701027

PHOENIX_CONTACT

Available

Ship on today

24 V DC Nanoline base unit. Equipped with 6 digital input and 4 PNP digital output channels. Additional I/O channels can be added using a maximum of three I/O extension modules. Optional communication modules provide network or serial connectivity. Optional Operator Panel provides user interface. Programming is via nanoNavigator.

More details


AUTOMATION Industrial Automation - PHOENIX CONTACT

Control technology - PHOENIX CONTACT

* Brand new produt in its original packing covered by the warranties and certifications provided by PHOENIX_CONTACT

*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Dimensions

Width80.5 mm
Height103.5 mm
Depth60 mm

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-25 °C ... 60 °C
Ambient temperature (storage/transport)-25 °C ... 85 °C
Permissible humidity (operation)90 %

Interfaces

InterfaceOperator Panel
Connection methodRJ45/Combicon
InterfaceRS-232
Connection methodSlot 1
InterfaceUSB
Connection methodSlot 1
InterfaceRealtime Clock
Connection methodSlot 2

Supply

Power supply connectionScrew connection
Supply voltage24 V DC (Power available to the I/O and Communications modules)
Supply voltage range19.2 V DC ... 30 V DC
Max. current consumption250 mA
Typical current consumption92 mA

Software interfaces

Programming toolnanoNavigator 1 or 2

Digital inputs

Input nameDigital inputs
Description of the inputEN 61131-2 type 1 NPN/PNP
Connection methodScrew connection
Number of inputs6
Typical response time60 µs (on)
70 µs (off)
Input voltage24 V DC
Input voltage range "0" signal0 V DC ... 5 V DC
Input voltage range "1" signal15 V DC ... 30 V DC
Nominal input current at UIN5 mA DC (On)

Digital outputs

Output nameDigital outputs
Output descriptionPNP outputs
Connection methodScrew connection
Number of outputs4
Protective circuitShort-circuit and overload protection
Output voltage24 V DC
Maximum output current per channel500 mA
Maximum output current per module / terminal block2 A
Maximum output current per module2 A
Nominal load, inductive12 VA ((1.2H))
Nominal load, lamp12 W
Nominal load, ohmic12 W

General

Mounting typeDIN rail mounting

Datasheet - PDF

Title:Language:Size:Type:
PHOENIX CONTACT-2701027-NLC-050-024D-06I-04QTP-00AEnglish119 KbytesPHOENIX CONTACT-2701027-NLC-050-024D-06I-04QTP-00A

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields

or