Key Commercial Data

Orderkey2801593
Packing unit1 pc
Catalog pagePage 162 (C-4-2017)
GTIN4046356868457
Weight per Piece (excluding packing)320.000 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height103 mm
Width25 mm
Depth63 mm

Ambient conditions

Ambient temperature (operation)-40 °C ... 85 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Degree of protectionIP20

General

Housing materialZinc die-cast
Colorsilver/black
Standards for cearances and creepage distancesIEC 60664-1
VDE 0110-1
Mounting typeConnection-specific attachment plug and DIN rail, 35 mm
TypeAttachment plug for DIN rail mounting
Number of positions4
Direction of actionLine-Line & Line-Ground/Shield

Protective circuit

IEC test classificationB2
C1
C2
C3
D1
VDE requirement classB2
C1
C2
C3
D1
Maximum continuous voltage UC185 V DC
130 V AC
Rated current≤ 380 mA (25 °C)
Operating effective current ICat UC≤ 6 µA
Residual current IPE≤ 4 µA
Nominal discharge current In(8/20) µs (line-line)≤ 5 kA
Nominal discharge current In(8/20) µs (line-earth)≤ 5 kA
Pulse discharge current Iimp(10/350) µs2.5 kA (Number of pulses category D1)
Total discharge current Itotal(8/20) µs10 kA
Nominal pulse current Ian (10/1000) µs (line-line)100 A
Nominal pulse current Ian (10/1000) µs (line-earth)100 A
Nominal pulse current Ian (10/700) µs (line-line)150 A
Nominal pulse current Ian (10/700) µs (line-earth)150 A
Voltage protection level Up(line-line)250 V (B2 - 100 A)
≤ 250 V (C1 - 500 A)
≤ 410 V (C2 - 5 kA)
≤ 250 V (C3 - 100 A)
Voltage protection level Up(line-earth)≤ 580 V (B2 - 100 A)
≤ 580 V (C1 - 500 A)
≤ 790 V (C2 - 5 kA)
≤ 300 V (C3 - 100 A)
Response time tA(line-line)≤ 100 ns
Response time tA(line-earth)≤ 100 ns
Input attenuation aE, sym.
typ. 0.3 dB (≤ 2,8 MHz / 100 Ω)
typ. 3 dB (≤ 25 MHz / 100 Ω)
Cut-off frequency fg (3 dB), sym. in 100 Ohm system25 MHz
Capacity (line-line)55 pF
Capacity (line-earth)7 pF
Resistance in series3.3 Ω 20 %
Surge protection fault messagenone
Impulse durability (line-line)C1 - 1 kV/500 A
C2 - 10 kV/5 kA
B2 - 4 kV/100 A
Impulse durability (line-earth)B2 - 4 kV/100 A
C1 - 1 kV/500 A
C2 - 10 kV/5 kA
D1 - 1 kA

Connection data

Connection methodRJ45/COMBICON
Connection method INRJ45 socket
MC 1,5/4
Connection method OUTRJ45 socket
MC 1,5/4
Connection technologyScrew connection
Screw threadM2
Tightening torque0.22 Nm
Stripping length7 mm
Conductor cross section flexible0.14 mm² ... 1.5 mm²
Conductor cross section solid0.14 mm² ... 1.5 mm²
Conductor cross section AWG28 ... 16

Connection, equipotential bonding

Connection methodCable connection/DIN rail

Standards and Regulations

Standards/regulationsIEC 61643-21
Standards/specificationsIEC 61643-21 2002

Classifications

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.