MNT-NET B/F 2882226 PHOENIX CONTACT Attachment plug with surge protection for mains sockets, optical power a.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

MNT-NET B/F 2882226 PHOENIX CONTACT Attachment plug with surge protection for mains sockets, optical power a..

MNT-NET B/F

2882226

PHOENIX_CONTACT

Available

Ship on today

Attachment plug with surge protection for mains sockets, optical power and fault display.

More details


Overvoltage Protection Over Voltage

TRABTECH Power and Signal Quality - PHOENIX CONTACT

Surge protection for information technology - PHOENIX CONTACT

* Brand new produt in its original packing covered by the warranties and certifications provided by PHOENIX_CONTACT

QuantityPrice
1+$32.74
7+$29.65
14+$28.92
21+$28.56
28+$28.33
*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Dimensions

Height76 mm
Width56 mm
Depth79 mm

Ambient conditions

Ambient temperature (storage/transport)-25 °C ... 75 °C
Ambient temperature (operation)-25 °C ... 75 °C

General

Housing materialPA 6
Flammability rating according to UL 94V-0
Colorjet black RAL 9005
Standards for cearances and creepage distancesEN 60664-1
IEC 60664-1
IEC 61643-1
EN 61643-11
TypeAttachment plug
Mounting typePlugging into the mains socket
For country-specific use inB, F, CZ, SVK, PL
Direction of actionL(N)-PE

Protective circuit

IEC test classificationIII
T3
EN typeT3
Nominal voltage UN230 V AC
Arrester rated voltage UC (L-N)275 V AC
Arrester rated voltage UC (L-PE)360 V AC
Arrester rated voltage UC (N-PE)360 V AC
Nominal frequency fN50 Hz (60 Hz)
Standby power consumption PC≤ 1 VA
Residual current IPE≤ 5 µA
Nominal discharge current In (8/20) µs3 kA (> 5x)
Combination wave UOC4 kV
Energy absorption symmetrical140 J (L-N)
Enery absorption, asymmetrical220 J (L(N)-PE)
Voltage protection level Up (L-N)≤ 1.2 kV
Voltage protection level Up (L-PE)≤ 1.5 kV
Voltage protection level Up (N-PE)≤ 1.5 kV
Response time tA (L-N)≤ 25 ns
Response time tA (L-PE)≤ 100 ns
Response time tA (N-PE)≤ 100 ns
Max. required back-up fuse16 A AC (gG / B / C)
Surge protection fault messageoptical

Non-heating apparatus connection, power supply

Connection methodGrounding plug/socket
Connection type INProtective contact plug CEE7
Connection type OUTProtective contact socket CEE7

Standards and Regulations

Standards/specificationsIEC 61643-11 2011
EN 61643-11 2012

Datasheet - PDF

Title:Language:Size:Type:
PHOENIX CONTACT-2882226-MNT-NET B/FEnglish108 KbytesPHOENIX CONTACT-2882226-MNT-NET B/F

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields

or