Inline analog input terminal with differential input channels, complete with accessories (connector plug and labeling field), 4 inputs, 0 - 20 mA, 4 - 20 mA, ±20 mA, 0 - 10 V, ±10 V, 0 - 5 V, ±5 V), 2-, 3- or 4-wire connection technology

More details


AUTOMATION Industrial Automation - PHOENIX CONTACT

I/O systems - PHOENIX CONTACT

* Brand new produt in its original packing covered by the warranties and certifications provided by PHOENIX_CONTACT

*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Dimensions

Width48.8 mm
Height135 mm
Depth71.5 mm

Ambient conditions

Ambient temperature (operation)-25 °C ... 55 °C
Ambient temperature (storage/transport)-25 °C ... 85 °C
Permissible humidity (operation)10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport)10 % ... 95 % (according to DIN EN 61131-2)
Air pressure (operation)70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protectionIP20

General

Net weight210 g
Note on weight specificationswith connectors
Mounting typeDIN rail
Operating modeProcess data mode with 5 words/1 word PCP

Interfaces

Fieldbus systemLokalbus
DesignationInline local bus
Connection methodInline data jumper
Transmission speed500 kBit/s
Transmission physicsCopper

Inline potentials

Communications power UL7.5 V DC (via voltage jumper)
Current consumption from ULmax. 100 mA
typ. 85 mA
Main circuit supply UM24 V DC
Current consumption from UMmax. 200 mA
I/O supply voltage UANA24 V DC
Current consumption from UANAmax. 20 mA
typ. 13 mA

Analog inputs

Number of inputsmax. 4 (Differential inputs, voltage or current can be chosen separately)
Connection methodInline shield connector
2, 3, 4-wire (shielded)
Input nameAnalog inputs
A/D conversion timemax. 10 µs
Limit frequency (3 dB)500 Hz
Type of protectionTransient protection
Protective circuit/componentYes, via arresters
Data formatsIB IL, IB ST, standardized representation, S7 compatible
Measured value resolution16 bits (15 bits + sign bit)
Current input signal0 mA ... 20 mA
4 mA ... 20 mA
-20 mA ... 20 mA
Voltage input signal0 V ... 5 V
-5 V ... 5 V
0 V ... 10 V
-10 V ... 10 V
Number of inputs4 (differential inputs, voltage)
Open circuit responseGoes to 0 V
Voltage input signal0 V ... 5 V
-5 V ... 5 V
0 V ... 10 V
-10 V ... 10 V
Input resistance of voltage input300 kΩ
Number of inputs4 (Differential inputs, current)
Type of protectionOverload protection
Open circuit responseGoes to 0 mA
Current input signal0 mA ... 20 mA
4 mA ... 20 mA
-20 mA ... 20 mA
Input resistance current inputapprox. 110 Ω

Datasheet - PDF

Title:Language:Size:Type:
PHOENIX CONTACT-2878447-IB IL AI 4/EF-PACEnglish131 KbytesPHOENIX CONTACT-2878447-IB IL AI 4/EF-PAC

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields

or