MINI MCR-2-RPSS-I-I 2902014 PHOENIX CONTACT Repeater power supply View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

MINI MCR-2-RPSS-I-I 2902014 PHOENIX CONTACT Repeater power supply

MINI MCR-2-RPSS-I-I

2902014

PHOENIX_CONTACT

Repeater power supply

More details


INTERFACE Components (IF)

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Total price: $248.42
Unit price: $248.42

Quantity Price
1+$248.42
2+$227.20
*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Key Commercial Data

Orderkey2902014
Packing unit1 pc
Catalog pagePage 75 (C-5-2017)
GTIN4046356651981
Weight per Piece (excluding packing)110.000 g
Custom tariff number85437090
Country of originDE (Germany)

Note

Utilization restrictionEMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width6.2 mm
Height110.5 mm
Depth120.5 mm

Ambient conditions

Ambient temperature (operation)-40 °C ... 70 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C

Input data

Description of the inputCurrent input (sensor circuit)
Number of inputs1
Current input signal4 mA ... 20 mA (repeater power supply and isolator operation)
0 mA ... 20 mA (isolator operation)
Input resistance current inputapprox. 68 Ω (+ 0.7 V for test diode)
Transmitter supply voltage> 19.5 V

Output data

Output nameCurrent output
Number of outputs1
Current output signal4 mA ... 20 mA (repeater power supply and isolator operation)
0 mA ... 20 mA (isolator operation)
Max. output current24 mA
Load/output load current output≤ 600 Ω (at 20 mA)
Ripple< 20 mVPP(at 600 Ω)
Transmission Behavior1:1 to input signal

Power supply

Nominal supply voltage24 V DC
Supply voltage range9.6 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
Typical current consumption25 mA (at 24 V DC and in isolator operation)
50 mA (at 24 V DC and in repeater power supply operation)
55 mA (at 12 V DC and in isolator operation)
110 mA (at 12 V DC and in repeater power supply operation)
Power consumption≤ 1400 mW (at IOUT= 20 mA, 9.6 V DC, 600 Ω load)

Connection data

Connection methodScrew connection
Single conductor/terminal point, solid, with ferrule, min.0.2 mm²
Single conductor/terminal point, solid, with ferrule, max.1.5 mm²
Single conductor/terminal point, solid, without ferrule, min.0.2 mm²
Single conductor/terminal point, solid, without ferrule, max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.1.5 mm²
Min. AWG conductor cross section, flexible24
Max. AWG conductor cross section, flexible12
Stripping length10 mm
Screw threadM3

General

No. of channels1
Maximum transmission error0.05 % (of final value, at 4 mA ... 20 mA)
0.1 % (of final value, at 0 mA ... 20 mA)
Maximum temperature coefficient0.0075 %/K
Temperature coefficient, typical0.0075 %/K
Limit frequency (3 dB)> 1.75 kHz (typ.)
Step response (10-90%)< 200 µs (typ.)
Protective circuitTransient protection
Electrical isolationReinforced insulation in accordance with IEC 61010-1
Overvoltage categoryII
Degree of pollution2
Rated insulation voltage300 V (effective)
Test voltage, input/output/supply3 kV (50 Hz, 1 min.)
Electromagnetic compatibilityConformance with EMC directive
Noise emissionEN 61000-6-4
Noise immunityEN 61000-6-2 When being exposed to interference, there may be minimal deviations.
Colorgray
Housing materialPBT
Mounting positionany
Assembly instructionsThe T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715.
ConformanceCE-compliant
ATEX II 3 G Ex nA IIC T4 Gc X
UL, USA/CanadaUL 508 Listed
Class I, Div. 2, Groups A, B, C, D T5
Class I, Zone 2, Group IIC T5
GLC, EMC2
Certificate of classificationDNV GL 14445-15HH
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 2

Data communication (bypass)

Limit frequency (3 dB)approx. 1.75 kHz

EMC data

DesignationElectromagnetic RF field
Standards/regulationsEN 61000-4-3
DesignationFast transients (burst)
Standards/regulationsEN 61000-4-4
DesignationConducted interferences
Standards/regulationsEN 61000-4-6

Standards and Regulations

Electromagnetic compatibilityConformance with EMC directive
Noise emissionEN 61000-6-4
Standards/regulationsEN 61000-4-2
DesignationElectromagnetic RF field
Standards/regulationsEN 61000-4-3
EN 61000-4-4
EN 61000-4-5
DesignationConducted interferences
Standards/regulationsEN 61000-4-6
Electrical isolationReinforced insulation in accordance with IEC 61010-1
ConformanceCE-compliant
ATEX II 3 G Ex nA IIC T4 Gc X
UL, USA/CanadaUL 508 Listed
Class I, Div. 2, Groups A, B, C, D T5
Class I, Zone 2, Group IIC T5
GLC, EMC2
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 2

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.