K8AK-AW1 100-240VAC K8AK0007M 378164 OMRON Single Phase Current Max & Min 20-500mA 100-240VAC 2 SPDT View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

K8AK-AW1 100-240VAC K8AK0007M 378164 OMRON Single Phase Current Max & Min 20-500mA 100-240VAC 2 SPDT

K8AK-AW1 100-240VAC

K8AK0007M

K8AKAW1100240VAC

OMRON

Available Ship on today

Single-phase Current, Max, and Min 20-500mA 100-240VAC 2 SPDT

More details


Monitoring Relays > K8AK

* Brand new product in its original packaging covered by the warranties and certifications provided by OMRON

Total price: $156.52
Unit price: $156.52

Quantity Price
1+$156.52
2+$148.03
*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Related products

More info



Features

Single-phase current relay, window type

These single-phase current relays monitor over- and undercurrents. Manual resetting and automatic resetting are supported by one relay. The start-up lock and operating time can be set separately. The relay warning status is easily monitored with the LED indicator.

  • Single-phase current window relay
  • In 22.5 mm wide industrial housing
  • Under and over control
  • Supply voltages: 24 VAC/DC, 100 to 240 VAC
  • Easy wiring with ferrules

Ordering information

Measuring current

Supply voltage

Order code

2 to 20 mA AC/DC,
10 to 100 mA AC/DC,
50 to 500 mA AC/DC

24 VAC/DC

K8AK-AW1 24 VAC/DC

100 to 240 VAC

K8AK-AW1 100-240 VAC

0.1 to 1 A AC/DC,
0.5 to 5 A AC/DC

24 VAC/DC

K8AK-AW2 24 VAC/DC

100 to 240 VAC

K8AK-AW2 100-240 VAC

10 to 100 A AC,
20 to 200 A AC

24 VAC/DC

K8AK-AW3 24 VAC/DC

100 to 240 VAC

K8AK-AW3 100-240 VAC

Accessories

Current transformer

Input range

Applicable relay

Order code

K8AK-AW_rev01-2.png

10 to 100 A AC, 20 to 200 A AC

K8AK-AW3

K8AC-CT200L

Note:The K8AK-AW3 is designed to be used in combination with the K8AC-CT200L (direct input not possible)

Specifications

Ambient operating temperature

-20 to 60°C (with no condensation or icing)

Storage temperature

-25 to 65°C (with no condensation or icing)

Operating voltage range

85% to 110% of rated operating voltage

Rated power supply frequency

50/60 Hz±5 Hz (AC power supply)

Output relays
(1 × SPDT, normally closed operation)

Resistive load

5 A at 250 VAC or at 30 VDC

Maximum contact voltage

250 VAC or 30 VDC

Maximum contact current

5 A

Maximum switching capacity

1,250 VA, 150 W

Mechanical life

10,000,000 operations

Electrical life

50,000 operations at 5 A, 250 VAC or 30 VDC

Degree of protection

Terminal section: IP20

Case material

PC and ABS

Weight

Approx. 150 g

Operating power

Isolated power supply

2.0 VA/1.1 W max. at 24 VAC/DC, 4.6 VA max. at 100 to 240 VAC

Operate (SV)

Operating value setting range

10% to 100% of maximum measuring current

Operating value

100% operation at set value

Reset (HYS.)

Hysteresis

5% of operating value (fixed)

Resetting method

Manual reset/automatic reset (switchable)
Manual reset: Turn OFF operating power for 1 s or longer

Operating time (T)

0.1 to 30 s

Operating power ON lock (LOCK)

0 to 30 s (The startup lock timer starts when the input has reached approximately 30% or more of the set value.)

Note: Enabled only for overcurrent operation

Repeat error

Operating value

±0.5% full scale (at 25°C and 65% humidity, rated power supply voltage, DC or 50/60 Hz sine wave input)

Operating time

±50 ms (at 25°C and 65% humidity, rated power supply voltage)

Input frequency range

K8AK-AW1/-AW2

DC input or AC input (45 to 65 Hz)

K8AK-AW3

AC input (45 to 65 Hz)

Overload capacity

K8AK-AW1/-AW2

Continuous input at 120% of maximum input, 1 s at 150%

K8AK-AW3

Continuous input at 120%, 30 s at 200%, and 1 s at 600% with an OMRON CT (K8AC-CT200L)

Indicators

Power (PWR): Green LED, relay output (RY): Yellow LED, alarm outputs (ALM): Red LED

Applicable standards

Conforming standards

EN 60947-5-1
Installation environment (pollution level 2, installation category III)

EMC

EN 60947-5-1

Safety standards

UL 508 (Recognition), Korean Radio Waves Act (Act 10564), CSA and CCC

Size in mm (H × W × D)

90 × 22.5 × 100

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.