- Easy and clear read-out thanks to bright liquid Crystal Display
- Exceptional versatility - multi-loop control, cascade control, and valve control
- Easy integration with DeviceNet, Profibus or Modbus
- SV programmer optional, 32 programs with up to 256 segments
Specifications & ordering info
Ordering information
Function | Loops | Input analog | Event Inputs | Number of outputs | Outputs | AUX outputs | Communication | Order code (96 × 96 mm) |
---|
100 to 240 VAC | 24 VAC/DC |
---|
standard | 1 | 1 | 2 | 2 | QC,Q | 4R | - | E5AR-Q4B AC100-240 | E5AR-Q4B AC/DC24 |
standard | 1 | 1 | 2 | 2 | QC,Q | 4R | RS-485 | E5AR-Q43B-FLK AC100-240V |
standard | 1 | 1 | 6 | 2 | QC,Q | 4R | RS-485 | E5AR-Q43DB-FLK AC100-240V |
standard | 1 | 1 | 6 | 4 | QC,Q,C,C | 4R | RS-485 | E5AR-QC43DB-FLK AC100-240 | E5AR-QC43DB-FLK AC/DC24 |
standard | max 2 | 2 | 4 | 2 | QC,Q | 4R | RS-485 | E5AR-Q43DW-FLK AC100-240V |
standard | max 2 | 2 | 4 | 4 | QC,Q,QC,Q | 4R | RS-485 | E5AR-QQ43DW-FLK AC100-240 | E5AR-QQ43DW-FLK AC/24 |
standard | max 4 | 4 | 4 | 4 | QC,Q,QC,Q | 4R | RS-485 | E5AR-QQ43DWW-FLK AC100-240V |
standard | 1 | 1 | 2 | 2 | C,C | 4R | - | E5AR-C4B AC100-240 | E5AR-C4B AC/DC24 |
standard | 1 | 1 | 2 | 2 | C,C | 4R | RS-485 | E5AR-C43B-FLK AC100-240V |
standard | 1 | 1 | 6 | 2 | C,C | 4R | RS-485 | E5AR-C43DB-FLK AC100-240V |
standard | max 2 | 2 | 4 | 2 | C,C | 4R | RS-485 | E5AR-C43DW-FLK AC100-240V |
standard | max 4 | 4 | 4 | 4 | C,C,C,C | 4R | RS-485 | E5AR-CC43DWW-FLK AC100-240 | E5AR-CC43DWW-FLK AC/DC24 |
valve | 1 | 1 + pot | 4 | 2 | R,R | 4R | - | E5AR-PR4DF AC100-240 | E5AR-PR4DF AC/DC24 |
valve | 1 | 1 + pot | 4 | 4 | R,R,QC,Q | 4R | RS-485 | E5AR-PRQ43DF-FLK AC100-240 | E5AR-PRQ43DF-FLK AC/DC24 |
standard | 1 | 1 | 2 | 2 | QC,Q | 4R | DeviceNet | E5AR-Q4B-DRT AC100-240V | E5AR-Q4B-DRT AC24V |
standard | 1 | 1 | 2 | 4 | QC,Q,C,C | 4R | DeviceNet | E5AR-QC4B-DRT AC100-240V | E5AR-QC4B-DRT AC24V |
standard | max 2 | 2 | - | 4 | QC,Q,QC,Q | 4R | DeviceNet | E5AR-QQ4W-DRT AC100-240V | E5AR-QQ4W-DRT AC24V |
standard | 1 | 1 | 2 | 2 | C,C | 4R | DeviceNet | E5AR-C4B-DRT AC100-240V | E5AR-C4B-DRT AC24V |
standard | max 4 | 4 | - | 4 | C,C,C,C | 4R | DeviceNet | E5AR-CC4WW-DRT AC100-240V |
valve | 1 | 1 + pot | - | 2 | R,R | 4R | DeviceNet | E5AR-PR4F-DRT AC100-240V | E5AR-PR4F-DRT AC24V |
valve | 1 | 1 + pot | - | 4 | R,R,QC,Q | 4R | DeviceNet | E5AR-PRQ4F-DRT AC100-240V | E5AR-PRQ4F-DRT AC24V |
SV programmer | 1 | 1 | 2 | 2 | QC,Q | 4R | - | E5AR-TQ4B AC100-240 | E5AR-TQ4B AC/DC24 |
SV programmer | 1 | 1 | 2 | 2 | C,C | 4R | - | E5AR-TC4B AC100-240 | E5AR-TC4B AC/DC24 |
SV programmer | 1 | 1 | 2 | 2 | QC,Q | 4R | RS-485 | E5AR-TQ43B-FLK AC100-240 |
SV programmer | 1 | 1 | 2 | 2 | C,C | 4R | RS-485 | E5AR-TC43B-FLK AC100-240 |
SV programmer | 1 | 1 | 10 | 2 | QC,Q | 10T | RS-485 | E5AR-TQE3MB-FLK AC100-240 |
SV programmer | 1 | 1 | 10 | 2 | C,C | 10T | RS-485 | E5AR-TCE3MB-FLK AC100-240 |
SV programmer | 1 | 1 | 10 | 4 | QC,Q,C,C | 10T | RS-485 | E5AR-TQCE3MB-FLK AC100-240V | E5AR-TQCE3MB-FLK AC/DC24 |
SV programmer | max 2 | 2 | 4 | 2 | QC,Q | 4R | RS-485 | E5AR-TQ43DW-FLK AC100-240 |
SV programmer | max 2 | 2 | 4 | 2 | C,C | 4R | RS-485 | E5AR-TC43DW-FLK AC100-240 |
SV programmer | max 2 | 2 | 8 | 4 | QC,Q,QC,Q | 10T | RS-485 | E5AR-TQQE3MW-FLK AC100-240 | E5AR-TQQE3MW-FLK AC/DC24 |
SV programmer | max 4 | 4 | 8 | 2 | C,C,C,C | 10T | RS-485 | E5AR-TCCE3MWW-FLK AC100-240 | E5AR-TCCE3MWW-FLK AC/DC24 |
SV programmer | max 4 | 4 | 8 | 4 | QC,Q,QC,Q | 10T | RS-485 | E5AR-TQQE3MWW-FLK AC100-240 |
SV programmer + valve | 1 | 1 + pot | 4 | 2 | R,R | 4R | - | E5AR-TPR4DF AC100-240 | E5AR-TPR4DF AC/DC24 |
SV programmer + valve | 1 | 1 + pot | 8 | 4 | R,R,QC,Q | 10T | RS-485 | E5AR-TPRQE3MF-FLK AC100-240 | E5AR-TPRQE3MF-FLK AC/DC24 |
- Note • Standard = heat and/or cool PID control, valve = valve positioning (relay up/down) (PRR)
- • max 2 = 2 loops heat and/or cool or 1 loop cascade, ratio or remote SP
- • max 4 = 4 loops heat and/or cool
- • 1, 2 or 4 = number of analog universal input 1 + pot = 1 universal and 1 slide wire feedback from valve
- • QC = voltage (pulse) or current (switch), Q = voltage (pulse), C = current, 4R = 4 two pole relay, 2T = two transistor output NPN
Function | Loops | Input analog | Event Inputs | Number of outputs | Outputs | AUX outputs | Communication | Order code (48 × 96 mm) |
---|
100 to 240 VAC | 24 VAC/DC |
---|
standard | 1 | 1 | 2 | 2 | QC+Q | 4R | - | E5ER-Q4B AC100-240 | E5ER-Q4B AC/DC24 |
standard | 1 | 1 | 2 | 2 | QC+Q | 4R | RS-485 | E5ER-Q43B-FLK AC100-240V |
standard | 1 | 1 | 2 | 4 | QC+Q+C+C | 4R | RS-485 | E5ER-QC43B-FLK AC100-240 | E5ER-QC43B-FLK AC/DC24 |
standard | 1 | 1 | 6 | 2 | QC+Q | 2T | RS-485 | E5ER-QT3DB-FLK AC100-240V |
standard | max 2 | 2 | 4 | 2 | QC+Q | 2T | RS-485 | E5ER-QT3DW-FLK AC100-240 | E5ER-QT3DW-FLK AC/DC24 |
standard | 1 | 1 | 2 | 2 | C+C | 4R | - | E5ER-C4B AC100-240 | E5ER-C4B AC/DC24 |
standard | 1 | 1 | 2 | 2 | C+C | 4R | RS-485 | E5ER-C43B-FLK AC100-240V |
standard | 1 | 1 | 6 | 2 | C+C | 2T | RS-485 | E5ER-CT3DB-FLK AC100-240V |
standard | max 2 | 2 | 4 | 2 | C+C | 2T | RS-485 | E5ER-CT3DW-FLK AC100-240 | E5ER-CT3DW-FLK AC/DC24 |
valve | 1 | 1 + pot | 4 | 2 | R+R | 2T | - | E5ER-PRTDF AC100-240 | E5ER-PRTDF AC/DC24 |
valve | 1 | 1 + pot | - | 4 | R+R+QC+Q | 4R | RS-485 | E5ER-PRQ43F-FLK AC100-240 | E5ER-PRQ43F-FLK AC/DC24 |
standard | 1 | 1 | 2 | 2 | QC+Q | 2T | DeviceNet | E5ER-QTB-DRT AC100-240V | E5ER-QTB-DRT AC24V |
standard | max 2 | 2 | - | 2 | QC+Q | 2T | DeviceNet | E5ER-QTW-DRT AC100-240V | E5ER-QTW-DRT AC24V |
standard | 1 | 1 | 2 | 2 | C+C | 2T | DeviceNet | E5ER-CTB-DRT AC100-240V | E5ER-CTB-DRT AC24V |
standard | max 2 | 2 | - | 2 | C+C | 2T | DeviceNet | E5ER-CTW-DRT AC100-240V | E5ER-CTW-DRT AC24V |
valve | 1 | 1 + pot | - | 2 | R+R | 2T | DeviceNet | E5ER-PRTF-DRT AC100-240V | E5ER-PRTF-DRT AC24V |
SV programmer | 1 | 1 | 2 | 2 | QC+Q | 4R | - | E5ER-TQ4B AC100-240 | E5ER-TQ4B AC/DC24 |
SV programmer | 1 | 1 | 2 | 2 | C+C | 4R | - | E5ER-TC4B AC100-240 | E5ER-TC4B AC/DC24 |
SV programmer | 1 | 1 | 2 | 2 | QC+Q | 4R | RS-485 | E5ER-TQC43B-FLK AC100-240 | E5ER-TQC43B-FLK AC/DC24 |
SV programmer | max 2 | 2 | 4 | 2 | QC+Q | 2T | RS-485 | E5ER-TQT3DW-FLK AC100-240 | E5ER-TQT3DW-FLK AC/DC24 |
SV programmer | max 2 | 2 | 4 | 2 | C+C | 2T | RS-485 | E5ER-TCT3DW-FLK AC100-240 | E5ER-TCT3DW-FLK AC/DC24 |
SV programmer + valve | 1 | 1 + pot | 4 | 2 | R+R | 2T | - | E5ER-TPRTDF AC100-240 | E5ER-TPRTDF AC/DC24 |
SV programmer + valve | 1 | 1 + pot | - | 3 | R+R+QC | 4R | RS-485 | E5ER-TPRQ43F-FLK AC100-240 | E5ER-TPRQ43F-FLK AC/DC24 |
- Note • Standard = heat and/or cool PID control, valve = valve positioning (relay up/down) (PRR)
- • max 2 = 2 loops heat and/or cool or 1 loop cascade, ratio or remote SP
- • max 4 = 4 loops heat and/or cool
- • 1, 2 or 4 = number of analog universal input 1 + pot = 1 universal and 1 slide wire feedback from valve
- • QC = voltage (pulse) or current (switch), Q = voltage (pulse), C = current, 4R = 4 two pole relay, 2T = two transistor output NPN
Accessories
Terminal covers | Order code |
---|
Terminal cover for E5AR | E53-COV14 |
Terminal cover for E5ER | E53-COV15 |
E5_R/E5_R-T optional tools
Option | Order code |
---|
PC based configuration and tuning software CX-Thermo | EST2-2C-MV4 |
Specifications
Item |
|
---|
Thermocouple input type | K, J, T, E, L, U, N, R, S, B, W |
RTD input type | Pt100 |
Linear input type | mA, V |
Control mode | 2-PID or ON/OFF control |
Accuracy | ±0.1% FS |
Auto-tuning | yes |
RS-485 | optional |
Event input | optional |
Ambient temperature | -10 to 55°C |
IP rating front panel | IP66 |
Sampling period | 50 ms |
Size in mm (H×W×D) | E5ER: 96×48×110 E5AR: 96×96×110 |