Standards | | | Specification for general requirements: IEC/EN 61800-2 EMC requirements: IEC/EN 61800-3 Safety requirements: IEC/EN 61800-5-1 |
Certifications | | | CE, UL, cUL, c-Tick, Ukr Sepro, EAC |
Production quality | | | RoHS, ISO 9001 |
Climatic proofing | ρw | % | < 95%, average relative humidity (RH), non-condensing, non-corrosive |
Ambient temperature | | | |
operation (150 % overload) | ϑ | °C | -10 - +50 |
Storage | ϑ | °C | -40 - +60 |
Mounting position | | | Vertical |
Altitude | | m | 0 - 1000 m above sea level Above 1000 m: 1% derating for every 100 m max. 4000 m |
Degree of Protection | | | IP20/NEMA 0 |
Protection against direct contact | | | BGV A3 (VBG4, finger- and back-of-hand proof) |
|
Supply | | | |
Rated operational voltage | Ue | | 230 V AC, 3-phase 240 V AC, 3-phase |
Mains voltage (50/60Hz) | ULN | V | 200 (-10%) - 240 (+10%) |
Input current (150% overload) | ILN | A | 3 |
System configuration | | | AC supply systems with earthed center point |
Supply frequency | fLN | Hz | 50/60 |
Frequency range | fLN | Hz | 48 - 62 |
Mains switch-on frequency | | | Maximum of one time every 30 seconds |
Power section | | | |
Function | | | Frequency inverter with internal DC link and IGBT inverter |
Overload current (150% overload) | IL | A | 3.45 |
max. starting current (High Overload) | IH | % | 175 |
Note about max. starting current | | | for 2 seconds every 20 seconds |
Output voltage with Ve | U2 | | 230 V AC, 3-phase 240 V AC, 3-phase |
Output Frequency | f2 | Hz | 0 - 50/60 (max. 500) |
Switching frequency | fPWM | kHz | 16 adjustable 4 - 32 (audible) |
Operation Mode | | | U/f control Speed control with slip compensation |
Frequency resolution (setpoint value) | Δf | Hz | 0.1 |
Rated operational current | | | |
At 150% overload | Ie | A | 2.3 |
Note | | | Rated operational current at an operating frequency of 16 kHz and an ambient air temperature of +50 °C |
Power loss | | | |
Heat dissipation at rated operational current | PV | W | 14.8 |
Efficiency | η | % | 96 |
Maximum leakage current to ground (PE) without motor | IPE | mA | < 1 |
Fitted with | | | 7-digital display assembly |
Frame size | | | FS1 |
Motor feeder | | | |
Note | | | for normal internally and externally ventilated 4 pole, three-phase asynchronous motors with 1500 rpm-1 at 50 Hz or 1800 min-1 at 60 Hz |
Note | | | Overload cycle for 60 s every 600 s |
Note | | | at 230 V, 50 Hz |
150 % Overload | P | kW | 0.37 |
Note | | | at 220 - 240 V, 60 Hz |
150 % Overload | P | HP | 0.5 |
maximum permissible cable length | I | m | screened: 50 screened, with motor choke: 100 unscreened: 75 unscreened, with motor choke: 150 |
Apparent power | | | |
Apparent power at rated operation 230 V | S | kVA | 0.92 |
Apparent power at rated operation 240 V | S | kVA | 0.96 |
Braking function | | | |
Standard braking torque | | | max. 30 % MN |
DC braking torque | | | adjustable to 100 % |
|
Reference voltage | Us | V | 10 V DC (max. 10 mA) |
Analog inputs | | | 2, parameterizable, 0 - 10 V DC, 0/4 - 20 mA |
Analog outputs | | | 1, parameterizable, 0 - 10 V |
Digital inputs | | | 4, parameterizable, max. 30 V DC |
Digital outputs | | | 1, parameterizable, 24 V DC |
Relay outputs | | | 1, parameterizable, N/O, 6 A (250 V, AC-1) / 5 A (30 V, DC-1) |
Interface/field bus (built-in) | | | OP-Bus (RS485)/Modbus RTU, CANopen® |
|
Power Wiring | | | |
IEC (Type B, gG), 150 % | | | FAZ-B6/3 |
UL (Class CC or J) | | A | 6 |
150 % overload (CT/IH, at 50 °C) | | | DX-LN3-004 |
Motor feeder | | | |
150 % overload (CT/IH, at 50 °C) | | | DX-LM3-005 |
150 % overload (CT/IH, at 50 °C) | | | DX-SIN3-004 |