ETR4-11-W 031883 XTTR6A100HS11N EATON ELECTRIC Timing relay, 1W, 0.05s-60h, on-delayed, 400VAC View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

ETR4-11-W 031883 XTTR6A100HS11N EATON ELECTRIC Timing relay, 1W, 0.05s-60h, on-delayed, 400VAC

ETR4-11-W

031883

XTTR6A100HS11N

EATON-MOELLER

Timing relay, 1W, 0.05s-60h, on-delayed, 400VAC

More details


Relays > Timer relay

Relay timers (KETR, KEMR, KESR)

* Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

Total price: $164.13
Unit price: $164.13

Quantity Price
1+$164.13
2+$143.21
3+$137.91
*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Timing relay, 1W, 0.05s-60h, on-delayed, 400VAC
Electronic timing relay according to IEC/EN 61812-1, VDE 0435, 22.5 mm wide, time range 0.05s-100h, mechanical lifespan 30 * 106, DIN top-hat rail mounting, any required mounting position, 400VAC, on-delayed, industry form factor

General specifications
Product name
Eaton Moeller® series ETR4 Timing relay
Part no.
ETR4-11-W
EAN
4015080318835
Product Length/Depth
103 millimetre
Product height
83 millimetre
Product width
23 millimetre
Product weight
0.107 kilogram
Certifications
VDE 0435
IEC/EN 61000-4-3
Standard IEC/EN 61812
IEC/EN 61000-4-2
Product Tradename
ETR4
Product Type
Timing relay
Product Sub Type
None
Catalog Notes
Making and breaking conditions to DC13, time constant as stated
When supplied directly from mains or transformer > 1000 VA
Features & Functions
Electric connection type
Screw connection
Functions
On-delayed
Delay-on energization
Fixed timing function
General information
Degree of protection
Terminals: IP20
IP20
Lifespan, mechanical
30,000,000 Operations (AC operated)
30,000,000 Operations (DC operated)
Mounting position
As required
Number of contacts (change-over contacts)
1
Overvoltage category
III
Pollution degree
2
Product category
ETR4 timing relays
Rated impulse withstand voltage (Uimp)
6000 V AC
Shock resistance
4 g, Make contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 20 ms
Suitable for
DIN rail (top hat rail) mounting
Terminal capacity
1 x (20 - 14) AWG, solid or stranded
1 x (0.5 - 2.5) mm², solid
1 x (0.5 - 2.5) mm², flexible with ferrule
2 x (0.5 - 1.5) mm², solid
2 x (0.5 - 1.5) mm², flexible with ferrule
Time range - min
0.05 s
Time range - max
360000 s
Type
Timer relay
Voltage type
AC
Climatic environmental conditions
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
60 °C
Ambient operating temperature (enclosed) - min
-25 °C
Ambient operating temperature (enclosed) - max
45 °C
Ambient storage temperature - min
-45 °C
Ambient storage temperature - max
85 °C
Climatic proofing
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Electro magnetic compatibility
Air discharge
8 kV
Burst impulse
According to IEC/EN 61000-4-4
2 kV, Supply cable
1 kV, Signal cable
Contact discharge
6 kV
Electromagnetic fields
1 V/m at 2.0 - 2.7 GHz (according to IEC EN 61000-4-3)
10 V/m at 80 - 1000 MHz (according to IEC EN 61000-4-3)
3 V/m at 1.4 - 2 GHz (according to IEC EN 61000-4-3)
Immunity to line-conducted interference
10 V (according to IEC/EN 61000-4-6)
Radio interference class
Class B (EN 55011, radiated)
Class B (EN 55011, conducted)
Surge rating
According to IEC/EN 61000-4-5, power pulses (Surge), EMC
4 kV, asymmetrical, power pulses (Surge), EMC
2 kV, symmetrical, power pulses (Surge), EMC
Electrical rating
Conventional thermal current ith of auxiliary contacts (1-pole, open)
6 A
Mains voltage tolerance
400 V AC (at 50/60 Hz)
Nominal current
3 A
Rated breaking capacity
1.1 x Iₑ (DC-11 L/R - 40 ms)
3 A at AC-15 (cos ϕ = 0.3 220 V)
3 A at AC-14 (cos ϕ = 0.3 440 V)
Rated insulation voltage (Ui)
600 V
Rated making capacity
48 A (AC-14 cos ϕ = 0.3 400 V)
1.1 x Iₑ (DC-11 L/R - 40 ms)
50 A (AC-15 cos ϕ = 0.3 220 V)
Rated operational current (Ie)
1.5 A at DC-11, 24 V
3 A at AC-14, 380 V 400 V 415 V
3 A at AC-15, 380 V 400 V 415 V
3 A at AC-15, 220 V 230 V 240 V
3 A at AC-14, 440 V
1.2 A at DC-11, L/R max. 50 ms
Rated operational voltage (Ue) at AC - max
440 V
Safe isolation
250 V AC, Between coil and auxiliary contacts, According to EN 61140
250 V AC, Between auxiliary contacts, According to EN 61140
Short-circuit protection rating
Max. 6 A gG/gL, fuse, Without welding, Contacts
Max. 6 A gG/gL, Fuse, Short-circuit rating without welding, Contacts
Magnet system
Command time
50 ms, AC
Contact changeover time
4 ms
Duty factor
100 %
Operating frequency
4000 Operations/h
Pick-up voltage
0.85 - 1.1 V AC x Uc
Power consumption
0.5 VA at AC (Sealing power)
0.5 VA at AC (Pick-up power)
Rated control supply voltage (Us) at AC, 50 Hz - min
400 V
Rated control supply voltage (Us) at AC, 50 Hz - max
400 V
Rated control supply voltage (Us) at AC, 60 Hz - min
400 V
Rated control supply voltage (Us) at AC, 60 Hz - max
400 V
Rated control supply voltage (Us) at DC - min
0 V
Rated control supply voltage (Us) at DC - max
0 V
Recovery time
70 ms (after 100 % time delay)
Repetition accuracy
≤ 0.5 % (deviation)
Design verification
Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
1.4 W
Rated operational current for specified heat dissipation (In)
6 A
Static heat dissipation, non-current-dependent Pvs
0.5 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 9.0

Relays (EG000019) / Timer relay (EC001439)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Relay and socket / Timer relay (ecl@ss13-27-37-16-05 [AKF092018])
Type of electric connection
Screw connection
Complete with socket
No
Suitable for DIN rail (top hat rail) mounting
Yes
Suitable for front mounting
No
Pluggable on auxiliary contact block
No
Function delay-on energization
Yes
Function delay on de-energization
No
Function floating contact on energization
No
Function floating contact on de-energization
No
Function star-delta
No
Function pulse shaping
No
Function flashing, starting with pause, fixed time
No
Function flashing, starting with pulse, fixed time
No
Clock function, starting with pause, variable
No
Clock function, starting with pulse, variable
No
Time range
0.05 - 360000 s
Remote operation possible
No
Suitable as remote control
No
Rated control supply voltage AC 50 Hz
400 - 400 V
Rated control supply voltage AC 60 Hz
400 - 400 V
Rated control supply voltage DC
0 - 0 V
Voltage type for actuating
AC
Number of outputs, undelayed, normally closed contact
0
Number of outputs, undelayed, normally open contact
0
Number of outputs, undelayed, change-over contact
0
Number of outputs, delayed, normally closed contact
0
Number of outputs, delayed, normally open contact
0
Number of outputs, delayed, change-over contact
1
Outputs, reversible delayed/undelayed
No
With semiconductor output
No
Material of contact insert
Material contact
Material of contact surface
Operating voltage AC 50 Hz
400 - 400 V
Operating voltage AC 60 Hz
400 - 400 V
Operating voltage DC
V
Voltage type (operating voltage)
AC
Nominal current
3 A
Max. starting current
A
Degree of protection (IP)
IP20
Relay technology category according to IEC 61810-7
Width
23 mm
Height
83 mm
Depth
103 mm

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.