INX40N3-40W 150084 EATON ELECTRIC Switch-disconnector, 3p, 4000 A, withdrawable View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

INX40N3-40W 150084 EATON ELECTRIC Switch-disconnector, 3p, 4000 A, withdrawable

INX40N3-40W

150084

EATON-MOELLER

Switch-disconnector, 3p, 4000 A, withdrawable

More details


Home > EATON - MOELLER

* Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Delivery programme
Product range
Air circuit-breakers/switch-disconnectors
Product range
Open switch-disconnectors
Current Range
Up to 4000 A
Installation type
Withdrawable
Construction size
INX40
Release system
without releases
Standard/Approval
IEC
Number of poles
3 pole
Degree of Protection
IP20, IP55 with protective cover, IP41 door sealing frame
optionally fittable by user with comprehensive accessories
Rated current = rated uninterrupted current
In= Iu A 4000
Making capacity Icm to 440 V 50/60 Hz
Icm kA 187
t = 1 s
Icw kA 85
t = 3 s
Icw kA 66
Technical data
General
Standards
IEC/EN 60947
Ambient temperature
Storage
ϑ °C -40 - +70
Ambient temperature
°C -25 - +70
Mounting position
>>
Utilization category
B
Degree of Protection
IP20, IP55 with protective cover, IP41 door sealing frame
Direction of incoming supply
as required
Main conducting paths
Rated current = rated uninterrupted current
In= Iu A 4000
Rated uninterrupted current at 50 °C
Iu A 4000
Rated uninterrupted current at 60 °C
Iu A 3650
Rated uninterrupted current at 70 °C
Iu A 3500
Rated impulse withstand voltage
Uimp V AC 12000
Rated operational voltage
Ue V AC 690
Overvoltage category/pollution degree
III/3
Rated insulation voltage
Ui V 1000
Switching capacity
Rated short-circuit making capacity
Icm
up to 440 V 50/60 Hz
Icm kA 187
up to 690 V 50/60 Hz
Icm kA 166
Rated short-time withstand current 50/60 Hz
Rated short-time withstand current (t=1s)
Icw kA 85
t = 3 s
Icw kA 66
Operating times
Closing delay via spring release
ms 35
Total opening delay via shunt release
ms 22
Total opening delay via undervoltage release
ms 37
Maximum operating frequency
Ops./h
Maximum operating frequency
Operations/h 60
Heat dissipation at rated current In
Withdrawable units (switch with cassette)
W 880
Weight
Withdrawable
3-pole
kg 70
4-pole
kg 86
Cassette
3 pole
kg 27
4 pole
kg 35
Terminal capacities
Copper bar
Withdrawable units
Black
mm 4 x 100 x 10
These are values used in separate switchgear. The actual values will depend on the temperature around the circuit-breaker, which is influenced by the ambient temperature, the degree of protection (IP), the mounting height, the partitions, and any external ventilation. Depending on the specific switchgear design, this may result in derating, which can then be compensated for by increasing the cross-sectional area. Temperature rise tests in the specific switchgear can provide specific and detailed information.
Design verification as per IEC/EN 61439(Show features)(Hide features)
Technical data for design verification
Rated operational current for specified heat dissipation
In A 4000
Equipment heat dissipation, current-dependent
Pvid W 880
Operating ambient temperature min.
°C -25
Operating ambient temperature max.
°C 70
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Technical data ETIM 6.0
Low-voltage industrial components (EG000017) / Switch disconnector (EC000216)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Off-load switch, circuit breaker, control switch / Switch disconnector ([email protected] [AKF060010])
Version as main switch
Yes
Version as maintenance-/service switch
No
Version as safety switch
No
Version as emergency stop installation
No
Version as reversing switch
No
Max. rated operation voltage Ue AC
V 690
Rated operating voltage
V 690 - 690
Rated permanent current Iu
A 4000
Rated permanent current at AC-21, 400 V
A 0
Rated operation power at AC-3, 400 V
kW 0
Rated short-time withstand current lcw
kA 85
Rated operation power at AC-23, 400 V
kW 0
Switching power at 400 V
kW 0
Conditioned rated short-circuit current Iq
kA 187
Number of poles
3
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
2
Motor drive optional
Yes
Motor drive integrated
No
Voltage release optional
Yes
Device construction
Built-in device slide-in technique (withdrawable)
Suitable for ground mounting
Yes
Suitable for front mounting 4-hole
No
Suitable for front mounting center
No
Suitable for distribution board installation
Yes
Suitable for intermediate mounting
No
Colour control element
Green
Type of control element
Push button
Interlockable
Yes
Type of electrical connection of main circuit
Rail connection
Degree of protection (IP), front side
IP20

Datasheet - PDF

Title: Size: Type:
PDF CATALOGUE EATON EN.pdf 51 Mbytes
36 Kbytes

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.