DMV-1000N/3 1814445 EATON ELECTRIC Switch-disconnector, 3 pole, 1000 A, Without rotary handle and drive shaf.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

DMV-1000N/3 1814445 EATON ELECTRIC Switch-disconnector, 3 pole, 1000 A, Without rotary handle and drive shaf..

DMV-1000N/3

1814445

EATON-MOELLER

Switch-disconnector, 3 pole, 1000 A, Without rotary handle and drive shaft, surface mounting

DMV-1000N/3

Switch-disconnector, DMV, 1000 A, 3 pole, Stop Function optional, Without rotary handle and drive shaft

More details


Low-voltage industrial components > Switch disconnector

DUMECO Switch-Disconnectors

* Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

Total price: $956.22
Unit price: $956.22

*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Switch-disconnector, DMV, 1000 A, 3 pole, Stop Function optional, Without rotary handle and drive shaft
Switch-disconnector, Product range: Switch-disconnector, Main switch, maintenance switch, Part group reference: DMV, Stop Function: optional, Without rotary handle and drive shaft, Notes: visible contacts, Information about equipment supplied: auxiliary contact fitted by user., including connection materials, 3 pole, Degree of Protection: IP00, IP20 with terminal cover, Design: surface mounting, Motor rating AC-23A, 50 - 60 Hz 400 V: P = 425 kW, Rated uninterrupted current: Iu = 1000 A, Standards: IEC/EN 60947, VDE 0660, IEC/EN 60204, Switch-disconnector according to IEC/EN 60947-3

General specifications
Product name
Eaton DMV Switch-disconnector
Part no.
DMV-1000N/3
EAN
8711426529441
Product Length/Depth
305 millimetre
Product height
107 millimetre
Product width
256 millimetre
Product weight
4.96 kilogram
Certifications
IEC/EN 60947
KEMA
IEC/EN 60947-3
Lloyds
RoHS
IEC/EN 60204
EAC
VDE 0660
CE
Product Tradename
DMV
Product Type
Switch-disconnector
Product Sub Type
None
Catalog Notes
Current for a time of 0.3 seconds
visible contacts
Without rotary handle and drive shaft
Features & Functions
Features
Version as main switch
Version as maintenance-/service switch
Version as emergency stop installation
Functions
Optional Stop Function
Number of poles
Three-pole
General information
Accessories
Auxiliary contact fitted by user.
Connection materials included with supplied equipment.
Actuator color
Other
Actuator type
Other
Degree of protection
NEMA Other
Degree of protection (front side)
IP20
Lifespan, mechanical
5,000 Operations
Mounting method
Surface mounting
Mounting position
As required
Overvoltage category
III
Pollution degree
3
Product Category
Main switch
Switch-disconnector
Rated impulse withstand voltage (Uimp)
12000 V
Safety parameter (EN ISO 13849-1)
B10d values as per EN ISO 13849-1, table C.1
Suitable for
Distribution board installation
Ground mounting
Climatic environmental conditions
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
55 °C
Ambient storage temperature - min
-30 °C
Ambient storage temperature - max
80 °C
Terminal capacities
Terminal capacity
600 mm², Flat conductor connection with busbars
Screw size
M12 x 35, Terminal screw
Tightening torque
28 Nm, Screw terminals
Electrical rating
Rated breaking capacity at 400/415 V (cos phi to IEC 60947-3)
6072 A
Rated breaking capacity at 500 V (cos phi to IEC 60947-3)
4600 A
Rated breaking capacity at 660/690 V (cos phi to IEC 60947-3)
3496 A
Rated insulation voltage (Ui)
1000 V
Rated operational current (Ie) at AC-21, 400 V, 415 V
1000 A
Rated operational current (Ie) at AC-21, 500 V
1000 A
Rated operational current (Ie) at AC-21, 690 V
1000 A
Rated operational current (Ie) at AC-22, 380 V, 400 V, 415 V
1000 A
Rated operational current (Ie) at AC-22, 500 V
1000 A
Rated operational current (Ie) at AC-22, 690 V
1000 A
Rated operational current (Ie) at AC-23A, 400 V, 415 V
759 A
Rated operational current (Ie) at AC-23A, 500 V
575 A
Rated operational current (Ie) at AC-23A, 690 V
437 A
Rated operational power at AC-23A, 400 V, 50 Hz
425 kW
Rated operational power at AC-23A, 500 V, 50 Hz
425 kW
Rated operational power at AC-23A, 690 V, 50 Hz
425 kW
Rated operational power at AC-3, 380/400 V, 50 Hz
0 kW
Rated operational voltage (Ue) at AC - max
690 V
Rated uninterrupted current (Iu)
1000 A
Uninterrupted current
Rated uninterrupted current Iu is specified for max. cross-section.
Short-circuit rating
Breaking current
65 kA (at In = 630)
70 kA (at In = 1000)
Let-through energy
Max. 4200 kA²s (at In = 1000)
Max. 3200 kA²s (at In = 630)
Rated conditional short-circuit current (Iq)
100 kA
50 kA at In = 1000
Rated short-time withstand current (Icw)
36 kA
36 kA, Contacts, 1 second
Short-circuit protection rating
1000/630, Fuse, Contacts
Contacts
Number of auxiliary contacts (change-over contacts)
0
Number of auxiliary contacts (normally closed contacts)
0
Number of auxiliary contacts (normally open contacts)
0
Design verification
Equipment heat dissipation, current-dependent Pvid
35.3 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
44.75 W
Rated operational current for specified heat dissipation (In)
1000 A
Static heat dissipation, non-current-dependent Pvs
0 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 9.0

Low-voltage industrial components (EG000017) / Switch disconnector (low voltage) (EC000216)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Off-load switch, circuit breaker, control switch / Switch disconnector (ecl@ss13-27-37-14-03 [AKF060018])
Version as main switch
Yes
Version as maintenance-/service switch
Yes
Version as safety switch
No
Version as emergency stop installation
Yes
Version as reversing switch
No
Number of switches
1
Max. rated operation voltage Ue AC
690 V
Rated operating voltage
690 - 690 V
Rated permanent current Iu
1000 A
Rated permanent current at AC-23, 400 V
759 A
Rated permanent current at AC-21, 400 V
1000 A
Rated operation power at AC-3, 400 V
0 kW
Rated short-time withstand current lcw
36 kA
Rated operation power at AC-23, 400 V
425 kW
Switching power at 400 V
375 kW
Conditioned rated short-circuit current Iq
100 kA
Number of poles
3
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Motor drive optional
No
Motor drive integrated
No
Voltage release optional
No
Device construction
Complete device in housing
Suitable for floor mounting
Yes
Suitable for front mounting 4-hole
No
Suitable for front mounting centre
No
Suitable for distribution board installation
Yes
Suitable for intermediate mounting
No
Colour control element
Other
Type of control element
Other
Interlockable
No
Type of electrical connection of main circuit
Screw connection
With pre-assembled cabling
No
Degree of protection (IP), front side
IP20
Degree of protection (NEMA)
Other
Width
256 mm
Height
107 mm
Depth
305 mm
Width in number of modular spacings

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.