DS7-342SX100N0-N 134938 EATON MOELLER Soft starter, 3p, 100A, 200-480VAC, us 110/230VAC View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

DS7-342SX100N0-N 134938 EATON MOELLER Soft starter, 3p, 100A, 200-480VAC, us 110/230VAC

DS7-342SX100N0-N

134938

EATON - MOELLER

Available

Ship on today

Soft starter, 3p, 100A, 200-480VAC, us=110/230VAC

More details


Softstarters Soft Starters Motor

Soft starters - EATON - MOELLER

DS - EATON - MOELLER

* Brand new produt in its original packing covered by the warranties and certifications provided by EATON - MOELLER

QuantityPrice
1+$601.74
2+$597.58
*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Delivery programme
Description
  With internal bypass contacts
Function
  Soft starters for three-phase loads
Mains supply voltage (50/60 Hz)
ULNV AC200 - 480
Supply voltage
Us 110 - 230 V AC
Control voltage
UC 110 - 230 V AC
Assigned motor rating (Standard connection, In-Line)
   
at 400 V, 50 Hz
PkW55
at 460 V, 60 Hz
PHP75
Rated operational current
   
AC-53
IeA100
Startup class
  CLASS 10 (star-delta replacement)
CLASS 20 (heavy starting duty 3 x Ie for 45 s)
Rated operational voltage
Ue 200 V
230 V
400 V
480 V
Connection to SmartWire-DT
  no
Technical data
General
Standards
  IEC/EN 60947-4-2
UL 508
CSA22.2-14
Approvals
  CE
Approvals
  UL
CSA
C-Tick
UkrSEPRO
Climatic proofing
  Damp heat, constant, to IEC 60068-2-3
Damp heat, cyclic, to IEC 60068-2-10
Ambient temperature
   
Operation
ϑ°C-5 - +40
up to 60 at 2% derating per Kelvin temperature rise
Storage
ϑ°C-25 - +60
Altitude
 m0 - 1000 m, above that 1 % derating per 100 m , up to 2000 m
Mounting position
  Vertical
Degree of protection
   
Degree of Protection
  IP20 (terminals IP00)
Integrated
  Protection type IP40 can be achieved on all sides with covers from the NZM range.
Protection against direct contact
  Finger- and back-of-hand proof
Overvoltage category/pollution degree
  II/2
Shock resistance
  8 g/11 ms
Vibration resistance to EN 60721-3-2
  2M2
Radio interference level (IEC/EN 55011)
  A
Static heat dissipation, non-current-dependent
PvsW25
Weight
 kg1.8
Main conducting paths
Rated operating voltage
UeV AC200 - 480
Supply frequency
fLNHz50/60
Rated operational current
IeA 
AC-53
IeA100
Assigned motor rating (Standard connection, In-Line)
   
at 230 V, 50 Hz
PkW30
at 400 V, 50 Hz
PkW55
at 200 V, 60 Hz
PHP30
at 230 V, 60 Hz
PHP30
at 460 V, 60 Hz
PHP75
Overload cycle to IEC/EN 60947-4-2
   
AC-53a
  99 A: AC-53a: 3 - 5: 75 - 10
Internal bypass contacts
  
Technical data for design verification
   
Rated operational current for specified heat dissipation
InA100
Heat dissipation per pole, current-dependent
PvidW0
Equipment heat dissipation, current-dependent
PvidW25
Static heat dissipation, non-current-dependent
PvsW25
Heat dissipation capacity
PdissW0
Operating ambient temperature min.
 °C-5
Operating ambient temperature max.
 °C40
IEC/EN 61439 design verification
   
10.2 Strength of materials and parts
   
10.2.2 Corrosion resistance
  Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
  Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
  Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
  Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
  Meets the product standard's requirements.
10.2.5 Lifting
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
  Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
  Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
  Meets the product standard's requirements.
10.5 Protection against electric shock
  Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
  Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
  Is the panel builder's responsibility.
10.8 Connections for external conductors
  Is the panel builder's responsibility.
10.9 Insulation properties
   
10.9.2 Power-frequency electric strength
  Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
  Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
  Is the panel builder's responsibility.
10.10 Temperature rise
  The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
  Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
  Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
  The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Technical data ETIM 6.0(Show features)(Hide features)
Low-voltage industrial components (EG000017) / Soft starter (EC000640)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Load breakout, motor breakout / Semiconductor motor controller or soft starter ([email protected] [ACO300008])
Rated operation current Ie at 40 °C Tu
 A100
Rated operating voltage Ue
 V230 - 460
Rated power three-phase motor, inline, at 230 V
 kW30
Rated power three-phase motor, inline, at 400 V
 kW55
Rated power three-phase motor, inside delta, at 230 V
 kW0
Rated power three-phase motor, inside delta, at 400 V
 kW0
Internal bypass
  Yes
With display
  No
Torque control
  No
Rated surrounding temperature without derating
 °C40
Rated control supply voltage Us at AC 50HZ
 V110 - 230
Rated control supply voltage Us at AC 60HZ
 V110 - 230
Rated control supply voltage Us at DC
 V0 - 0
Voltage type for actuating
  AC
Integrated motor overload protection
  No
Approvals
Product Standards  IEC/EN 60947-4-2; GB 14048.6; UL 508; CSA-C22.2 No 0-M91; CSA-C22.2 No 14-05 CE marking
UL File No.  E251034
CSA File No.  2511305
CSA Class No.  321106
Specially designed for North America  No
Suitable for  Branch circuits
Current Limiting Circuit-Breaker  No
Max. Voltage Rating  480 V
Degree of Protection  IP20; UL/CSA Type 1
Dimensions
IL03902005Z Instructions for DS7 Soft Starter
 
>
>
>>

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields

or