Sine filter, 3p, 400VAC, 90A, for FU

More details


Variable Adjustable Frequency Speed Drives Inverters Vfd Vvvf Voltage

Frequency inverters - EATON - MOELLER

Frequency inverters M-MAX - EATON - MOELLER

* Brand new produt in its original packing covered by the warranties and certifications provided by EATON - MOELLER

*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Delivery programme
Product range
  Accessories
Accessories
  Sine filter
Description
  three-phase
For use with
  DA1, DL1, DG1, SVX, SPX
Max. permissible connection voltage
 V AC520 V + 0% (0 - 150 Hz)
Rated operational current
IeA90
Inductance
LmH0.8
Maximum heat dissipation
PvW290
Design verification as per IEC/EN 61439(Show features)(Hide features)
Technical data for design verification
   
Rated operational current for specified heat dissipation
InA90
Heat dissipation per pole, current-dependent
PvidW0
Equipment heat dissipation, current-dependent
PvidW290
Static heat dissipation, non-current-dependent
PvsW0
Heat dissipation capacity
PdissW0
Operating ambient temperature min.
 °C0
IEC/EN 61439 design verification
   
10.2 Strength of materials and parts
   
10.2.2 Corrosion resistance
  Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
  Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
  Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
  Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
  Meets the product standard's requirements.
10.2.5 Lifting
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
  Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
  Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
  Meets the product standard's requirements.
10.5 Protection against electric shock
  Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
  Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
  Is the panel builder's responsibility.
10.8 Connections for external conductors
  Is the panel builder's responsibility.
10.9 Insulation properties
   
10.9.2 Power-frequency electric strength
  Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
  Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
  Is the panel builder's responsibility.
10.10 Temperature rise
  The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
  Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
  Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
  The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Technical data ETIM 6.0(Show features)(Hide features)
Low-voltage industrial components (EG000017) / Accessories for frequency controller (EC002025)
Electric engineering, automation, process control engineering / Electrical drive / Electrical drive (accessories) / Frequency controller (accessories) ([email protected] [ACN127008])
Type of accessory
  Filter
Approvals
Product Standards  UL 508C; CSA-C22.2 No. 14; IEC/EN61800-3; IEC/EN61800-5; CE marking
UL File No.  E300273
UL Category Control No.  NMTR2, NMTR8
CSA File No.  UL report applies to both US and Canada
North America Certification  UL listed, certified by UL for use in Canada
Specially designed for North America  No
Suitable for  Branch circuits
Max. Voltage Rating  1~ 240 V AC IEC: TN-S UL/CSA: Y (Solidly Grounded Wey), 3~ 240 V AC IEC: TN-S UL/CSA: Y (Solidly Grounded Wey), 3~ 480 V AC IEC: TN-S UL/CSA: Y (Solidly Grounded Wey)
Degree of Protection  IEC: IP00
Dimensions
IL00906001Z Sine filter
 
>
>
>
>
>
>
>>