A-PKZ0(*V60HZ) 982166 EATON ELECTRIC Star-delta contactor combination, 132kW/400V/AC3 View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

A-PKZ0(*V60HZ) 982166 EATON ELECTRIC Star-delta contactor combination, 132kW/400V/AC3

A-PKZ0(*V60HZ)

982166

-

EATON-MOELLER

Star-delta contactor combination, 132kW/400V/AC3

Trigger coil; Shunt; *V 60 Hz

Shunt release (for power circuit breaker), …V 60 Hz (24 - 600 V), Non-standard voltages outside standard voltages, AC, Screw terminals, For use with: Shunt release PKZ0(4), PKE

More details


Low-voltage industrial components > Shunt release (for power circuit breaker)

Motor-protective circuit-breakers PKZ (Accessories)

* Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Shunt release (for power circuit breaker), …V 60 Hz (24 - 600 V), Non-standard voltages outside standard voltages, AC, Screw terminals, For use with: Shunt release PKZ0(4), PKE
Shunt release with screw terminals, for circuit-breaker PKZ(M)0 size, non-standard voltage

Delivery program

Product range
Accessories
Accessories
Shunt release
Actuating voltage
…V 60 Hz (24 - 600 V)
Voltage type
Non-standard voltages outside standard voltages
Current actuation
AC
Contact sequence
121S017
Connection technique
Screw terminals
For use with
Shunt release PKZ0(4), PKE
For use with
PKZM0
PKZM4
PKZM0-T
PKM0
PKZM01
PKE
For non-standard voltages, the required actuation voltage from the specified range (...-...V) must be indicated in the * for the part no.
Notes
Can be fitted to the left of:
Motor protective circuit-breaker
Cannot be combined with:
U‐PKZ0 undervoltage release

Technical data

General
Terminal capacitiesSolid or flexible conductor, with ferrule
1 x (0,75 - 2,5)
2 x (0,75 - 2,5) mm2
Terminal capacitiesSolid or stranded
1 x (18 - 14)
2 x (18 - 14) AWG
Actuating voltage
…V 60 Hz (24 - 600 V)
Operating range
Alternating voltage
0.7- 1.1 x US
Power consumption
ACPull-in power [Pick-up]
5 VA
ACSealing power [Sealing]
3 VA

Design verification as per IEC/EN 61439

Technical data for design verification
Rated operational current for specified heat dissipation [In]
0 A
Heat dissipation per pole, current-dependent [Pvid]
0 W
Equipment heat dissipation, current-dependent [Pvid]
0 W
Static heat dissipation, non-current-dependent [Pvs]
0.5 W
Heat dissipation capacity [Pdiss]
0 W
Operating ambient temperature min.
-25 °C
Operating ambient temperature max.
+55 °C
IEC/EN 61439 design verification
10.2 Strength of materials and parts10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9 Insulation properties10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9 Insulation properties10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 7.0

Low-voltage industrial components (EG000017) / Shunt release (for power circuit breaker) (EC001023)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Circuit breaker (LV < 1 kV) / Full load current trip ([email protected] [AKF016013])
Rated control supply voltage Us at AC 50HZ
0 - 0 V
Rated control supply voltage Us at AC 60HZ
24 - 600 V
Rated control supply voltage Us at DC
0 - 0 V
Voltage type for actuating
AC
Initial value of the undelayed short-circuit release - setting range
0 A
End value adjustment range undelayed short-circuit release
0 A
Type of electric connection
Screw connection
Number of contacts as normally open contact
0
Number of contacts as normally closed contact
0
Number of contacts as change-over contact
0
Suitable for power circuit breaker
No
Suitable for off-load switch
No
Suitable for motor safety switch
Yes
Suitable for overload relay
No

Approvals

Product Standards
UL 508; CSA-C22.2 No. 14; IEC60947-4-1; CE marking
UL File No.
E36332
UL Category Control No.
NLRV
CSA File No.
165628
CSA Class No.
3211-05
North America Certification
UL listed, CSA certified
Specially designed for North America
No

Characteristics

121O006
Accessories
1: Motor-protective circuit-breakers

Dimensions

121X008

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.