LSM-11 266144 EATON MOELLER Safety position switch, metal, 1N/O+1N/C, +rounded plunger View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

LSM-11 266144 EATON MOELLER Safety position switch, metal, 1N/O+1N/C, +rounded plunger

LSM-11

266144

EATON - MOELLER

Available

Ship on today

Safety position switch, metal, 1N/O+1N/C, +rounded plunger

More details


Limit Switches

Position switches - EATON - MOELLER

Metal Box LS position switches - EATON - MOELLER

* Brand new produt in its original packing covered by the warranties and certifications provided by EATON - MOELLER

QuantityPrice
1+$23.05
8+$20.69
16+$20.18
24+$19.93
32+$19.76
*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Delivery programme
Basic function
  Position switches
Safety position switches
Part group reference
  LS(M)-…
Product range
  Rounded plunger
Degree of Protection
  IP66, IP67
Features
  Basic device, expandable
Ambient temperature
 °C-25 - +70
Design
  EN 50047 Form B
Contacts
   
N/O = Normally open
  1 N/O
N/C = Normally closed
  1 NC
General
Standards
  IEC/EN 60947
Climatic proofing
  Damp heat, constant, to IEC 60068-2-78; damp heat, cyclical, to IEC 60068-2-30
Ambient temperature
 °C-25 - +70
Mounting position
  As required
Degree of Protection
  IP66, IP67
Terminal capacities
 mm2 
Solid
 mm21 x (0.5 - 2.5)
Flexible with ferrule
 mm21 x (0.5 - 1.5)
Contacts/switching capacity
Rated impulse withstand voltage
UimpV AC4000
Rated insulation voltage
UiV400
Overvoltage category/pollution degree
  III/3
Rated operational current
IeA 
AC-15
   
24 V
IeA6
220 V 230 V 240 V
IeA6
380 V 400 V 415 V
IeA4
DC-13
   
24 V
IeA3
110 V
IeA0.6
220 V
IeA0.3
Control circuit reliability
   
at 24 V DC/5 mA
HFFault probability< 10 -7, < 1 fault in 107 operations
at 5 V DC/1 mA
HFFault probability< 10-6, < 1 failure at 5 x 106 operations
Supply frequency
 Hzmax. 400
Short-circuit rating to IEC/EN 60947-5-1
   
max. fuse
 A gG/gL6
Repetition accuracy
 mm0.15
Rated conditional short-circuit current
 kA1
Mechanical variables
Lifespan, mechanical
Operationsx 1068
Contact temperature of roller head
 °C
Technical data for design verification
   
Rated operational current for specified heat dissipation
InA6
Heat dissipation per pole, current-dependent
PvidW0.17
Equipment heat dissipation, current-dependent
PvidW0
Static heat dissipation, non-current-dependent
PvsW0
Heat dissipation capacity
PdissW0
Operating ambient temperature min.
 °C-25
Operating ambient temperature max.
 °C70
IEC/EN 61439 design verification
   
10.2 Strength of materials and parts
   
10.2.2 Corrosion resistance
  Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
  Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
  Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
  Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
  Meets the product standard's requirements.
10.2.5 Lifting
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
  Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
  Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
  Meets the product standard's requirements.
10.5 Protection against electric shock
  Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
  Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
  Is the panel builder's responsibility.
10.8 Connections for external conductors
  Is the panel builder's responsibility.
10.9 Insulation properties
   
10.9.2 Power-frequency electric strength
  Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
  Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
  Is the panel builder's responsibility.
10.10 Temperature rise
  The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
  Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
  Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
  The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Technical data ETIM 6.0(Show features)(Hide features)
Sensors (EG000026) / End switch (EC000030)
Electric engineering, automation, process control engineering / Binary sensor technology, safety-related sensor technology / Position switch / Position switch (Type 1) ([email protected] [AGZ382012])
Width sensor
 mm31
Diameter sensor
 mm0
Height of sensor
 mm61
Length of sensor
 mm33.5
Rated operation current Ie at AC-15, 24 V
 A6
Rated operation current Ie at AC-15, 125 V
 A6
Rated operation current Ie at AC-15, 230 V
 A6
Rated operation current Ie at DC-13, 24 V
 A3
Rated operation current Ie at DC-13, 125 V
 A0.8
Rated operation current Ie at DC-13, 230 V
 A0.3
Switching function
  Slow-action switch
Output electronic
  No
Forced opening
  Yes
Number of safety auxiliary contacts
  0
Number of contacts as normally closed contact
  1
Number of contacts as normally open contact
  1
Number of contacts as change-over contact
  0
Type of interface
  None
Type of interface for safety communication
  None
Housing according to norm
  DIN EN 50047
Construction type housing
  Cuboid
Material housing
  Metal
Coating housing
  -
Type of control element
  Plunger
Alignment of the control element
  -
Type of electric connection
  Cable entry metrical
With status indication
  No
Suitable for safety functions
  Yes
Explosion safety category for gas
  None
Explosion safety category for dust
  None
Ambient temperature during operating
 °C-25 - 70
Degree of protection (IP)
  IP67
Approvals
Product Standards  IEC/EN 60947-5; UL 508; CSA-C22.2 No. 14; CE marking
UL File No.  E29184
UL Category Control No.  NKCR
CSA File No.  12528
CSA Class No.  3211-03
North America Certification  UL listed, CSA certified
Degree of Protection  IEC: IP66, 67, UL/CSA Type 3R, 4X (indoor use only), 12, 13
Dimensions
>

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields

or