NZM3-XR208-240AC 259850 EATON MOELLER Remote operator, 208-240VAC, for size 3 View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

NZM3-XR208-240AC 259850 EATON MOELLER Remote operator, 208-240VAC, for size 3

NZM3-XR208-240AC

259850

EATON - MOELLER

Available

Ship on today

Remote operator, 208-240VAC, for size 3

More details


Circuit Breakers Electrical Power

Circuit-breakers NZM and LZM (Accessories) - EATON - MOELLER

Remote operators 208-240V 50/60Hz - EATON - MOELLER

* Brand new produt in its original packing covered by the warranties and certifications provided by EATON - MOELLER

*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Delivery programme
Product range
  Accessories
Accessories
  Remote operator, can be synchronized
Rated operating frequency
  AC 50/60 Hz
Standard/Approval
  UL/CSA, IEC
Construction size
  NZM3
Description
  

For remote switching of circuit-breakers and switch-disconnectors.

ON and OFF switching and resetting by means of two-wire or three-wire control.

Local switching by hand possible.

Lockable in the 0 position of the remote operator with up to 3 padlocks (hasp thickness: 4 – 8 mm)

Can be synchronized

 Please note during engineering:
Three-wire controlTerminal 70/71:
 
Remote operator
Rated control voltage
UsV 
AC
UsV AC208-240
Operating range
   
AC
 x Us0.85 - 1.1
DC
 x Us0.85 - 1.1
Current heat loss per pole at I u
PkWh 
AC
   
110 V … 130 V AC
 VA350
DC
 x Us 
24 V … 30 V DC
 W250
Minimum signal duration
   
with switch on
 ms30
with switch off
 ms250
Lifespan, mechanical
Operations 15000
Maximum operating frequency
 Ops./h 
Max. operating frequency
 Ops/h60
Terminal capacities
 mm2 
Solid or flexible conductor, with ferrule
 mm20,75 - 2,5
 
 AWG18 … 14
Design verification as per IEC/EN 61439(Show features)(Hide features)
IEC/EN 61439 design verification
   
10.2 Strength of materials and parts
   
10.2.2 Corrosion resistance
  Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
  Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
  Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
  Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
  Meets the product standard's requirements.
10.2.5 Lifting
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
  Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
  Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
  Meets the product standard's requirements.
10.5 Protection against electric shock
  Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
  Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
  Is the panel builder's responsibility.
10.8 Connections for external conductors
  Is the panel builder's responsibility.
10.9 Insulation properties
   
10.9.2 Power-frequency electric strength
  Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
  Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
  Is the panel builder's responsibility.
10.10 Temperature rise
  The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
  Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
  Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
  The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Technical data ETIM 6.0
Low-voltage industrial components (EG000017) / Motor operator for power circuit-breaker (EC001030)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Circuit breaker (LV < 1 kV) / Electrical drive for circuit breakers ([email protected] [AKF010010])
Type of switch drive
  Motor drive
Rated control supply voltage Us at AC 50HZ
 V208 - 240
Rated control supply voltage Us at AC 60HZ
 V208 - 240
Rated control supply voltage Us at DC
 V0 - 0
Voltage type for actuating
  AC
Approvals
Product Standards  UL489; CSA-C22.2 No. 5-09; IEC60947, CE marking
UL File No.  E140305
UL Category Control No.  DIHS
CSA File No.  022086
CSA Class No.  1437-01
North America Certification  UL listed, CSA certified
Dimensions
IL01208006Z (AWA1230-2018) NZM3 remote operator
 
>>

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields

or