ZEB32-1,65/KK 136494 EATON MOELLER Overload relay, electronic, 0.33-1.65A, separate mounting View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

ZEB32-1,65/KK 136494 EATON MOELLER Overload relay, electronic, 0.33-1.65A, separate mounting

ZEB32-1,65/KK

136494

EATON - MOELLER

Available

Ship on today

Product on demand only, returns will not be accepted.

Overload relay, electronic, 0.33-1.65A, separate mounting

More details


Contactor Relays

DIL Contactors - EATON - MOELLER

Electronic Motor-Protective Relay Unit ZEB - EATON - MOELLER

* Brand new produt in its original packing covered by the warranties and certifications provided by EATON - MOELLER

QuantityPrice
1+$55.45
3+$52.95
5+$52.04
7+$51.51
9+$51.19
*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Delivery programme
Product range
  Electronic overload relays ZEB
Phase-failure sensitivity
  IEC/EN 60947, VDE 0660 Part 102
Description
  Test/off button
Reset pushbutton
Manual/auto reset selectable
Protection with heavy starting duty (Class 10A-30)
Mounting type
  Separate mounting
Earth-fault protection
   
Earth-fault protection
  none
Setting range
   
Overload releases
General
Standards
  IEC/EN 60947, VDE 0660, UL, CSA
Climatic proofing
  Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature
   
Open
 °C-25 - +65
Ambient temperature open max.
 °C65
Mechanical shock resistance
 g15
Shock duration 10 ms
according to IEC 60068-2-27
Degree of Protection
  IP20
Protection against direct contact when actuated from front (EN 50274)
  Finger and back-of-hand proof
Main conducting paths
Rated impulse withstand voltage
UimpV AC6000
Overvoltage category/pollution degree
  III/3
Rated insulation voltage
UiV AC690
Rated operational voltage
UeV AC690
Rated frequency
fHz50/60
Safe isolation to EN 61140
   
Between auxiliary contacts and main contacts
 V AC600
Between main circuits
 V AC600
Terminal capacities
 mm2 
Solid
 mm21 x 1.5 - 16
Solid or stranded
 AWG1 x 14 - 4
Auxiliary and control circuits
Rated impulse withstand voltage
UimpV6000
Overvoltage category/pollution degree
  III/3
Terminal capacities
 mm2 
Solid
 mm22 x (0.75 - 4)
Flexible with ferrule
 mm22 x (0.75 - 2.5)
Solid or stranded
 AWG2 x (18 - 12)
Terminal screw
  M3.5
Tightening torque
 Nm0.8 - 1.2
Tightening torque
 lb-in7
Tools
   
Pozidriv screwdriver
 Size2
Standard screwdriver
 mm1 x 6
Rated insulation voltage
UiV AC500
Rated operational voltage
UeV AC500
Safe isolation to EN 61140
   
between the auxiliary contacts
 V AC240
Conventional thermal current
IthA5
Rated operational current
IeA 
AC-15
   
Make contact
   
120 V
IeA1.5
220 V 230 V 240 V
IeA1.5
380 V 400 V 415 V
IeA0.5
500 V
IeA0.5
Break contact
   
120 V
IeA1.5
220 V 230 V 240 V
IeA1.5
380 V 400 V 415 V
IeA0.9
500 V
IeA0.8
DC-13 L/R - 15 ms
   
24 V
IeA0.9
60 V
IeA0.75
110 V
IeA0.4
220 V
IeA0.2
Short-circuit rating without welding
   
max. fuse
 A gG/gL6
Design verification as per IEC/EN 61439(Show features)(Hide features)
Technical data for design verification
   
Rated operational current for specified heat dissipation
InA1.65
Heat dissipation per pole, current-dependent
PvidW0.17
Equipment heat dissipation, current-dependent
PvidW0.5
Static heat dissipation, non-current-dependent
PvsW0
Heat dissipation capacity
PdissW0
Operating ambient temperature min.
 °C-25
Operating ambient temperature max.
 °C65
IEC/EN 61439 design verification
   
10.2 Strength of materials and parts
   
10.2.2 Corrosion resistance
  Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
  Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
  Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
  Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
  Meets the product standard's requirements.
10.2.5 Lifting
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
  Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
  Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
  Meets the product standard's requirements.
10.5 Protection against electric shock
  Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
  Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
  Is the panel builder's responsibility.
10.8 Connections for external conductors
  Is the panel builder's responsibility.
10.9 Insulation properties
   
10.9.2 Power-frequency electric strength
  Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
  Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
  Is the panel builder's responsibility.
10.10 Temperature rise
  The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
  Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
  Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
  The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Technical data ETIM 6.0(Show features)(Hide features)
Low-voltage industrial components (EG000017) / Electronic overload relay (EC001080)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Overload protection device / Electronic overload relay ([email protected] [AKF076011])
Adjustable current range
 A0.33 - 1.65
Mounting method
  Separate positioning
Type of electrical connection of main circuit
  Screw connection
Number of auxiliary contacts as normally closed contact
  1
Number of auxiliary contacts as normally open contact
  1
Number of auxiliary contacts as change-over contact
  0
Rated control supply voltage Us at AC 50HZ
 V0 - 0
Rated control supply voltage Us at AC 60HZ
 V0 - 0
Rated control supply voltage Us at DC
 V0 - 0
Release class
  Adjustable
Voltage type for actuating
  Selfsupplied
Approvals
Product Standards  UL 508; CSA-C22.2 No. 14; IEC/EN 60947-4-1; CE marking
UL File No.  E1230
UL Category Control No.  NKCR
CSA File No.  2290956
CSA Class No.  3211-03
North America Certification  UL listed, CSA certified
Specially designed for North America  No
Suitable for  Branch circuits
Max. Voltage Rating  600 V AC
Degree of Protection  IEC: IP20, UL/CSA Type: -
Dimensions
IL04210002E Solid-state motor protection relay
 
>>

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields

or