ZB32-0,6 278445 EATON MOELLER Overload relay, 0.4-0.6A, 1N/O+1N/C View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

ZB32-0,6 278445 EATON MOELLER Overload relay, 0.4-0.6A, 1N/O+1N/C

ZB32-0,6

278445

EATON - MOELLER

Available

Ship on today

Overload relay, 0.4-0.6A, 1N/O+1N/C

More details


Contactor Relays

DIL Contactors - EATON - MOELLER

ZB and Z5 Relays- EATON - MOELLER

* Brand new produt in its original packing covered by the warranties and certifications provided by EATON - MOELLER

QuantityPrice
1+$31.88
4+$29.87
8+$29.14
12+$28.78
16+$28.58
*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Delivery programme
Product range
  Overload relay ZB up to 150 A
Frame size
  ZB32
Phase-failure sensitivity
  IEC/EN 60947, VDE 0660 Part 102
Description
  Test/off button
Reset pushbutton manual/auto
Trip-free release
Mounting type
  Direct mounting
Fitted directly to the contactorSeparate mounting
 
General
Standards
  IEC/EN 60947, VDE 0660, UL, CSA
Climatic proofing
  Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature
   
 
  Operating range to IEC/EN 60947
PTB: -5 °C - +55 °C
Open
 °C-25 - +55
Enclosed
 °C- 25 - 40
Temperature compensation
  Continuous
Weight
 kg0.15
Mechanical shock resistance
 g10
Sinusoidal
Shock duration 10 ms
Degree of Protection
  IP20
Protection against direct contact when actuated from front (EN 50274)
  Finger and back-of-hand proof
Main conducting paths
Rated impulse withstand voltage
UimpV AC6000
Overvoltage category/pollution degree
  III/3
Rated insulation voltage
UiV690
Rated operational voltage
UeV AC690
Safe isolation to EN 61140
   
Between auxiliary contacts and main contacts
 V AC440
Between main circuits
 V AC440
Temperatur compensation residual error > 40 ºC
  
Technical data for design verification
   
Rated operational current for specified heat dissipation
InA0.6
Heat dissipation per pole, current-dependent
PvidW1.6
Equipment heat dissipation, current-dependent
PvidW4.8
Static heat dissipation, non-current-dependent
PvsW0
Heat dissipation capacity
PdissW0
Operating ambient temperature min.
 °C-25
Operating ambient temperature max.
 °C55
IEC/EN 61439 design verification
   
10.2 Strength of materials and parts
   
10.2.2 Corrosion resistance
  Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
  Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
  Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
  Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
  Meets the product standard's requirements.
10.2.5 Lifting
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
  Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
  Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
  Meets the product standard's requirements.
10.5 Protection against electric shock
  Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
  Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
  Is the panel builder's responsibility.
10.8 Connections for external conductors
  Is the panel builder's responsibility.
10.9 Insulation properties
   
10.9.2 Power-frequency electric strength
  Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
  Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
  Is the panel builder's responsibility.
10.10 Temperature rise
  The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
  Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
  Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
  The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Technical data ETIM 6.0(Show features)(Hide features)
Low-voltage industrial components (EG000017) / Thermal overload relay (EC000106)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Overload protection device / Thermal overload relay ([email protected] [AKF075011])
Adjustable current range
 A0.4 - 0.6
Max. rated operation voltage Ue
 V690
Mounting method
  Direct attachment
Type of electrical connection of main circuit
  Screw connection
Number of auxiliary contacts as normally closed contact
  1
Number of auxiliary contacts as normally open contact
  1
Number of auxiliary contacts as change-over contact
  0
Release class
  CLASS 10
Approvals
Product Standards  UL 508; CSA-C22.2 No. 14; IEC/EN 60947-4-1; IEC/EN 60947-5-1; CE marking
UL File No.  E29184
UL Category Control No.  NKCR
CSA File No.  12528
CSA Class No.  3211-03
North America Certification  UL listed, CSA certified
Specially designed for North America  No
Suitable for  Branch circuits
Max. Voltage Rating  600 V AC
Degree of Protection  IEC: IP20, UL/CSA Type: -
Characteristics
IL03407015Z (AWA2300-2114) Overload relay
 
>
>
>>

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields

or