FAZ-C2/3-NA 102240 EATON MOELLER Over current switch, 2A, 3p, C-Char, AC View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

FAZ-C2/3-NA 102240 EATON MOELLER Over current switch, 2A, 3p, C-Char, AC

FAZ-C2/3-NA

102240

EATON - MOELLER

Available

Ship on today

Over current switch, 2A, 3p, C-Char, AC

More details


Circuit Breakers Electrical Power

Industrial Protective Devices - EATON - MOELLER

Miniature Circuit Breakers FAZ - EATON - MOELLER

* Brand new produt in its original packing covered by the warranties and certifications provided by EATON - MOELLER

QuantityPrice
1+$101.65
2+$98.95
3+$97.61
4+$96.75
6+$95.96
*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Delivery programme
Basic function
  Miniature circuit breakers
Pole
  3 pole
Tripping characteristic
  C
Application
  Switchgear for export to North America (UL-listed)
Rated current
InA2
Rated switching capacity acc. to IEC/EN 60947-2
 kA15
Product range
  FAZ-NA
Technical data
Electrical
Standards
  UL 489, CSA C22.2 No. 5
IEC 60947-2
Rated operational voltage
UeV 
 
UeV AC277/480 Y
 
 V DC48
Rated switching capacity acc. to IEC/EN 60947-2
 kA15
Characteristic
  B, C, D
Selectivity Class
  3
Lifespan
Operations > 20000
Direction of incoming supply
  as required
Mechanical
Standard front dimension
 mm45
Enclosure height
 mm105
Terminal protection
  Finger and back-of-hand proof to BGV A2
Mounting width per pole
 mm17.7
Mounting
  IEC/EN 60715 top-hat rail
Degree of Protection
  IP20, IP40 (when fitted)
Terminals top and bottom
  Twin-purpose terminals
Mounting position
  As required
Design verification as per IEC/EN 61439(Show features)(Hide features)
Technical data for design verification
   
Rated operational current for specified heat dissipation
InA2
Heat dissipation per pole, current-dependent
PvidW0
Equipment heat dissipation, current-dependent
PvidW4.3
Static heat dissipation, non-current-dependent
PvsW0
Heat dissipation capacity
PdissW0
Operating ambient temperature min.
 °C-25
Operating ambient temperature max.
 °C75
 
  linear, per +1 °C, results in a 0.5% reduction of current carrying capacity
IEC/EN 61439 design verification
   
10.2 Strength of materials and parts
   
10.2.2 Corrosion resistance
  Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
  Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
  Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
  Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
  Meets the product standard's requirements.
10.2.5 Lifting
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
  Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
  Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
  Meets the product standard's requirements.
10.5 Protection against electric shock
  Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
  Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
  Is the panel builder's responsibility.
10.8 Connections for external conductors
  Is the panel builder's responsibility.
10.9 Insulation properties
   
10.9.2 Power-frequency electric strength
  Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
  Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
  Is the panel builder's responsibility.
10.10 Temperature rise
  The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
  Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
  Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
  The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Technical data ETIM 6.0(Show features)(Hide features)
Circuit breakers and fuses (EG000020) / Miniature circuit breaker (MCB) (EC000042)
Electric engineering, automation, process control engineering / Electrical installation, device / Miniature circuit breaker system (MCB) / Miniature circuit breaker (MCB) ([email protected] [AAB905011])
Release characteristic
  C
Number of poles (total)
  3
Number of protected poles
  3
Nominal rated current
 A2
Nominal rated voltage
 V415
Rated short-circuit breaking capacity Icn EN 60898 at 230 V
 kA0
Rated short-circuit breaking capacity Icn EN 60898 at 400 V
 kA0
Rated short-circuit breaking capacity Icu IEC 60947-2 at 230 V
 kA15
Rated short-circuit breaking capacity Icu IEC 60947-2 at 400 V
 kA15
Voltage type
  AC
Current limiting class
  3
Frequency
 Hz50 - 60
Concurrently switching N-neutral
  No
Suitable for flush-mounted installation
  No
Over voltage category
  3
Pollution degree
  2
Width in number of modular spacings
  3
Built-in depth
 mm70.5
Additional equipment possible
  Yes
Degree of protection (IP)
  IP20
Approvals
Product Standards  IEC/EN 60947-2; UL 489; CSA-C22.2 No. 5-09; CE marking
UL File No.  E235139
UL Category Control No.  DIVQ
CSA File No.  204453
CSA Class No.  1432-01
North America Certification  UL listed, CSA certified
Specially designed for North America  Yes, suitable as BCPD
Suitable for  Feeder circuits, branch circuits
Current Limiting Circuit-Breaker  Yes
Max. Voltage Rating  ≤ 32 A
Degree of Protection  IEC: IP20, UL/CSA Type: -
Characteristics
>

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields

or