NZM-XMC-TC-MB 169832 EATON MOELLER NZM-XMC-TC-MB Measuring and communication module for external current tra.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

NZM-XMC-TC-MB 169832 EATON MOELLER NZM-XMC-TC-MB Measuring and communication module for external current tra..

NZM-XMC-TC-MB

169832

EATON - MOELLER

Available

Ship on today

NZM-XMC-TC-MB Measuring and communication module for external current transformers

More details


Circuit-breakers NZM - EATON - MOELLER

* Brand new produt in its original packing covered by the warranties and certifications provided by EATON - MOELLER

*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Delivery programme
Product range
  Accessories
Accessories
  Measuring modules
Accessories
  Accessories, diagnostics & communication
Description
  

For measuring current, voltage, power, and energy.

In addition, the module requires three current transformers and three voltage taps wired externally. X/5A standard current transformers rated for up to 6,300 A are suitable.

230 VAC power supply

2 configurable outputs (S0 pulse, alarm, etc.)

RS-485 Modbus port (slave)

The total energy consumption value will be stored in retentive memory on the module.

BreakerVisu displays (NZM-XMC-MDISP...) can be used for visualization and logging purposes.

Number of poles
  3/4 pole
For use with
  NZM…
Rated operating frequency
  AC 50/60 Hz
Standard/Approval
  IEC
Construction size
  NZM1/2/3/4
Notes 

The minimum clearances relative to the NZM circuit-breaker need to be maintained for installation.

The module can be installed on the input or outgoer side, as well as on a top hat DIN rail.

The Eaton Modbus Configurator (www.eaton.eu) can be used to set up the module.

Cannot be combined with NZM-XMC-DISP display device.

Technical data
General
Dimensions (W x H x D)
 mm52 x 85 x 70
Weight
 kg0.21
Environmental conditions
Operating temperature
 °C-10 - +50
Storage
 °C 
Storage
ϑ°C-10 - +50
Relative humidity, non-condensing (IEC/EN 60068-2-30)
 %5 - 95
Suitable for height
  2000
Degree of Protection
  IP20
Power supply module
Supply voltage
Us 230 V AC
Power supply
Rated operational voltage
UeV AC300 / 520
Max. voltage
 V AC520
Frequency
 Hz45 - 65
Accuracy
  0.5% +/- 1 digit
Overvoltage category
  Category III - 300 VAC / 520 VAC
Max. current
Overvoltage category
  Category III - 300 VAC / 520 VAC
Power monitoring PM
Accuracy
  0.5% +/- 1 digit
 
Output type
  NPN, optocoupled
Transistor voltage
  24 / -
Transistor current
  50 / -
Switching Frequency
 Hz5
Pulse duration
 ms100 / -
Design verification as per IEC/EN 61439(Show features)(Hide features)
IEC/EN 61439 design verification
   
10.2 Strength of materials and parts
   
10.2.2 Corrosion resistance
  Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
  Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
  Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
  Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
  Meets the product standard's requirements.
10.2.5 Lifting
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
  Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
  Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
  Meets the product standard's requirements.
10.5 Protection against electric shock
  Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
  Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
  Is the panel builder's responsibility.
10.8 Connections for external conductors
  Is the panel builder's responsibility.
10.9 Insulation properties
   
10.9.2 Power-frequency electric strength
  Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
  Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
  Is the panel builder's responsibility.
10.10 Temperature rise
  The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
  Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
  Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
  The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Technical data ETIM 6.0
PLC's (EG000024) / Fieldbus, decentr. periphery - communication module (EC001604)
Electric engineering, automation, process control engineering / Control / Field bus, decentralized peripheral / Field bus, decentralized peripheral - communications module ([email protected] [BAA073010])
Supply voltage AC 50 Hz
 V230 - 230
Supply voltage AC 60 Hz
 V230 - 230
Supply voltage DC
 V0 - 0
Voltage type of supply voltage
  AC
Supporting protocol for TCP/IP
  No
Supporting protocol for PROFIBUS
  No
Supporting protocol for CAN
  No
Supporting protocol for INTERBUS
  No
Supporting protocol for ASI
  No
Supporting protocol for KNX
  No
Supporting protocol for MODBUS
  Yes
Supporting protocol for Data-Highway
  No
Supporting protocol for DeviceNet
  No
Supporting protocol for SUCONET
  No
Supporting protocol for LON
  No
Supporting protocol for SERCOS
  No
Supporting protocol for PROFINET IO
  No
Supporting protocol for PROFINET CBA
  No
Supporting protocol for Foundation Fieldbus
  No
Supporting protocol for EtherNet/IP
  No
Supporting protocol for AS-Interface Safety at Work
  No
Supporting protocol for DeviceNet Safety
  No
Supporting protocol for INTERBUS-Safety
  No
Supporting protocol for PROFIsafe
  No
Supporting protocol for SafetyBUS p
  No
Supporting protocol for other bus systems
  No
Radio standard Bluetooth
  No
Radio standard WLAN 802.11
  No
Radio standard GPRS
  No
Radio standard GSM
  No
Radio standard UMTS
  No
IO link master
  No
System accessory
  Yes
Degree of protection (IP)
  IP20
With potential separation
  Yes
Fieldbus connection over separate bus coupler possible
  Yes
Rail mounting possible
  No
Wall mounting/direct mounting
  Yes
Front build in possible
  No
Rack-assembly possible
  No
Suitable for safety functions
  No
Category according to EN 954-1
  -
SIL according to IEC 61508
  None
Performance level acc. to EN ISO 13849-1
  None
Appendant operation agent (Ex ia)
  No
Appendant operation agent (Ex ib)
  No
Explosion safety category for gas
  None
Explosion safety category for dust
  None
Width
 mm52
Height
 mm85
Depth
 mm70
Dimensions
border=1>>border=1>

Datasheet - PDF

Title:Language:Size:Type:
EATON MOELLER-169832-NZM-XMC-TC-MBEnglish203 KbytesEATON MOELLER-169832-NZM-XMC-TC-MB

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields

or