Product name
Eaton DX Motor choke
Product Length/Depth
265 millimetre
Product height
265 millimetre
Product width
270 millimetre
Product weight
4.8 kilogram
Certifications
IEC/EN61800-5
UL Category Control No.: XPTQ2, XPTQ8
CSA-C22.2 No. 14
VDE 0570 Part 2-20/2001-04
UL
CSA
UL 508C
UL File No.: E167225
UL report applies to both US and Canada
IEC/EN61800-3
IEC/EN 61558-2-20-2000
Certified by UL for use in Canada
CE
CSA
UL
Product Sub Type
Motor choke
Fitted with:
PE stud
Terminations
Number of poles
Three-pole
Degree of protection
IP20
NEMA Other
Product Category
Accessories
Suitable as
Ripple filter choke
Suitable for
Branch circuits, (UL/CSA)
Used with
DA1, DC1, DE1, DE11, DG1, DM1, SPX, SVX
Ambient conditions, mechanical
Mounting position
Free surrounding areas > 50 mm
Suspended horizontally
Standing vertically
Shock resistance
3 shocks
Shock duration: 11 ms
Vibration resistance
0 - 150 Hz, 1 g
10 - 55 Hz, 0.35 mm
Climatic environmental conditions
Altitude
Max. 5000 m with current reduction
Max. 1000 m
Ambient operating temperature - max
40 °C
Ambient operating temperature - min
-25 °C
Ambient storage temperature - max
85 °C
Ambient storage temperature - min
-25 °C
Operating temperature details
-25 - 40 °C (up to 70 °C with current derating)
Terminal capacity
20 - 10 AWG
4 mm²
Tightening torque
0.8 Nm, Screw terminals
Permissible connection voltage
Max. 550 V AC (0 - 400 Hz)
Power loss
78 W (12 kHz)
50 W (3 kHz)
75 W (5 kHz)
Rated current (Ith) at rated voltage DC - max
16 A
Rated frequency - min
0 Hz
Rated frequency - max
400 Hz
Rated operational current (Ie) - min
16 A
Rated operational current (Ie) - max
16 A
Rated operational voltage (Ue) - max
750 V
Relative short-circuit voltage
0 %
Voltage rating - max
480 V
Heat dissipation capacity Pdiss
0 W
Rated operational current for specified heat dissipation (In)
16 A
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.