DX-LN1-024 269498 EATON MOELLER Main choke, AC, 1p, 24A, 1.22mH, 260V50/60Hz View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

DX-LN1-024 269498 EATON MOELLER Main choke, AC, 1p, 24A, 1.22mH, 260V50/60Hz

DX-LN1-024

269498

EATON - MOELLER

Available

Ship on today

Product on demand only, returns will not be accepted.

Main choke, AC, 1p, 24A, 1.22mH, 260V50/60Hz

More details


Variable Adjustable Frequency Speed Drives Inverters Vfd Vvvf Voltage

Frequency inverters - EATON - MOELLER

Frequency inverters M-MAX - EATON - MOELLER

* Brand new produt in its original packing covered by the warranties and certifications provided by EATON - MOELLER

QuantityPrice
1+$52.22
4+$49.04
7+$48.08
10+$47.55
14+$47.15
*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Delivery programme
Product range
  Accessories
Accessories
  Mains chokes
Description
  Single-phase
For use with
  DE1, DE11, DC1, DA1
Max. permissible connection voltage
 V AC260 V + 0% (50/60 Hz)
Rated operational current
IeA24
Inductance
LmH1.22
Maximum heat dissipation
PvW20
Technical data
General
Standards
  IEC/EN 61558-2-20-2000, VDE 0570 Part 2-20/2001-04, UL, CSA
Operating temperature
 °C-25 to +40, up to 70 with current derating (see the note)
Storage temperature
ϑ°C-25 - +85
Mechanical shock resistance
 g11 ms2/15
3 shocks
Vibration resistance
 g1 (0 - 150 Hz)
Vibration
  0.35 mm at 10 - 55 Hz
Altitude
 m0 – 1000 above sea level, up to 5000 with current reduction (see notes)
Mounting position
  Standing vertically, suspended horizontally
Free surrounding areas
 MM< 50
Degree of Protection
  IP20 (terminal)
Rated duty factor
 % DF100
Weight
 kg2
Electrical data
Rated operational voltage
  1 AC 230 V
Max. supply voltage
 V AC260 V + 0% (50/60 Hz)
Operating frequency
fHz50/60
Insulation class
  B
Rated operational current
IeA24
Inductance
LmH1.22
Maximum heat dissipation
PvW20
Voltage sag
Uk%4
Connection
Terminations
  
Technical data for design verification
   
Rated operational current for specified heat dissipation
InA24
Heat dissipation per pole, current-dependent
PvidW0
Equipment heat dissipation, current-dependent
PvidW20
Static heat dissipation, non-current-dependent
PvsW0
Heat dissipation capacity
PdissW0
Operating ambient temperature min.
 °C-25
Operating ambient temperature max.
 °C40
IEC/EN 61439 design verification
   
10.2 Strength of materials and parts
   
10.2.2 Corrosion resistance
  Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
  Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
  Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
  Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
  Meets the product standard's requirements.
10.2.5 Lifting
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
  Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
  Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
  Meets the product standard's requirements.
10.5 Protection against electric shock
  Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
  Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
  Is the panel builder's responsibility.
10.8 Connections for external conductors
  Is the panel builder's responsibility.
10.9 Insulation properties
   
10.9.2 Power-frequency electric strength
  Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
  Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
  Is the panel builder's responsibility.
10.10 Temperature rise
  The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
  Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
  Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
  The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Technical data ETIM 6.0(Show features)(Hide features)
Low-voltage industrial components (EG000017) / Coil for low-voltage (EC002563)
Electric engineering, automation, process control engineering / Electronic coil and filter / Electronic choke coil / Electronic choke coil (unspecified) ([email protected] [ADJ199004])
Suitable as interference suppression reactance coil
  No
Suitable as net reactance coil
  Yes
Suitable as commutation reactance coil
  No
Suitable as ripple filter choke
  No
Suitable as output reactance coil
  No
Number of poles, primary side
  1
Rated clock frequency
 kHz0
Rated operation frequency
 Hz50 - 60
Max. rated operation voltage Ue
 V260
Rated current at AC
 A24 - 24
Max. rated current (Ith) at rated voltage DC
 A24
Rated inductance
 mH1.22
Degree of protection (IP)
  IP20
Relative short circuit voltage
 %4
Resonance frequency
 Hz0
Dimensions
IL00906001Z Mains chokes, motor chokes
 
>
>
>
>
>
>
>>

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields

or