CI-K4X-125-TS-NA 231224 EATON MOELLER Insulated enclosure, HxWxD 240x160x125mm, +mounting rail, NA type View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

CI-K4X-125-TS-NA 231224 EATON MOELLER Insulated enclosure, HxWxD 240x160x125mm, +mounting rail, NA type

CI-K4X-125-TS-NA

231224

EATON - MOELLER

Available

Ship on today

Product on demand only, returns will not be accepted.

Insulated enclosure, HxWxD=240x160x125mm, +mounting rail, NA type

More details


Control Cabinets Switch Boxes Distribution Enclosures

Enclosures- EATON - MOELLER

CI-K insulated enclosures - EATON - MOELLER

* Brand new produt in its original packing covered by the warranties and certifications provided by EATON - MOELLER

QuantityPrice
1+$33.62
6+$30.82
11+$30.17
16+$29.82
22+$29.57
*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Delivery programme
Product range
  CI-K small enclosures
Basic function
  Basic enclosures
Product function
  Basic enclosures for North America
Single unit/Complete unit
  Single unit
Degree of Protection
  Front IP65
IP65, with push-through cable entry
Degree of Protection
  Front IP65
IP65, with push-through cable entry
Description
  Approved for UL, CSA
smooth all round with mit sharp corners
Enclosure base RAL 9005, black
Operator only RAL 7035, light gray
Dimensions
   
Width
 mm160
Height
 mm240
Depth
 mm125
Features
  With mounting rail
Mounting depth:
 mm93
Design verification as per IEC/EN 61439(Show features)(Hide features)
Technical data for design verification
   
Degree of Protection
  Front IP65
IP65, with push-through cable entry
Surface treatment
  Resistant to corrosion
Temperature resistant
  -40 °C - 120 °C (enclosure)
-40 °C - +80 °C (gasket)
IEC/EN 61439 design verification
   
10.2 Strength of materials and parts
   
10.2.2 Corrosion resistance
  Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
  Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
  Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
  Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
  Please enquire
10.2.5 Lifting
  Not applicable.
10.2.6 Mechanical impact
  Meets the product standard's requirements.
10.2.7 Inscriptions
  Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
  Meets the product standard's requirements.
10.4 Clearances and creepage distances
  Meets the product standard's requirements.
10.5 Protection against electric shock
  Is the panel builder's responsibility.
10.6 Incorporation of switching devices and components
  Is the panel builder's responsibility.
10.7 Internal electrical circuits and connections
  Is the panel builder's responsibility.
10.8 Connections for external conductors
  Is the panel builder's responsibility.
10.9 Insulation properties
   
10.9.2 Power-frequency electric strength
  Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
  Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
  Meets the product standard's requirements.
10.10 Temperature rise
  The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
  Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
  Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
  The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Technical data ETIM 6.0(Show features)(Hide features)
Low-voltage industrial components (EG000017) / Empty enclosure for switchgear (EC000712)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Component for low-voltage switching technology / Empty housing for switch devices ([email protected] [AKN343011])
Material housing
  Plastic
Width
 mm160
Height
 mm240
Depth
 mm125
With transparent cover
  No
Suitable for emergency stop
  No
Model
  Surface mounting
Degree of protection (IP)
  IP65
Approvals
Product Standards  UL 508; CSA-C22.2 No. 14-05; CSA-C22.2 No. 94; IEC/EN 60947-3; CE marking
UL File No.  E54120
UL Category Control No.  MITW2
CSA File No.  12528
CSA Class No.  3211-07
North America Certification  UL listed, CSA certified
Specially designed for North America  Yes
Degree of Protection  IEC: IP65; UL/CSA Type 1, 3R, 4X, 12, 13 – indoor and outdoor use
CAD data
>Product-specific CAD data
>3D Preview

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields

or