CI-PKZ01-NA-SVB 281630 XTPBXENASLO65 EATON ELECTRIC Insulated enclosure, for PKZ01, +padlocking feature yell.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

CI-PKZ01-NA-SVB 281630 XTPBXENASLO65 EATON ELECTRIC Insulated enclosure, for PKZ01, +padlocking feature yell..

CI-PKZ01-NA-SVB

281630

XTPBXENASLO65

EATON-MOELLER

Insulated enclosure, for PKZ01, +padlocking feature yellow, NA type

CI-PKZ01-NA-SVB

More details


Low-voltage industrial components > Empty enclosure for switchgear

Motor-protective circuit-breakers PKZ (Accessories)

* Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

Total price: $32.19
Unit price: $32.19

*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Insulated enclosure, for PKZ01, +padlocking feature yellow, NA type
Insulated enclosure for PKZM01, degree of protection IP65 integrated terminal for PE(N) connection., Can be locked in O position

Delivery program

Product range
Accessories
Subrange
Surface mounting enclosures
Accessories
Insulated enclosures for PKZ
Can be locked in O position
Degree of Protection
IP65
For use with
PKZM01
+NHI-E or VHI-PKZ01
+U or A
+L (2 off)
North American design
Notes
With integrated PE(N) terminal.
In each case 2 metric M25 cable entry knockouts top and bottom.
With thread and adapter for 1/2-inch screw connection.
2 metric M20 cable entry knockouts in the rear wall.
Hard mirror with cable entry knockouts which can be cut out.

Design verification as per IEC/EN 61439

Technical data for design verification
Rated operational current for specified heat dissipation [In]
0 A
Heat dissipation per pole, current-dependent [Pvid]
0 W
Equipment heat dissipation, current-dependent [Pvid]
0 W
Static heat dissipation, non-current-dependent [Pvs]
0 W
Heat dissipation capacity [Pdiss]
10 W
Operating ambient temperature min.
-25 °C
Operating ambient temperature max.
+70 °C
IEC/EN 61439 design verification
10.2 Strength of materials and parts10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.4 Resistance to ultra-violet (UV) radiation
Please enquire
10.2 Strength of materials and parts10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9 Insulation properties10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9 Insulation properties10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 7.0

Low-voltage industrial components (EG000017) / Empty enclosure for switchgear (EC000712)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Component for low-voltage switching technology / Empty housing for switch devices ([email protected] [AKN343014])
Material housing
Plastic
Width
97 mm
Height
160 mm
Depth
80 mm
With transparent cover
No
Suitable for emergency stop
Yes
Model
Surface mounting
Degree of protection (IP)
IP65
Degree of protection (NEMA)
Other

Approvals

Product Standards
UL 508; CSA-C22.2 No. 14; IEC60947-4-1; CE marking
UL File No.
E36332
UL Category Control No.
NLRV
CSA File No.
165628
CSA Class No.
3211-05
North America Certification
UL listed, CSA certified
Specially designed for North America
Yes
Degree of Protection
IEC: IP65, UL/CSA Type: -

Dimensions

321X015
Insulated enclosure for top mounting

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.