Product name
Eaton xComfort IKA industrial series
Product Length/Depth
115 millimetre
Product height
231 millimetre
Product width
238 millimetre
Product weight
0.93 kilogram
Certifications
IEC/EN 60670-24
EN 62208
Product Tradename
xComfort IKA
Product Type
Industrial series
Type
Basic deviceIKA industrial distribution boardInstallation distribution board
Application
Indoor (installation site)Outdoor (installation site)
Color
Light gray (RAL 7035)
Gray
Technical Data - Electrical
Voltage rating at AC
415 V AC
Frequency rating of contacts
50 Hz
Technical Data - Mechanical
Enclosure material
Plastic
Width in number of modular spacings
8
Mounting method
DIN-rail
Surface mounting
Surface mounted (plaster)
Material
Polycarbonate (plastic)
Degree of protection
IP65
IK08 (impact resistance)
Number of module space units per row
8
Terminal type
Screw terminals
PE and N terminal number and cross section
N: 4 x (2.5 mm² - 6 mm²) + 4 x (4 mm² - 10 mm²) + 1 x (16 mm² - 35 mm²)
PE: 4 x (2.5 mm² - 6 mm²) + 4 x (4 mm² - 10 mm²) + 1 x (16 mm² - 35 mm²)
Cover/door color
Transparent
Cover/door model
With notch
Cover/door type
Door
Single
Module rack type
Single-rail
Protective shrouding material
Plastic
Temperature-rise verification as per IEC 60890
Heat diss. ambient 35°C delta T:20°C wall mount individ. encl. top (IEC 60890)
14 W
Heat diss. ambient 35°C delta T:35°C wall mount individ. encl. top (IEC 60890)
29 W
Design verification as per IEC/EN 61439 - technical data
Ambient operating temperature details
-25 °C - 40 °C
Design verification as per IEC/EN 61439
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
850 °C; meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
1000 h of UV exposure as per ISO 4892-2; meets the product standard's requirements.
10.2.5 Lifting
Does not apply to enclosures without lifting aids.
10.2.6 Mechanical impact
IK08
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
IP65
10.4 Clearances and creepage distances
Is the panel builder's responsibility.
10.5 Protection against electric shock
Protection class 2, therefore not applicable.
10.6 Incorporation of switching devices and components
Is the panel builder's responsibility.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Ui = 1000 V AC
10.9.3 Impulse withstand voltage
3.3 kV
10.9.4 Testing of enclosures made of insulating material
Meets the product standard's requirements.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
Meets the product standard's requirements.
Fitted with:
Neutral-/protective conductor terminal
Device support rails
Current circuit designation
Basic device
Sealing caps
Locking screws can be sealed
Functions
Basic device
Extension possible
Protection class
II (totally insulated)
Special features
IP65Protection Class IIPlastic enclosure gray (RAL 7035)
Used with
Basic device
IKA industrial distribution board
Installation distribution board