EU5E-SWD-4D4D 116382 4519769 EATON ELECTRIC I/O module, SmartWire-DT, 24 V DC, 4DI, 4DO-Trans, 0.5A View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

EU5E-SWD-4D4D 116382 4519769 EATON ELECTRIC I/O module, SmartWire-DT, 24 V DC, 4DI, 4DO-Trans, 0.5A

EU5E-SWD-4D4D

116382

4519769

EATON-MOELLER

I/O module, SmartWire-DT, 24 V DC, 4DI, 4DO-Trans, 0.5A

EU5E-SWD-4D4D

SWD I/O module, 24 V DC, 4 digital inputs, 4 digital transistor -outputs 0, 0.5A

More details


PLC's > Fieldbus, decentr. periphery - digital I/O module

Smartwire Darwin

* Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

Total price: $159.52
Unit price: $159.52

Quantity Price
1+$159.52
2+$144.24
4+$128.78
5+$125.11
7+$122.31
*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Often bought together

More info



SWD I/O module, 24 V DC, 4 digital inputs, 4 digital transistor -outputs 0, 0.5A
SmartWire-DT module for connecting four digital input/output signals, automatic address setting, 24 V DC inputs, transistor outputs 24 V DC / 0.5 A short-circuit proof, connection with clamp-type push-in terminals

General specifications
Product name
Eaton EU5E I/O module
Part no.
EU5E-SWD-4D4D
EAN
4015081161126
Product Length/Depth
102 millimetre
Product height
90 millimetre
Product width
35 millimetre
Product weight
0.09 kilogram
Certifications
UL Category Control No.: NKCR
CSA File No.: 2324643
CSA
IEC/EN 61131-2
UL File No.: E29184
UL
CSA Class No.: 3211-07
Product Tradename
EU5E
Product Type
I/O module
Product Sub Type
None
Features & Functions
Electric connection type
Flat plug-in connection
Features
Fieldbus connection over separate bus coupler possible
Overload proof (with diagnostics)
Functions
For connection of digital I/O signals
General information
Current consumption
33 mA, SmartWire-DT network
Degree of protection
IP20
Overvoltage category
II
Pollution degree
2
Product category
SmartWire-DT slave
Residual ripple
≤ 5 % (input voltage)
Terminal capacity
0.2 - 1.5 mm² (AWG 24 - 16), solid, Terminal for I/O sensor
0.25 - 1.5 mm² (24 - 16 AWG), flexible with ferrule, Terminal for I/O sensor
Type
Digital modules
Voltage type
DC
Ambient conditions, mechanical
Constant acceleration
1 g, 8.4 - 150 Hz, according to IEC/EN 61131-2, Vibrations
Constant amplitude
3,5 mm, 5 - 8.4 Hz, according to IEC/EN 61131-2, Vibrations
Drop and topple
50 mm Drop height, Drop to IEC/EN 60068-2-31
Height of fall (IEC/EN 60068-2-32) - max
0.3 m
Mounting position
As required
Shock resistance
15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 9 Impacts
Climatic environmental conditions
Air pressure
795 - 1080 hPa (operation)
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
55 °C
Ambient storage temperature - min
-40 °C
Ambient storage temperature - max
70 °C
Climatic proofing
Dry heat to IEC 60068-2-2
Damp heat, constant, to IEC 60068-2-3
Environmental conditions
Condensation: prevent with appropriate measures
Operating temperature - min
-25 °C
Operating temperature - max
55 °C
Relative humidity
5 - 95 % (non-condensing, IEC/EN 60068-2-30)
Electro magnetic compatibility
Air discharge
8 kV, according to IEC 61131-2, level 3, ESD
Burst impulse
1 kV, Signal cable, according to IEC/EN 61131-2, Level 3
1 kV, SmartWire-DT cable, according to IEC/EN 61131-2, Level 3
2 kV, Supply cable, according to IEC/EN 61131-2, Level 3
Contact discharge
4 kV, according to IEC/EN 61131-2, Level 2, ESD
Electromagnetic fields
1 V/m at 2.0 - 2.7 GHz (according to IEC/EN 61131-2:2008)
10 V/m at 80 - 1000 MHz (according to IEC/EN 61131-2:2008)
3 V/m at 1.4 - 2 GHz (according to IEC/EN 61131-2:2008)
Radiated RFI
10 V (IEC/EN 61131-2:2008, Level 3)
Radio interference class
Class A (EN 55011)
Surge rating
0.5 kV, Surge power cables, Surge (IEC/EN 61131-2:2008, Level 1), EMC
1 kV, Surge I/O cables, Surge (IEC/EN 61131-2:2008, Level 1), EMC
Electrical rating
Input current
4 mA (at 24 V DC, Digital inputs)
Input current at signal 1
4 mA
Output current
0.5 A
Power loss
1.1 W
Rated operational voltage
24 V DC (-15 %/+ 20 % - power supply)
Short-circuit protection
Outputs are short-circuit proof
Short-circuit tripping current
Max. 1.2 A over 3 ms, Digital semi-conductor outputs
Supply voltage at AC, 50 Hz - min
0 V AC
Supply voltage at AC, 50 Hz - max
0 V AC
Supply voltage at DC - min
20.4 V DC
Supply voltage at DC - max
28.8 V DC
Communication
Connection to SmartWire-DT
Yes
Connection type
Plug, 8-pole, SmartWire-DT
Connection plug: external device plug SWD4-8SF2-5, SmartWire-DT
Push in terminals, Supply and I/O sensor
Data transfer rate
Setting automatically
250 kBit/s, SmartWire-DT
LED indicator
Status indication of SmartWire-DT network: Green LED
Status indication of input: Yellow LED
Status indication of display outputs: Yellow LED
Protocol
Other bus systems
Station
SmartWire-DT slave, SmartWire-DT network
Input/Output
Input delay
< 0.2 ms
Lamp load
≤ 3 W (at RLL)
Limit value type 1
High: > 15 V DC
Low: < 5 V DC
Number of inputs (digital)
4
Number of outputs (digital)
4
Output
4 Transistor Outputs
Switching capacity
IEC/EN 60947-5-1, utilization category DC-13, Digital outputs
Safety
Explosion safety category for dust
None
Explosion safety category for gas
None
Potential isolation
Outputs to SmartWire-DT: yes
Inputs for SmartWire-DT: yes
Protection against polarity reversal
Yes
Yes, for supply voltage (Siemens MPI optional)
Design verification
Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
1.1 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 9.0

Programmable logic controllers PLC (EG000024) / Fieldbus, decentr. periphery - digital I/O module (EC001599)
Electric engineering, automation, process control engineering / Control, Process Control System (PCS) / Field bus, decentralized peripheral / Field bus, decentralized peripheral - digital I/O module (ecl@ss13-27-24-26-04 [BAA055019])
Supply voltage AC 50 Hz
0 - 0 V
Supply voltage AC 60 Hz
0 - 0 V
Supply voltage DC
20.4 - 28.8 V
Voltage type (supply voltage)
DC
Number of digital inputs
4
Number of digital outputs
4
Digital inputs configurable
No
Digital outputs configurable
No
Input current at signal 1
4 mA
Permitted voltage at input
20.4 - 28.8 V
Type of voltage (input voltage)
DC
Type of digital output
Other
Output current
0.5 A
Permitted voltage at output
20.4 - 28.8 V
Type of output voltage
DC
Short-circuit protection, outputs available
No
Number of HW-interfaces industrial Ethernet
0
Number of interfaces PROFINET
0
Number of HW-interfaces RS-232
0
Number of HW-interfaces RS-422
0
Number of HW-interfaces RS-485
0
Number of HW-interfaces serial TTY
0
Number of HW-interfaces parallel
0
Number of HW-interfaces wireless
0
Number of HW-interfaces USB
0
Number of HW-interfaces other
0
With optical interface
No
Supporting protocol for EtherCAT
No
Supporting protocol for TCP/IP
No
Supporting protocol for PROFIBUS
No
Supporting protocol for CAN
No
Supporting protocol for INTERBUS
No
Supporting protocol for ASI
No
Supporting protocol for KNX
No
Supporting protocol for Modbus
No
Supporting protocol for Data-Highway
No
Supporting protocol for DeviceNet
No
Supporting protocol for SUCONET
No
Supporting protocol for LON
No
Supporting protocol for PROFINET IO
No
Supporting protocol for PROFINET CBA
No
Supporting protocol for SERCOS
No
Supporting protocol for Foundation Fieldbus
No
Supporting protocol for EtherNet/IP
No
Supporting protocol for AS-Interface Safety at Work
No
Supporting protocol for DeviceNet Safety
No
Supporting protocol for INTERBUS-Safety
No
Supporting protocol for PROFIsafe
No
Supporting protocol for SafetyBUS p
No
Supporting protocol for other bus systems
Yes
Radio standard Bluetooth
No
Radio standard WLAN 802.11
No
Radio standard GPRS
No
Radio standard GSM
No
Radio standard UMTS
No
IO link master
No
System accessory
Yes
Degree of protection (IP)
IP20
Type of electric connection
Flat plug-in connection
Time delay at signal change
0 - 0 ms
Fieldbus connection over separate bus coupler possible
Yes
Rail mounting possible
Yes
Wall mounting/direct mounting
Yes
Front built-in possible
No
Rack-assembly possible
No
Suitable for safety functions
No
SIL according to IEC 61508
None
Performance level according to EN ISO 13849-1
None
Appendant operation agent (Ex ia)
No
Appendant operation agent (Ex ib)
No
Explosion safety category for gas
None
Explosion safety category for dust
None
Certified for UL hazardous location class I
No
Certified for UL hazardous location class II
No
Certified for UL hazardous location class III
No
Certified for UL hazardous location division 1
No
Certified for UL hazardous location division 2
No
Certified for UL hazardous location group A (acetylene)
No
Certified for UL hazardous location group B (hydrogen)
No
Certified for UL hazardous location group C (ethylene)
No
Certified for UL hazardous location group D (propane)
No
Certified for UL hazardous location group E (metal dusts)
No
Certified for UL hazardous location group F (carbonaceous dusts)
No
Certified for UL hazardous location group G (non-conductive dusts)
No
Width
35 mm
Height
90 mm
Depth
102 mm

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.