EU5E-SWD-4AX 144062 4519612 EATON ELECTRIC I/O module, SmartWire-DT, 24 V DC, 4AI configurable 0-10V/0-20mA View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

EU5E-SWD-4AX 144062 4519612 EATON ELECTRIC I/O module, SmartWire-DT, 24 V DC, 4AI configurable 0-10V/0-20mA

EU5E-SWD-4AX

144062

4519612

EATON-MOELLER

I/O module, SmartWire-DT, 24 V DC, 4AI configurable 0-10V/0-20mA

EU5E-SWD-4AX

More details


PLC's > Fieldbus, decentr. periphery - analogue I/O module

Smartwire Darwin

* Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

Total price: $273.25
Unit price: $273.25

Quantity Price
1+$273.25
2+$246.93
*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Often bought together

More info



I/O module, SmartWire-DT, 24 V DC, 4AI configurable 0-10V/0-20mA
SmartWire-DT slave for the connection of analog input signals, automatic address setting, module with 4 analog inputs 0-10V/0-20mA, can be configured individually, connection with clamp-type push-in terminals

General specifications
Product name
Eaton EU5E Accessory Input module
Part no.
EU5E-SWD-4AX
EAN
4015081405923
Product Length/Depth
102 millimetre
Product height
90 millimetre
Product width
35 millimetre
Product weight
0.091 kilogram
Certifications
CSA Class No.: 3211-07
IEC/EN 61131-2
UL Category Control No.: NKCR
CSA File No.: 2324643
CSA
UL
UL File No.: E29184
Product Tradename
EU5E
Product Type
Accessory
Product Sub Type
Input module
Features & Functions
Electric connection type
Flat plug-in connection
Features
Input, voltage
Analog outputs configurable
Input, current
Fieldbus connection over separate bus coupler possible
Analog inputs configurable
Functions
For connection of analog I/O signals
Adjustable parameter settings
General information
Current consumption
22 mA, SmartWire-DT network
Degree of protection
IP20
NEMA 1
Overvoltage category
II
Pollution degree
2
Product category
SmartWire-DT slave
Repetition accuracy
0.5 % (Analog inputs)
Residual ripple
≤ 5 % (input voltage)
Terminal capacity
0.25 - 1.5 mm² (24 - 16 AWG), flexible with ferrule, Terminal for I/O sensor
0.2 - 1.5 mm² (AWG 24 - 16), solid, Terminal for I/O sensor
Type
Analog modules
Voltage type
DC
Ambient conditions, mechanical
Constant acceleration
1 g, 8.4 - 150 Hz, according to IEC/EN 61131-2, Vibrations
Constant amplitude
3,5 mm, 5 - 8.4 Hz, according to IEC/EN 61131-2, Vibrations
Drop and topple
50 mm Drop height, Drop to IEC/EN 60068-2-31
Height of fall (IEC/EN 60068-2-32) - max
0.3 m
Mounting position
As required
Shock resistance
15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 9 Impacts
Climatic environmental conditions
Air pressure
795 - 1080 hPa (operation)
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
55 °C
Ambient storage temperature - min
-40 °C
Ambient storage temperature - max
70 °C
Climatic proofing
Damp heat, constant, to IEC 60068-2-3
Dry heat to IEC 60068-2-2
Environmental conditions
Condensation: prevent with appropriate measures
Operating temperature - min
-25 °C
Operating temperature - max
55 °C
Relative humidity
5 - 95 % (non-condensing, IEC/EN 60068-2-30)
Electro magnetic compatibility
Air discharge
8 kV, according to IEC 61131-2, level 3, ESD
Burst impulse
2 kV, Supply cable, according to IEC/EN 61131-2, Level 3
2 kV, Signal cable, according to IEC/EN 61131-2, Level 3
2 kV, SmartWire-DT cable, according to IEC/EN 61131-2, Level 3
Contact discharge
4 kV, according to IEC/EN 61131-2, Level 2, ESD
Electromagnetic fields
10 V/m at 80 - 1000 MHz (according to IEC/EN 61131-2:2008)
3 V/m at 1.4 - 2 GHz (according to IEC/EN 61131-2:2008)
1 V/m at 2.0 - 2.7 GHz (according to IEC/EN 61131-2:2008)
Radiated RFI
10 V (IEC/EN 61131-2:2008, Level 3)
Radio interference class
Class B (EN 55011)
Surge rating
1 kV, Surge I/O cables, Surge (IEC/EN 61131-2:2008, Level 1), EMC
1 kV, Surge power cables, Surge (IEC/EN 61131-2:2008, Level 1), EMC
Electrical rating
Input current
0 - 20 mA (Analog inputs)
Input voltage
0 - 10 V (Analog inputs)
Power loss
0.6 W
Rated operational voltage
24 V DC (-15 %/+ 20 % - power supply)
Supply voltage at AC, 50 Hz - min
0 V AC
Supply voltage at AC, 50 Hz - max
0 V AC
Supply voltage at DC - min
0 V DC
Supply voltage at DC - max
0 V DC
Communication
Connection to SmartWire-DT
Yes
Connection type
Connection plug: external device plug SWD4-8SF2-5, SmartWire-DT
Plug, 8-pole, SmartWire-DT
Push in terminals, Supply and I/O sensor
Data transfer rate
Setting automatically
250 kBit/s, SmartWire-DT
LED indicator
Status indication of SmartWire-DT network: Green LED
Protocol
Other bus systems
Station
SmartWire-DT slave, SmartWire-DT network
Input/Output
Conversions
20 ms, Analog inputs
Dielectric strength
30 kV/mm, according to IEC 60243-1
Input
Inputs, configurable (0 - 10 V, 0 - 20 mA)
Current
Voltage
Input impedance
< 250 Ω
Number of inputs (analog)
4
Number of outputs (analog)
0
Resolution
12 Bit (Analog inputs)
Total error
± 1 %, Inputs
Safety
Explosion safety category for dust
None
Explosion safety category for gas
None
Potential isolation
Inputs for SmartWire-DT: yes
Protection against polarity reversal
Yes
Yes, for supply voltage (Siemens MPI optional)
Design verification
Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
0.6 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 9.0

Programmable logic controllers PLC (EG000024) / Fieldbus, decentr. periphery - analogue I/O module (EC001596)
Electric engineering, automation, process control engineering / Control, Process Control System (PCS) / Field bus, decentralized peripheral / Field bus, decentralized peripheral - analogue I/O module (ecl@ss13-27-24-26-01 [BAA061019])
Supply voltage AC 50 Hz
0 - 0 V
Supply voltage AC 60 Hz
0 - 0 V
Supply voltage DC
0 - 0 V
Voltage type (supply voltage)
DC
Power consumption
0.6 W
Input, current
Yes
Input, voltage
Yes
Input, resistor
No
Input, resistance thermometer
No
Input, thermocouple
No
Input signal, configurable
No
Resolution of the analogue inputs
4 Bit
Output, current
No
Output, voltage
No
Output signal configurable
No
Resolution of the analogue outputs
0 Bit
Number of analogue inputs
4
Number of analogue outputs
0
Analogue inputs configurable
Yes
Analogue outputs configurable
Yes
Number of HW-interfaces industrial Ethernet
0
Number of interfaces PROFINET
0
Number of HW-interfaces RS-232
0
Number of HW-interfaces RS-422
0
Number of HW-interfaces RS-485
0
Number of HW-interfaces serial TTY
0
Number of HW-interfaces parallel
0
Number of HW-interfaces wireless
0
Number of HW-interfaces USB
0
Number of HW-interfaces other
0
Supporting protocol for EtherCAT
No
Supporting protocol for TCP/IP
No
Supporting protocol for PROFIBUS
No
Supporting protocol for CAN
No
Supporting protocol for INTERBUS
No
Supporting protocol for ASI
No
Supporting protocol for KNX
No
Supporting protocol for Modbus
No
Supporting protocol for Data-Highway
No
Supporting protocol for DeviceNet
No
Supporting protocol for SUCONET
No
Supporting protocol for LON
No
Supporting protocol for PROFINET IO
No
Supporting protocol for PROFINET CBA
No
Supporting protocol for SERCOS
No
Supporting protocol for Foundation Fieldbus
No
Supporting protocol for EtherNet/IP
No
Supporting protocol for AS-Interface Safety at Work
No
Supporting protocol for DeviceNet Safety
No
Supporting protocol for INTERBUS-Safety
No
Supporting protocol for PROFIsafe
No
Supporting protocol for SafetyBUS p
No
Supporting protocol for other bus systems
Yes
Radio standard Bluetooth
No
Radio standard WLAN 802.11
No
Radio standard GPRS
No
Radio standard GSM
No
Radio standard UMTS
No
IO link master
No
System accessory
Yes
Degree of protection (IP)
IP20
Degree of protection (NEMA)
1
Type of electric connection
Flat plug-in connection
Fieldbus connection over separate bus coupler possible
Yes
Rail mounting possible
Yes
Wall mounting/direct mounting
Yes
Front built-in possible
No
Rack-assembly possible
No
Suitable for safety functions
No
SIL according to IEC 61508
None
Performance level according to EN ISO 13849-1
None
Appendant operation agent (Ex ia)
No
Appendant operation agent (Ex ib)
No
Explosion safety category for gas
None
Explosion safety category for dust
None
Certified for UL hazardous location class I
No
Certified for UL hazardous location class II
No
Certified for UL hazardous location class III
No
Certified for UL hazardous location division 1
No
Certified for UL hazardous location division 2
No
Certified for UL hazardous location group A (acetylene)
No
Certified for UL hazardous location group B (hydrogen)
No
Certified for UL hazardous location group C (ethylene)
No
Certified for UL hazardous location group D (propane)
No
Certified for UL hazardous location group E (metal dusts)
No
Certified for UL hazardous location group F (carbonaceous dusts)
No
Certified for UL hazardous location group G (non-conductive dusts)
No
Width
35 mm
Height
90 mm
Depth
102 mm

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.