Standards
EN 61000-6-1/-2/-3/-4, IEC/EN 61000-4, IEC 60068-2-6, IEC 60068-2-27
Dimensions (W x H x D)
89 x 90 x 44 mm
Mounting
Fitted into the power supply unit.
Solid
0.2⁄4 (AWG 24 - 12) mm2
Flexible with ferrule
0.2⁄2.5 (AWG 24 - 12) mm2
Standard screwdriver
3.5 x 0.6 mm
Climatic environmental conditions
Operating ambient temperature
-25 to 55, cold as per IEC 60068-2-1, heat as per IEC 60068-2-2 °C
Condensation
Take appropriate measures to prevent condensation
Relative humidity, non-condensing (IEC/EN 60068-2-30)
5 - 95 %
Air pressure (operation)
795 - 1080 hPa
Ambient conditions, mechanical
Protection type (IEC/EN 60529, EN50178, VBG 4)
IP20
Vibrations (IEC/EN 60068-2-6)Constant amplitude 0.15 mm
10 - 57 Hz
Vibrations (IEC/EN 60068-2-6)Constant acceleration 2 g
57 - 150 Hz
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15 g/11 ms
18 Impacts
Drop to IEC/EN 60068-2-31 [Drop height]
50 mm
Free fall, packaged (IEC/EN 60068-2-32)
1 m
Mounting position
Vertical or horizontal
Electromagnetic compatibility (EMC)
Electrostatic discharge (IEC/EN 61000-4-2, Level 3, ESD)Air discharge
8 kV
Electrostatic discharge (IEC/EN 61000-4-2, Level 3, ESD)Contact discharge
6 kV
Electromagnetic fields (RFI) to IEC EN 61000-4-3
10 V/m
Radio interference suppression
EN 55011 Class B, EN 55022 Class B
Burst Impulse (IEC/EN 61000-4-4, Level 3)Supply cable
2 kV
Burst Impulse (IEC/EN 61000-4-4, Level 3)Signal lines
2 kV
Power pulses (surge) (IEC/EN 61000-4-5)
2 (supply cables, symmetrical) kV
power pulses (surge) (IEC/EN 61000-4-5, level 2)
0.5 (symmetrical power lines) kV
Immunity to line-conducted interference to (IEC/EN 61000-4-6)
10 V
Clearance in air and creepage distances
EN 50178, UL 508, CSA C22.2, No. 142
Insulation resistance
EN 50178
Inputs can be used as analog inputs
4 (I7, I8, I11, I12)
Potential isolationFrom power supply
No
Potential isolationBetween digital inputs
No
Potential isolationFrom the outputs
Yes
Potential isolationto PC interface, memory card, easyNet, easyLink
Yes
Rated operational voltage [Ue]
24 V DC
On 0 signal [Ue]
< 5.0 (I1 - I6, I9 - I10) < 8 (I7, I8, I11, I12) V DC
On 1 signal [Ue]
< 5.0 (I1 - I6, I9 - I10) < 8 (I7, I8, I11, I12) V DC
Input current on 1 signalI1 to I6
3.3 (at 24 V DC) mA
Input current on 1 signalI7, I8
2.2 (at 24 V DC) mA
Input current on 1 signalI9, I10
3.3 (at 24 V DC) mA
Input current on 1 signalI11, I12
2.2 (at 24 V DC) mA
Delay time from 0 to 1Debounce ON
20 ms
Delay time from 0 to 1Debounce OFF
Normally 0.025 (I1 - I4), normally 0.25 (I5, I6, I9, I10), normally 0.15 (I7, I8, I11, I12) ms
Delay time from 1 to 0Debounce ON
20 ms
Delay time from 1 to 0Debounce OFF
Normally 0.025 (I1 - I4), normally 0.25 (I5, I6, I9, I10), normally 0.15 (I7, I8, I11, I12) ms
Cable length (unscreened)
100 m
Frequency counterQuantity
4 (I1, I2, I3, I4)
Frequency counterCounter frequency
< 3 kHz
Frequency counterPulse shape
Square
Frequency counterPulse pause ratio
01:01
Incremental counterQuantity
2 (I1 + I2, I3 + I4)
Incremental counterCounter frequency
≦ 3 kHz
Incremental counterPulse shape
Square
Incremental counterSignal offset
90°
Incremental counterPulse pause ratio
01:01
Rapid counter inputsNumber
4 (I1, I2, I3, I4)
Rapid counter inputsCounter frequency
< 3 kHz
Rapid counter inputsPulse shape
Square
Rapid counter inputsPulse pause ratio
01:01
Cable length, screened
< 20 m
Potential isolationFrom power supply
No
Potential isolationFrom the digital inputs
No
Potential isolationFrom the outputs
Yes
Potential isolationFrom the PC interface, memory card NET network, EASY-Link
Yes
Resolution, digital
0.01 V
Resolution
10 (value 0 - 1023) Bit
Accuracy of actual valuetwo MFD devices
± 3 %
Accuracy of actual valueWithin a single device
± 2 %
Conversion time, analog/digital
Every CPU cycle ms
Cable length screened
< 30 m
Analog inputs temperature resistance Pt100 or Ni1000 sensors
Potential isolationFrom power supply
No
Potential isolationFrom the digital inputs
No
Potential isolationFrom the outputs
Yes
Parallel switching of outputs for increased output
Not permissible
Protection of an output relay
Miniature circuit-breaker B16 or fuse 8 A (slow)
Potential isolationFrom power supply
Yes
Potential isolationFrom the inputs
Yes
Potential isolationFrom the PC interface, memory card NET network, EASY-Link
Yes
Potential isolationSafe isolation according to EN 50178
300 V AC
Potential isolationBasic insulation
600 V AC
Lifespan, mechanical [Operations]
10 x 106
ContactsConventional thermal current (10 A UL)
8 A
ContactsRecommended for load: 12 V AC/DC
> 500 mA
ContactsShort-circuit-proof cos ϕ = 1, characteristic B16 at 600 A
16 A
ContactsShort-circuit-proof cos ϕ = 0.5 to 0.7, characteristic B16 at 900 A
16 A
ContactsRated impulse withstand voltage Uimpof contact coil
6 kV
ContactsRated operational voltage [Ue]
250 V AC
Rated insulation voltage [Ui]
250 V AC
Safe isolation to EN 50178 between coil and contact
300 V AC
Safe isolation to EN 50178 between 2 contacts
300 V AC
Making capacityAC-15, 230 V AC, 3 A [Operations]
300000
Making capacityDC-13, 24 V DC, 5 A, 0.1 Hz [Operations]
200000
Breaking capacityAC-15, 250 V AC, 3 A (600 Ops./h) [Operations]
300000
Breaking capacityDC-13, L/R ≦ 150 ms, 24 V DC, 1 A (500 S/h) [Operations]
200000
Filament bulb load1000 W at 230/240 V AC [Operations]
25000
Filament bulb load500 W at 115/120 V AC [Operations]
25000
Fluorescent lamp loadFluorescent lamp load 10 x 58 W at 230/240 V ACWith upstream electrical device [Operations]
25000
Fluorescent lamp loadFluorescent lamp load 10 x 58 W at 230/240 V ACUncompensated [Operations]
25000
Fluorescent lamp loadFluorescent lamp load 1 x 58 W at 230/240 V AC, conventional, compensated [Operations]
25000
Switching frequencyMechanical operations
10 x 106
Switching frequencySwitching frequency
10 Hz
Switching frequencyResistive load/lamp load
2 Hz
Switching frequencyInductive load
0.5 Hz
UL/CSAUninterrupted current at 240 V AC
10 A
UL/CSAUninterrupted current at 24 V DC
8 A
UL/CSAACControl Circuit Rating Codes (utilization category)
B 300 Light Pilot Duty
UL/CSAACMax. rated operational voltage
300 V AC
UL/CSAACmax. thermal continuous current cos ϕ = 1 at B 300
5 A
UL/CSAACmax. make/break cos ϕ ≠ capacity 1 at B 300
3600⁄360 VA
UL/CSADCControl Circuit Rating Codes (utilization category)
R 300 Light Pilot Duty
UL/CSADCMax. rated operational voltage
300 V DC
UL/CSADCMax. thermal uninterrupted current at R 300
1 A
UL/CSADCMax. make/break capacity at R 300
28⁄28 VA
Potential isolationFrom power supply
No
Potential isolationFrom the digital inputs
No
Potential isolationFrom the digital outputs
Yes
Potential isolationFrom the PC interface, memory card NET network, EASY-Link
Yes
Max. output current
0.01 A
Overload and short-circuit protection
Yes
Resolution, analog
0.01 V DC
Resolution, digital
10, (value: 0 - 1023) Bit
Accuracy-25 °C - 55 °C
2 %
Conversion time
Every CPU cycle