Dimensions (W x H x D)
71.5 x 90 x 58 (4 PE) mm
Climatic environmental conditions
Operating ambient temperature
-25 to + 55
cold as per IEC 60068-2-1
heat as per IEC 60068-2-2 °C
Condensation
Take appropriate measures to prevent condensation
relative humidity
5 - 95 %
Air pressure (operation)
795 - 1080 hPa
Ambient conditions, mechanical
Protection type (IEC/EN 60529, EN50178, VBG 4)
IP20
Vibrations (IEC/EN 60068-2-6)Constant amplitude 0.15 mm
10 - 57 Hz
Vibrations (IEC/EN 60068-2-6)Constant acceleration 2 g
57 - 150 Hz
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15 g/11 ms
18 Impacts
Drop to IEC/EN 60068-2-31 [Drop height]
50 mm
Free fall, packaged (IEC/EN 60068-2-32)
1 m
Mounting position
Vertical or horizontal
Electromagnetic compatibility (EMC)
Overvoltage category/pollution degree
II/2
Electrostatic discharge (ESD)applied standard
IEC EN 61000-4-2, Level 3
Electrostatic discharge (ESD)Air discharge
8 kV
Electrostatic discharge (ESD)Contact discharge
6 kV
Burst
according to IEC/EN 61000-4-4
Supply cables: 2
Signal cables: 2 kV
power pulses (Surge)
2 kV (supply cables, symmetrical, EASY...AC)
0.5 kV (supply cables, symmetrical, easy-DC)
according to IEC/EN 61000-4-5
Immunity to line-conducted interference to (IEC/EN 61000-4-6)
10 V
Insulation resistance
EN 50178
Rated operational voltage [Ue]
24 DC (-15/+20%) V
Rated operational voltage [Ue]
24 DC (-15/+20%) V
Permissible range [Ue]
20.4 - 28.8 V DC
Input current
40 mA at Ue
2 A at Uewith load
Potential isolation
to interface/memory card: no
Signal range
0 - 10 V DC and 0 - 20 mA and Pt100 (-50…+200°C)
Resolution
10 Bit (value 0 - 1023)
Accuracy of actual valuetwo devices from series
± 3 %
Accuracy of actual valueWithin a single device
< ± 3 % %
Conversion time, analog/digital
800 ms
Cable length
≦ 10, screened m
Potential isolation
to easyLink: yes
Max. output current
0.01 A
Overload and short-circuit protection
Yes
Resolution
0.01 V analog
10 Bit (value 0 - 1023) digital
Accuracy-25 °C - 55 °C
2 %
Conversion time, analog/digital
200 ms
Rated operational voltage [Ue]
24 V DC
Permissible range [Ue]
20.4 - 28.8 V DC
Supply current
Norm./max. 24V/2A at signal 0
12/22 at signal 1 mA
Protection against polarity reversal
yes (Caution: A short circuit will result if 0 V or earth is applied to the outputs in the event that the supply voltage is connected to the wrong poles.)
Potential isolation
to the memory card: yes
Rated operational current at signal „1” DC per channel [Ie]
1 A
Lamp load without Rvper channel
5 W
Residual current on 0 signal per channel
< 0.1 mA
Max. output voltage
2.5 (signal 0 at external load < 10 MΩ)
U = Ue- 1 V (signal 1 at Ie= 0.5 A) V
Short-circuit protection
Yes, thermal (evaluation through diagnostics input R16)
Short-circuit tripping current for Ra≦ 10 mΩ
1.4 ≦ Ie≦ 4 A
Total short-circuit current
8 A
Peak short-circuit current
16 A
Max. operating frequency with constant resistive load
40000 Operations/h
Parallel connection of outputsWith resistive load, inductive load with external suppressor circuit, combination within a group
Q1 and Q2
Parallel connection of outputsNumber of outputs [max.]
2
Parallel connection of outputsMax. total current
2 (Caution! Outputs must be actuated simultaneously and for the same length of time.) A
Output status indication
LCD display (if provided)
Protection against polarity reversal
yes (Caution: A short circuit will result if 0 V or earth is applied to the outputs in the event that the supply voltage is connected to the wrong poles.)