QSA125N1-00/3 1318030 EATON MOELLER Switch-disconnector-fuse, 3 pole, 125 A, rear mounting, NH00 View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

QSA125N1-00/3 1318030 EATON MOELLER Switch-disconnector-fuse, 3 pole, 125 A, rear mounting, NH00

QSA125N1-00/3

1318030

EATON - MOELLER

Available

Ship on today

Switch-disconnector-fuse, 3 pole, 125 A, rear mounting, NH00

More details


Isolator Switch Isolation

DUMECO Switch-Disconnectors- EATON - MOELLER

DUMECO Switch-Disconnectors- EATON - MOELLER

* Brand new produt in its original packing covered by the warranties and certifications provided by EATON - MOELLER

QuantityPrice
1+$183.13
2+$178.62
3+$176.39
4+$175.02
*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Delivery programme
Product range
  Fuse-switch-disconnector
Main switch
maintenance switch
Part group reference
  QSA
Emergency STOP
  optional
Notes
  Suitable for DIN fuse-links (blade contacts type)
Information about equipment supplied
  Auxiliary contact or neutral conductor fitted by user.
Number of poles
  3 pole
Auxiliary contacts
   
 
General
Standards
  IEC/EN 60947, VDE 0660, IEC/EN 60204,
Switch-disconnector according to IEC/EN 60947-3
Certifications
  CE, RoHs
Overvoltage category/pollution degree
  III/3
Mounting position
  As required
Protection against direct contact when actuated from front (EN 50274)
  Finger and back-of-hand proof
Contacts
Mechanical variables
   
Number of poles
  3 pole
Auxiliary contacts
   
 
 N/O0
 
 N/C0
Electrical characteristics
   
Rated uninterrupted current
IuA125
Note on rated uninterrupted current !u
  Rated uninterrupted current Iu is specified for max. cross-section.
Design verification as per IEC/EN 61439(Show features)(Hide features)
Technical data for design verification
   
Rated operational current for specified heat dissipation
InA125
Heat dissipation per pole, current-dependent
PvidW9
Equipment heat dissipation, current-dependent
PvidW0
Static heat dissipation, non-current-dependent
PvsW0
Heat dissipation capacity
PdissW0
IEC/EN 61439 design verification
   
10.2 Strength of materials and parts
   
10.2.2 Corrosion resistance
  Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
  Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
  Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
  Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
  Meets the product standard's requirements.
10.2.5 Lifting
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
  Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
  Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
  Meets the product standard's requirements.
10.5 Protection against electric shock
  Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
  Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
  Is the panel builder's responsibility.
10.8 Connections for external conductors
  Is the panel builder's responsibility.
10.9 Insulation properties
   
10.9.2 Power-frequency electric strength
  Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
  Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
  Is the panel builder's responsibility.
10.10 Temperature rise
  The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
  Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
  Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
  The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Technical data ETIM 6.0(Show features)(Hide features)
Low-voltage industrial components (EG000017) / Fuse switch disconnector (EC001040)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Off-load switch, circuit breaker, control switch / Fuse switch disconnector ([email protected] [AKF058010])
Version as main switch
  Yes
Version as safety switch
  No
Max. rated operation voltage Ue AC
 V690
Rated permanent current Iu
 A125
Rated operation power at AC-23, 400 V
 kW59
Conditioned rated short-circuit current Iq
 kA50
Rated short-time withstand current lcw
 kA0
Suitable for fuses
  NH00
Number of poles
  3
With error protection
  No
Type of electrical connection of main circuit
  Screw connection
Suitable for ground mounting
  Yes
Suitable for front mounting 4-hole
  No
Suitable for busbar mounting
  No
Type of control element
  -
Position control element
  Front side
Motor drive optional
  No
Motor drive integrated
  No
Version as emergency stop installation
  No
Degree of protection (IP), front side
  IP00
Dimensions
IL008011ZU Safety switch-disconnector
 
>>

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields

or