Contactors up to 170A

* Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Function element, contactor, SmartWire-DT, DIL/MSC
Function element, Connection to SmartWire-DT: yes, For use with: DILM(C)7… - DILM(C)32…, DILM38…, DILA…, DILMP20…, DILMP32…, DILMP45…, MSC-D(E)-...(24VDC)

General specifications
Product name
Eaton Moeller® series DIL-SWD SWD contactor module
Part no.
DIL-SWD-32-001
EAN
4015081168309
Product Length/Depth
72 millimetre
Product height
38 millimetre
Product width
45 millimetre
Product weight
0.04 kilogram
Certifications
IEC/EN 60947-4-1
IEC/EN 60947
EN 50178
UL File No.: E29184
IEC/EN 61131-2
CE
CSA
CSA Class No.: 3211-07
UL 508
CSA-C22.2 No. 14-05
CSA File No.: 2324643
UL
UL Category Control No.: NKCR
Product Tradename
DIL-SWD
Product Type
Accessory
Product Sub Type
SWD contactor module
Catalog Notes
1 electrical interlock for the surface mounting of reversing starters
Minimum length 8 mm.
Features & Functions
Features
Fieldbus connection over separate bus coupler possible
Functions
Contactor actuation
Display of Switch status Contactor, status of the digital inputs 1 and 2
For connecting the contactors to SmartWire-DT
Fitted with:
Own supply
Electric connection type
Spring clamp connection
General information
Cable length
≤ 2.8 m, Connection auxiliary contact
Current consumption
40 mA, SmartWire-DT network
Degree of protection
IP20
Input current at signal 1
3 mA
Number of inputs (digital)
2
Number of outputs (digital)
1
Output current
0.5 A
Overvoltage category
II
Pollution degree
2
Product category
SmartWire-DT slave
Protocol
Other bus systems
Type
SWD contactor modules
Voltage type
DC
Ambient conditions, mechanical
Constant acceleration
1 g, 8.4 - 150 Hz, according to IEC/EN 61131-2, Vibrations
Constant amplitude
3,5 mm, 5 - 8.4 Hz, according to IEC/EN 61131-2, Vibrations
Drop and topple
50 mm Drop height, Drop to IEC/EN 60068-2-31
Height of fall (IEC/EN 60068-2-32) - max
0.3 m
Mounting position
As DILM7 to DILM38
Shock resistance
15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 9 Impacts
Climatic environmental conditions
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
60 °C
Ambient storage temperature - min
30 °C
Ambient storage temperature - max
70 °C
Environmental conditions
Condensation: prevent with appropriate measures
Relative humidity
5 - 95 % (non-condensing, IEC/EN 60068-2-30)
Electro magnetic compatibility
Air discharge
8 kV, according to IEC 61131-2, level 3, ESD
Burst impulse
1 kV, Signal cable, according to IEC/EN 61131-2, Level 3
1 kV, SmartWire-DT cable, according to IEC/EN 61131-2, Level 3
Contact discharge
4 kV, according to IEC/EN 61131-2, Level 2, ESD
Electromagnetic fields
1 V/m at 2.0 - 2.7 GHz (according to IEC/EN 61131-2:2008)
10 V/m at 80 - 1000 MHz (according to IEC/EN 61131-2:2008)
3 V/m at 1.4 - 2 GHz (according to IEC/EN 61131-2:2008)
Radiated RFI
10 V (IEC/EN 61131-2:2008, Level 3)
Radio interference class
Class A (EN 55011)
Terminal capacities
Terminal capacity
0.2 - 1.5 mm² (24 - 16 AWG), solid
0.25 - 1.5 mm², flexible with ferrule
Electrical rating
Rated operational voltage
15 V DC (auxiliary contact)
Supply voltage at AC, 50 Hz - min
0 V AC
Supply voltage at AC, 50 Hz - max
0 V AC
Supply voltage at DC - min
15 V DC
Supply voltage at DC - max
15 V DC
Magnet system
Pick-up current
500 mA (for DILM 17-38)
188 mA (for DILM 12-15)
125 mA (for DILM 7-9)
Power consumption
3 W for DILM 7-9 (Pick-up power)
4.5 W for DILM 12-15 (Pick-up power)
4.5 W for DILM 12-15 (Sealing power)
12 W for DILM 17-38 (Pick-up power)
3 W for DILM 7-9 (Sealing power)
0.5 W for DILM 17-38 (Sealing power)
Sealing current
125 mA, SmartWire-DT network for DILM 7-9
21 mA, SmartWire-DT network for DILM 17-38
188 mA, SmartWire-DT network for DILM 12-15
Communication
Addressing
Address set automatically
Connection to SmartWire-DT
Yes
Connection type
Push in terminals, Auxiliary contact
SWD: Plug, 8-pole
External device plug SWD4-8SF2-5, SmartWire-DT
LED indicator
Status indication of SmartWire-DT network: Green and orange LED
Station
SmartWire-DT slave, SmartWire-DT network
Contacts
Number of auxiliary contacts
2
Safety
Explosion safety category for dust
None
Explosion safety category for gas
None
Potential isolation
Connection auxiliary contact: no
Design verification
Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
0.8 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 9.0

Programmable logic controllers PLC (EG000024) / Fieldbus, decentr. periphery - digital I/O module (EC001599)
Electric engineering, automation, process control engineering / Control, Process Control System (PCS) / Field bus, decentralized peripheral / Field bus, decentralized peripheral - digital I/O module (ecl@ss13-27-24-26-04 [BAA055019])
Supply voltage AC 50 Hz
0 - 0 V
Supply voltage AC 60 Hz
0 - 0 V
Supply voltage DC
15 - 15 V
Voltage type (supply voltage)
DC
Number of digital inputs
2
Number of digital outputs
1
Digital inputs configurable
No
Digital outputs configurable
No
Input current at signal 1
3 mA
Permitted voltage at input
15 - 15 V
Type of voltage (input voltage)
DC
Type of digital output
None
Output current
0.5 A
Permitted voltage at output
20.4 - 28.8 V
Type of output voltage
DC
Short-circuit protection, outputs available
No
Number of HW-interfaces industrial Ethernet
0
Number of interfaces PROFINET
0
Number of HW-interfaces RS-232
0
Number of HW-interfaces RS-422
0
Number of HW-interfaces RS-485
0
Number of HW-interfaces serial TTY
0
Number of HW-interfaces parallel
0
Number of HW-interfaces wireless
0
Number of HW-interfaces USB
0
Number of HW-interfaces other
1
With optical interface
No
Supporting protocol for EtherCAT
No
Supporting protocol for TCP/IP
No
Supporting protocol for PROFIBUS
No
Supporting protocol for CAN
No
Supporting protocol for INTERBUS
No
Supporting protocol for ASI
No
Supporting protocol for KNX
No
Supporting protocol for Modbus
No
Supporting protocol for Data-Highway
No
Supporting protocol for DeviceNet
No
Supporting protocol for SUCONET
No
Supporting protocol for LON
No
Supporting protocol for PROFINET IO
No
Supporting protocol for PROFINET CBA
No
Supporting protocol for SERCOS
No
Supporting protocol for Foundation Fieldbus
No
Supporting protocol for EtherNet/IP
No
Supporting protocol for AS-Interface Safety at Work
No
Supporting protocol for DeviceNet Safety
No
Supporting protocol for INTERBUS-Safety
No
Supporting protocol for PROFIsafe
No
Supporting protocol for SafetyBUS p
No
Supporting protocol for other bus systems
Yes
Radio standard Bluetooth
No
Radio standard WLAN 802.11
No
Radio standard GPRS
No
Radio standard GSM
No
Radio standard UMTS
No
IO link master
No
System accessory
Yes
Degree of protection (IP)
IP20
Type of electric connection
Spring clamp connection
Time delay at signal change
10 - 84 ms
Fieldbus connection over separate bus coupler possible
Yes
Rail mounting possible
No
Wall mounting/direct mounting
No
Front built-in possible
No
Rack-assembly possible
No
Suitable for safety functions
No
SIL according to IEC 61508
None
Performance level according to EN ISO 13849-1
None
Appendant operation agent (Ex ia)
No
Appendant operation agent (Ex ib)
No
Explosion safety category for gas
None
Explosion safety category for dust
None
Certified for UL hazardous location class I
No
Certified for UL hazardous location class II
No
Certified for UL hazardous location class III
No
Certified for UL hazardous location division 1
No
Certified for UL hazardous location division 2
No
Certified for UL hazardous location group A (acetylene)
No
Certified for UL hazardous location group B (hydrogen)
No
Certified for UL hazardous location group C (ethylene)
No
Certified for UL hazardous location group D (propane)
No
Certified for UL hazardous location group E (metal dusts)
No
Certified for UL hazardous location group F (carbonaceous dusts)
No
Certified for UL hazardous location group G (non-conductive dusts)
No
Width
45 mm
Height
38 mm
Depth
72 mm

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.