Standards
EN 61000-6-1/-2/-3/-4, IEC 60068-2-6, IEC 60068-2-27
Dimensions (W x H x D)
107.5 x 90 x 30 mm
Mounting
Fitted on the fixing shaft of the display or on top-hat rail according to IEC/EN 60715, 35 mm deep (without display)
Solid
0.2⁄4 (AWG 24 - 12) mm2
Flexible with ferrule
0.2⁄2.5 (AWG 24 - 12) mm2
Standard screwdriver
3.5 x 0.6 mm
Climatic environmental conditions
Operating ambient temperature
-25 to 55, cold as per IEC 60068-2-1, heat as per IEC 60068-2-2 °C
Condensation
Take appropriate measures to prevent condensation
Relative humidity, non-condensing (IEC/EN 60068-2-30)
5 - 95 %
Air pressure (operation)
795 - 1080 hPa
Ambient conditions, mechanical
Protection type (IEC/EN 60529, EN50178, VBG 4)
IP20
Vibrations (IEC/EN 60068-2-6)Constant amplitude 0.15 mm
10 - 57 Hz
Vibrations (IEC/EN 60068-2-6)Constant acceleration 2 g
57 - 150 Hz
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15 g/11 ms
18 Impacts
Drop to IEC/EN 60068-2-31 [Drop height]
50 mm
Free fall, packaged (IEC/EN 60068-2-32)
1 m
Mounting position
Vertical or horizontal
Electromagnetic compatibility (EMC)
Electrostatic discharge (IEC/EN 61000-4-2, Level 3, ESD)Air discharge
8 kV
Electrostatic discharge (IEC/EN 61000-4-2, Level 3, ESD)Contact discharge
6 kV
Electromagnetic fields (RFI) to IEC EN 61000-4-3
10 V/m
Radio interference suppression
EN 55011 Class B, EN 55022 Class B
Burst Impulse (IEC/EN 61000-4-4, Level 3)Supply cable
2 kV
Burst Impulse (IEC/EN 61000-4-4, Level 3)Signal lines
2 kV
Immunity to line-conducted interference to (IEC/EN 61000-4-6)
10 V
Clearance in air and creepage distances
EN 50178, UL 508, CSA C22.2, No. 142
Insulation resistance
EN 50178
Back-up of real-time clock
Accuracy of the real-time clock
Normally ±5 s/day (±0.5 h⁄Year) s/day
Repetition accuracy of timing relays
Accuracy of timing relays (of values)
± 0.02 %
ResolutionRange “M:S”
1 s
ResolutionRange “H:M”
1 min
Write cycles of the retentive memory
1010(read ⁄ write cycles)
Rated operational voltage [Ue]
100/110/115/120//230/240 AC (+10/-15 %) V
Admissible range
85…264 V AC
Frequency
50⁄60 (± 5%) Hz
Input currentat 115/120 V AC 60 Hz
Normally 90 mA
Input currentat 230/240 V AC 50 Hz
Normally 60 mA
Power lossHeat dissipation at 24 V DC
17 W
Power lossat 115/120 V AC
Normally 11 VA
Power lossat 230⁄240 V AC
Normally 15 VA
Data transfer rate/distance
1000 kBit/s, 6 m
500 Kbit/s, 25 m
250 Kbit/s, 40 m
125 kBit/s, 125 m
50 Kbit/s, 300 m
20 Kbit/s, 700 m
10 Kbit/s, 1000 m
Potential isolationFrom power supply
Yes
Potential isolationFrom the inputs
Yes
Potential isolationto PC interface, memory card, easyNet, easyLink
Yes
Bus termination (first and last station)
Yes
Connection technique
RJ45, 8-pole