Central processing unit/power supply unit, 24 V DC, expandable, without easyNet, p - EATON - MFD-CP8-ME - 267164 View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

Central processing unit/power supply unit, 24 V DC, expandable, without easyNet, p - EATON - MFD-CP8-ME - 267164





Ship on today

Central processing unit/power supply unit, 24 V DC, expandable, without easyNet, program and screen memory

More details

Programmable Relays


easyHMI - MFD-Titan - I/O expansions - EATON - MOELLER

* Brand new produt in its original packing covered by the warranties and certifications provided by EATON - MOELLER

Price: $268.28
*This price is per unit and is the net value (not including taxes if applicable).
Up to 35% discount for registered clients.

Request a quote
How it Works

How does the quotation request work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with our price proposals
4 You can directly process the order for the quotation

There are several options for payment
- Credit card
- Wire Transfer
- PayPal

More info

Delivery programme
Product range
  Multi-function-display MFD-Titan
Basic function
  Power supply unit/CPU modules
  CPU modules
Supply voltage
  24 V DC
  ohne easyNet

  can be combined with display/operating unit MFD-80-.. and I/O module
Expandable: Digital/analog inputs/outputs and AS-Interface, PROFIBUS-DP, CANopen®, DeviceNet bus systems
Bussystem easyNet optional on board
Program and screen memory
Delivery with user program possible with MFD-COMBINATION product (Article no. 201801)
  Program and screen memory
Connection type
  Spring-cage terminals
Degree of Protection
Technical data
  EN 61000-6-1/-2/-3/-4, IEC 60068-2-6, IEC 60068-2-27
Dimensions (W x H x D)
 mm107.5 x 90 x 30
  Fitted on the fixing shaft of the display or on top-hat rail according to IEC/EN 60715, 35 mm deep (without display)
Terminal capacities
 mm20.2⁄4 (AWG 24 - 12)
Flexible with ferrule
 mm20.2⁄2.5 (AWG 24 - 12)
Standard screwdriver
 mm3.5 x 0.6
Climatic environmental conditions
Operating ambient temperature
 °C-25 to 55, cold as per IEC 60068-2-1, heat as per IEC 60068-2-2
  Take appropriate measures to prevent condensation
 °C- 40 - 70
Relative humidity, non-condensing (IEC/EN 60068-2-30)
 %5 - 95
Air pressure (operation)
 hPa795 - 1080
Ambient conditions, mechanical
Protection type (IEC/EN 60529, EN50178, VBG 4)
Vibrations (IEC/EN 60068-2-6)
Constant amplitude 0.15 mm
 Hz10 - 57
Constant acceleration 2 g
 Hz57 - 150
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15 g/11 ms
Drop to IEC/EN 60068-2-31
Drop heightmm50
Free fall, packaged (IEC/EN 60068-2-32)
Mounting position
  Vertical or horizontal
Electromagnetic compatibility (EMC)
Electrostatic discharge (IEC/EN 61000-4-2, Level 3, ESD)
Air discharge
Contact discharge
Electromagnetic fields (RFI) to IEC EN 61000-4-3
Radio interference suppression
  EN 55011 Class B, EN 55022 Class B
Burst Impulse (IEC/EN 61000-4-4, Level 3)
Supply cable
Signal lines
Power pulses (surge) (IEC/EN 61000-4-5)
 kV2 (supply cables, symmetrical)
power pulses (surge) (IEC/EN 61000-4-5, level 2)
 kV2 (supply cables symmetrical, MFD-AC-CP8..)
Immunity to line-conducted interference to (IEC/EN 61000-4-6)
Insulation resistance
Clearance in air and creepage distances
  EN 50178, UL 508, CSA C22.2, No. 142
Insulation resistance
  EN 50178
Back-up of real-time clock
Back-up of real-time clock
Technical data for design verification
Rated operational current for specified heat dissipation
Heat dissipation per pole, current-dependent
Equipment heat dissipation, current-dependent
Static heat dissipation, non-current-dependent
Heat dissipation capacity
Operating ambient temperature min.
Operating ambient temperature max.
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance
  Meets the product standard's requirements. Verification of thermal stability of enclosures
  Meets the product standard's requirements. Verification of resistance of insulating materials to normal heat
  Meets the product standard's requirements. Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
  Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
  Meets the product standard's requirements.
10.2.5 Lifting
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
  Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
  Meets the product standard's requirements.
10.4 Clearances and creepage distances
  Meets the product standard's requirements.
10.5 Protection against electric shock
  Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
  Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
  Is the panel builder's responsibility.
10.8 Connections for external conductors
  Is the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength
  Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
  Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
  Is the panel builder's responsibility.
10.10 Temperature rise
  The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
  Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
  Is the panel builder's responsibility.
10.13 Mechanical function
  The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Technical data ETIM 6.0(Show features)(Hide features)
PLC's (EG000024) / Graphic panel (EC001412)
Electric engineering, automation, process control engineering / Control / Operate and Observe (HMI) / Graphic panel (HMI) ([email protected] [BAA722010])
Supply voltage AC 50 Hz
 V0 - 0
Supply voltage AC 60 Hz
 V0 - 0
Supply voltage DC
 V20.4 - 28.8
Voltage type of supply voltage
Number of HW-interfaces industrial Ethernet
Number of HW-interfaces PROFINET
Number of HW-interfaces RS-232
Number of HW-interfaces RS-422
Number of HW-interfaces RS-485
Number of HW-interfaces serial TTY
Number of HW-interfaces USB
Number of HW-interfaces parallel
Number of HW-interfaces Wireless
Number of HW-interfaces other
With SW interfaces
Supporting protocol for TCP/IP
Supporting protocol for PROFIBUS
Supporting protocol for CAN
Supporting protocol for INTERBUS
Supporting protocol for ASI
Supporting protocol for KNX
Supporting protocol for MODBUS
Supporting protocol for Data-Highway
Supporting protocol for DeviceNet
Supporting protocol for SUCONET
Supporting protocol for LON
Supporting protocol for PROFINET IO
Supporting protocol for PROFINET CBA
Supporting protocol for SERCOS
Supporting protocol for Foundation Fieldbus
Supporting protocol for EtherNet/IP
Supporting protocol for AS-Interface Safety at Work
Supporting protocol for DeviceNet Safety
Supporting protocol for INTERBUS-Safety
Supporting protocol for PROFIsafe
Supporting protocol for SafetyBUS p
Supporting protocol for other bus systems
Radio standard Bluetooth
Radio standard WLAN 802.11
Radio standard GPRS
Radio standard GSM
Radio standard UMTS
IO link master
Type of display
With colour display
Number of colours of the display
Number of grey-scales/blue-scales of display
Screen diagonal
Number of pixels, horizontal
Number of pixels, vertical
Useful project memory/user memory
With numeric keyboard
With alpha numeric keyboard
Number of function buttons, programmable
Number of buttons with LED
Number of system buttons
With touch screen
With message indication
With message system (incl. buffer and confirmation)
Process value representation (output) possible
Process default value (input) possible
With recipes
Number of password levels
Printer output available
Number of online languages
Additional software components, loadable
Degree of protection (IP), front side
Operation temperature
 °C-25 - 55
Rail mounting possible
Wall mounting/direct mounting
Suitable for safety functions
Width of the front
Height of the front
Built-in depth
Product Standards  IEC/EN see Technical Data; UL 508; CSA C22.2 No. 142-M1987; CSA C22.2 No. 213-M1987; CE marking
UL File No.  E135462
UL Category Control No.  NRAQ
CSA File No.  012528
CSA Class No.  2252-01 + 2258-02
North America Certification  UL listed, CSA certified
Degree of Protection  IEC: IP20, UL/CSA Type: -
IL05013014Z (AWA2528-2019) Multi function display, Control relay easy

PDF of Central processing unit/power supply unit, 24 V DC, expandable, without easyNet, p - EATON - MFD-CP8-ME - 267164

Datasheet 1: 267164 - MFD-CP8-MEEnglish253 KbytesDatasheet 1: 267164 - MFD-CP8-ME
Datasheet 2: 267164 - MFD-CP8-MEEnglish94 KbytesDatasheet 1: 267164 - MFD-CP8-ME
Complete catalogue 1: 267164 - MFD-CP8-MEEnglish13 MbytesDatasheet 1: 267164 - MFD-CP8-ME

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait

* Required fields