NZM1-XFIU 104611 EATON MOELLER Earth-fault release, 0.03-3A, 3p, bottom View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

NZM1-XFIU 104611 EATON MOELLER Earth-fault release, 0.03-3A, 3p, bottom

NZM1-XFIU

104611

EATON - MOELLER

Available

Ship on today

Product on demand only, returns will not be accepted.

Earth-fault release, 0.03-3A, 3p, bottom

More details


Circuit Breakers Electrical Power

Circuit-breakers NZM - EATON - MOELLER

Earth-fault release, up to 160A - EATON - MOELLER

* Brand new produt in its original packing covered by the warranties and certifications provided by EATON - MOELLER

*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Delivery programme
Description
  Earth-fault release to IEC/EN 60947-2
not UL/CSA approved
Suitable for use in three- and single-phase systems
Pulse-current sensitive according to core-balance principle
For 3 pole NZM1 circuit-breakers and N1 switch-disconnectors
Supply voltage-dependent Ue = 200 – 415 V 50/60 Hz
Contact sequence
  
Electrical
Standards
  IEC/EN 60947-2
IEC/EN 60947-2 annex B
Sensitivity
  Pulse-current sensitive as per core-balance principle (type A)
Min. operating voltage
UeV 
or detection of fault currents type A/AC
  80 V (dependent on mains voltage)
Suitability for the application
  in three-phase systems
Rated operational voltage
UeV AC200…415 (3~)
Rated frequency
fHz50/60
Number of poles
  4-pole
Rated current range
InA15…100
Rated fault currents
IΔnA0.03…0.1…0.3…0.5…1…3
Detection range of the fault current
  50/60 Hz
Rated ultimate short-circuit making capacity and rated ultimate short-circuit breaking capacity
IΔmA= ICU
Mechanical shock resistance (IEC 60068-2-27)
  20 (half-sinusoidal shock 20 ms)
Lifespan, mechanical (50 % with fault current)
Operations 20000
Mechanical
Standard front dimension
 mm45
Mounting
  Bottom
Mounting position
  Vertical and 90° in all directions
Supply
   
 
  NZM1 from above
Degree of protection
  IP20 in the operating component area
Ambient temperature
  -5 - +40
Sealability
  yes, setting buttons
Terminal capacity
   
Flexible without ferrule
 mm2wie NZM1 Standardklemme
flexible with ferrules
 mm2such as NZM1 standard terminal
Design verification as per IEC/EN 61439(Show features)(Hide features)
Technical data for design verification
   
Operating ambient temperature min.
 °C-5
Operating ambient temperature max.
 °C40
IEC/EN 61439 design verification
   
10.2 Strength of materials and parts
   
10.2.2 Corrosion resistance
  Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
  Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
  Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
  Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
  Meets the product standard's requirements.
10.2.5 Lifting
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
  Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
  Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
  Meets the product standard's requirements.
10.5 Protection against electric shock
  Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
  Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
  Is the panel builder's responsibility.
10.8 Connections for external conductors
  Is the panel builder's responsibility.
10.9 Insulation properties
   
10.9.2 Power-frequency electric strength
  Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
  Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
  Is the panel builder's responsibility.
10.10 Temperature rise
  The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
  Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
  Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
  The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Technical data ETIM 6.0
Low-voltage industrial components (EG000017) / Residual current release for power circuit breaker (EC001021)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Circuit breaker (LV < 1 kV) / Fault current switch for circuit breakers ([email protected] [AKF009010])
Rated control supply voltage Us at AC 50HZ
 V200 - 415
Rated control supply voltage Us at AC 60HZ
 V200 - 415
Rated control supply voltage Us at DC
 V0 - 0
Rated fault current
 A0.03 - 3
Max. power on-delay time
 ms30
Delay adjustable
  Yes
Max. rated operation voltage Ue
 V415
Dimensions
>

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields

or