Standards
EN 55011, EN 55022, IEC/EN 61000-4, IEC 60068-2-6, IEC 60068-2-27
Dimensions (W x H x D)
35 x 110 x 125.5 (2 PE) mm
Mounting
Top-hat rail IEC/EN 60715, 35 mm or screw fixing using fixing brackets ZB4-101-GF1 (accessories)
Solid
0.2/1.5 (AWG 24 - 16) mm2
Flexible with ferrule
0.2/1.5 (AWG 24 - 16) mm2
Climatic environmental conditions
Operating ambient temperature
In accordance with IEC 60068-2-1, -25 - +55 °C
Condensation
Take appropriate measures to prevent condensation
Storage [ϑ]
In accordance with IEC 60068-2-1, -2, -14
-40 - +70 °C
relative humidity
in accordance with IEC 60068-2-30, IEC 60068-2-78
5 - 95 %
Air pressure (operation)
795 - 1080 hPa
Ambient conditions, mechanical
Protection type (IEC/EN 60529, EN50178, VBG 4)
IP20
Vibrations
In accordance with IEC 60068-2-6
constant amplitude 0.15 mm: 10 - 57
constant acceleration 2 g: 57 - 150 Hz
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15 g/11 ms
18 Impacts
Drop to IEC/EN 60068-2-31 [Drop height]
50 mm
Free fall, packaged (IEC/EN 60068-2-32)
0.3 m
Mounting position
Vertical or horizontal
Electromagnetic compatibility (EMC)
Overvoltage category/pollution degree
III/2
Electrostatic discharge (ESD)applied standard
nach IEC/EN 61000-4-2
Electrostatic discharge (ESD)Air discharge
8 kV
Electrostatic discharge (ESD)Contact discharge
6 kV
Electromagnetic fields (RFI) to IEC EN 61000-4-3
0.8 - 1.0 GHz: 10
1.4 - 2 GHz: 3
2.0 - 2.7 GHz: 1 V/m
Radio interference suppression
EN 55011 Class B
Burst
according to IEC/EN 61000-4-4
Supply cables: 2
Signal cables: 2
easyNet: 2
SWD lines: 2 kV
power pulses (Surge)
according to IEC/EN 61000-4-5
1 kV (supply cables, symmetrical)
Immunity to line-conducted interference to (IEC/EN 61000-4-6)
10 V
Clearance in air and creepage distances
EN 50178, UL 508, CSA C22.2, No. 142
Insulation resistance
EN 50178
Back-up of real-time clock
Back-up of real-time clock
① Backup time (hours) with fully charged double layer capacitor
② Service life (years)
Accuracy of the real-time clock
typ. ± 2 (± 0.2 h⁄Year) s/day
depending on ambient air temperature fluctuations of up to ± 5 s/day (± 0.5 h⁄year) are possible
Repetition accuracy of timing relays
Accuracy of timing relays (of values)
± 0.02 %
ResolutionRange “H:M”
1 min
Write cycles of the retentive memory
1014(read⁄write cycles)
Rated operational voltage [Ue]
24 DC (-15/+20%) V
Permissible range [Ue]
20.4 - 28.8 V DC
Protection against polarity reversal
yes
Input current
normally 900 mA at Ue
Inrush current and length
12.5 for 6 ms A
Voltage dips
≤ In accordance with IEC 61131-2
≤ 10 ms
Fuse
≧ 3 A (T) (e.g FAZ C3) A
Power loss [P]
Normally 1 W
Note on heat dissipation
Current consumption at 24 V DC
Potential isolation
from power supply: no
between digital inputs: no
from the outputs: no
to COM interface: yes
to easyNet: yes
to AUX: yes
to SmartWire-DT: no
Rated operational voltage [Ue]
24 V DC
Input voltage
Signal 0: ≦ 5 (I1 - I4)
Signal 1: ≧ 15 (I1 - I4) V DC
Input current at signal 1
I1 - I4: 3.9 mA
Deceleration time
20 (0 -> 1/1 -> 0, Debounce ON)
normally 0.025 (0 -> 1/1 -> 0, Debounce OFF) ms
Cable length
100 (unshielded) m
Frequency counterNumber
4 (I1, I2, I3, I4)
Frequency counterCounter frequency
≦ 5 kHz
Frequency counterPulse shape
Square
Frequency counterPulse pause ratio
1:1
Frequency counterCable length
≦ 20 (screened) m
Incremental counterNumber of counter inputs
2 (I1 + I2, I3 + I4)
Incremental counterCounter frequency
≦ 5 kHz
Incremental counterPulse shape
Square
Incremental counterSignal offset
90°
Incremental counterPulse pause ratio
1:1
Rapid counter inputsNumber
4 (I1, I2, I3, I4)
Rapid counter inputsCable length
≦ 20 (screened) m
Rapid counter inputsCounter frequency
≦ 5 kHz
Rapid counter inputsPulse shape
Square
Rapid counter inputsPulse pause ratio
1:1
Potential isolation
from power supply: no
From the inputs: yes: no
to COM interface: yes
to easyNet: yes
to AUX: yes
Rated operational current at signal „1” DC per channel [Ie]
max. 0.1 A
Lamp load without Rvper channel
1.2 W
Residual current on 0 signal per channel
< 0.1 mA
Max. output voltage
2.5 (signal 0 at external load < 10 MΩ)
U = Ue- 2 V (signal 1 at Ie= 0.1 A) V
Short-circuit protection
Yes, electronic (Q1 - Q2)
Short-circuit tripping current for Ra≦ 10 mΩ
0.15 - 0.35 per output
depending on number of active channels and their load A
Peak short-circuit current
10 A/80 ms (on short-circuit)
10 A/20 ms (on attempted restart of device after 10s) A
Output status indication
LED
Rated operational voltage [UAux]
24 V DC (-15/+20%) V
Permissible range
20.4 - 28.8 V DC
Output voltage SWD-OUT
Ue- 0.3 V
Protection against polarity reversal
yes
Residual ripple on the input voltage
≦ 5 %
Max. current [Imax]
3 (IEC)
2 (UL) A
Heat dissipation
type. 1 W at 24 V DC
Potential isolation
from power supply POW: yes
From the inputs: yes
from the outputs: yes
to COM interface: yes
to easyNet: yes
to SmartWire-DT: yes
SmartWire-DT supply voltage
Rated operating voltage [Ue]
14.5 ± 3 % V
Potential isolation
from power supply POW: no
From the inputs: yes: no
from the outputs: no
to COM interface: yes
to easyNet: yes
to AUX: yes
Number of SmartWire-DT slaves
Max. 99
Address allocation
Automatically (via Configuration button)
Status indication
SWD-LED: orange/green/red
Config. LED: green/red
Plug connector
Blade terminal SWD4-8MF2
Bus termination
Integrated in the device
SmartWire-DT line end with SWD4-RC8-10
Data transfer rate/distance
1000 KBit/s, 6 m
500 KBit/s, 25 m
250 Kbit/s, 40 m
125 Kbit/s, 300 m
50 KBit/s, 300 m
20 KBit/s, 700 m
10 KBit/s, 1000 m
Lengths from 40 m can be obtained only with cables with reinforced cross-section and terminal adapter.
Potential isolation
from power supply POW: yes
From the inputs: yes
from the outputs: yes
to COM interface: yes
to SmartWire-DT: yes
to AUX: yes
Bus termination (first and last station)
yes
Terminal types
RJ45, 8-polig
Terminal capacity
up to 1000 m, < 16 mΩ/m: 1.5 (AWG: 16)
up to 600 m, < 26 mΩ/m: 0.75 - 0.8 (AWG: 18)
up to 600 m, < 26 mΩ/m: 0.5 - 0.6 (AWG: 20, 19)
up to 400 m, < 40 mΩ/m: 0.34 - 0.5 (AWG: 22, 21, 20)
up to 250 m, < 60 mΩ/m: 0.25 - 0.34 (AWG: 23, 22)
up to 175 m, < 70 mΩ/m: 0.13 (AWG: 26)
up to 40 m, < 140 mΩ/m: 1.5 (AWG: 16)