DILA-22(400V50HZ,440V60HZ) 276401 EATON MOELLER Contactor relay, 2N / O + 2N / C, AC View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

DILA-22(400V50HZ,440V60HZ) 276401 EATON MOELLER Contactor relay, 2N / O + 2N / C, AC

DILA-22(400V50HZ,440V60HZ)

276401

EATON - MOELLER

Available

Ship on today

Contactor relay, 2N / O + 2N / C, AC

More details


Contactor Relays

DIL Contactors - EATON - MOELLER

Contactor Relays DILA - EATON - MOELLER

* Brand new produt in its original packing covered by the warranties and certifications provided by EATON - MOELLER

QuantityPrice
1+$18.54
7+$16.80
14+$16.38
20+$16.20
27+$16.06
*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Delivery programme
Product range
  DILA relays
Application
  Contactor relays
Description
  Basic devices with positive operation contacts
Connection technique
  Screw terminals
Rated operational current
   
AC-15
   
220 V 230 V 240 V
IeA4
380 V 400 V 415 V
IeA4
Contacts
   
N/O = Normally open
  2 N/O
N/C = Normally closed
  2 NC
Contact sequence
  
General
Standards
  IEC/EN 60947, VDE 0660, UL, CSA
Lifespan, mechanical
   
AC operated
Operationsx 10620
DC operated
Operationsx 10620
Maximum operating frequency
 Ops./h 
Maximum operating frequency
Operations/h 9000
Climatic proofing
  Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature
   
Open
 °C-25 - +60
Enclosed
 °C- 25 - 40
Ambient temperature, storage
 °C- 40 - 80
Mounting position
   
Mounting position
  
Technical data for design verification
   
Rated operational current for specified heat dissipation
InA15.5
Heat dissipation per pole, current-dependent
PvidW0.5
Equipment heat dissipation, current-dependent
PvidW0
Static heat dissipation, non-current-dependent
PvsW1.4
Heat dissipation capacity
PdissW0
Operating ambient temperature min.
 °C-25
Operating ambient temperature max.
 °C60
IEC/EN 61439 design verification
   
10.2 Strength of materials and parts
   
10.2.2 Corrosion resistance
  Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
  Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
  Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
  Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
  Meets the product standard's requirements.
10.2.5 Lifting
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
  Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
  Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
  Meets the product standard's requirements.
10.5 Protection against electric shock
  Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
  Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
  Is the panel builder's responsibility.
10.8 Connections for external conductors
  Is the panel builder's responsibility.
10.9 Insulation properties
   
10.9.2 Power-frequency electric strength
  Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
  Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
  Is the panel builder's responsibility.
10.10 Temperature rise
  The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
  Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
  Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
  The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Technical data ETIM 6.0(Show features)(Hide features)
Low-voltage industrial components (EG000017) / Contactor relay (EC000196)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Contactor (LV) / Contactor relay ([email protected] [AAB716011])
Rated control supply voltage Us at AC 50HZ
 V400 - 400
Rated control supply voltage Us at AC 60HZ
 V440 - 440
Rated control supply voltage Us at DC
 V0 - 0
Voltage type for actuating
  AC
Rated operation current Ie , 400 V
 A4
Connection type auxiliary circuit
  Screw connection
Mounting method
  DIN-rail/screw
Interface
  No
Number of auxiliary contacts as normally closed contact
  2
Number of auxiliary contacts as normally open contact
  2
Number of auxiliary contacts as normally closed contact, delayed switching
  0
Number of auxiliary contacts as normally open contact, leading
  0
With LED indication
  No
Number of auxiliary contacts as change-over contact
  0
Manual operation possible
  No
Approvals
Product Standards  IEC/EN 60947-4-1; UL 508; CSA-C22.2 No. 14-05; CE marking
UL File No.  E29184
UL Category Control No.  NKCR
CSA File No.  012528
CSA Class No.  3211-03
North America Certification  UL listed, CSA certified
Specially designed for North America  No
Characteristics
IL03407013Z (AWA2100-2126) Contactors
 
>>

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields

or