Standards
IEC/EN 60947, VDE 0660
Lifespan, mechanicalAC operated [Operations]
5 x 106
Operating frequency, mechanicalAC operated [Operations/h]
3600
Climatic proofing
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperatureOpen
-40 - +70 °C
Mounting positionMounting position
Mechanical shock resistance (IEC/EN 60068-2-27)Half-sinusoidal shock, 15 msMain contactsN/O contact
10 g
Protection against direct contact when actuated from front (EN 50274)
Finger and back-of-hand proof with terminal shroud
Terminal capacity main cableSolid
1 x (70 - 300)
2 x (35 - 185) mm2
Terminal capacity main cableStranded
1 x (70 - 300)
2 x (35 - 185) mm2
Terminal capacity control circuit cablesSolid
2 x (0.5 - 2.5) mm2
Main cable connection screw/bolt
M10
Tightening torque
12 - 16 Nm
Control circuit cable connection screw/bolt
M3.5
ToolControl circuit cablesPozidriv screwdriver
2 Size
Rated impulse withstand voltage [Uimp]
8000 V AC
Overvoltage category/pollution degree
III/3
Rated insulation voltage [Ui]
1000 V AC
Rated operational voltage [Ue]
1000 V AC
Safe isolation to EN 61140between coil and contacts
1000 V AC
Safe isolation to EN 61140between the contacts
690 V AC
Making capacity (cos ϕ) [Up to 690 V]
5000
According to IEC/EN 60947 A
Breaking capacity220 V 230 V
5000 A
Breaking capacity380 V 400 V
5000 A
Breaking capacity500 V
5000 A
Breaking capacity660 V 690 V
5000 A
Short-circuit ratingShort-circuit protection maximum fuseType “2” coordination400 V [gG/gL 500 V]
630 A
Short-circuit ratingShort-circuit protection maximum fuseType “1” coordination400 V [gG/gL 500 V]
630 A
AC-1Rated operational currentConventional free air thermal current, 3 pole, 50 - 60 HzOpenat 40 °C [Ith=Ie]
630 A
AC-1Rated operational currentConventional free air thermal current, 3 pole, 50 - 60 HzOpenat 55 °C [Ith=Ie]
470 A
AC-1Rated operational currentConventional free air thermal current, 3 pole, 50 - 60 HzOpenat 60 °C [Ith=Ie]
400 A
AC-1Rated operational currentConventional free air thermal current, 1 poleopen [Ith]
1760 A
AC-3Rated operational currentOpen, 3-pole: 50 – 60 Hz220 V 230 V [Ie]
400 A
AC-3Rated operational currentOpen, 3-pole: 50 – 60 Hz240 V [Ie]
400 A
AC-3Rated operational currentOpen, 3-pole: 50 – 60 Hz415 V [Ie]
400 A
AC-3Rated operational currentOpen, 3-pole: 50 – 60 Hz440V [Ie]
400 A
AC-3Rated operational currentOpen, 3-pole: 50 – 60 Hz500 V [Ie]
370 A
AC-3Rated operational currentOpen, 3-pole: 50 – 60 Hz660 V 690 V [Ie]
370 A
AC-3Rated operational currentOpen, 3-pole: 50 – 60 Hz1000 V [Ie]
155 A
AC-3Motor rating [P]220 V 230 V [P]
110 kW
AC-3Motor rating [P]240V [P]
110 kW
AC-3Motor rating [P]380 V 400 V [P]
200 kW
AC-3Motor rating [P]415 V [P]
200 kW
AC-3Motor rating [P]440 V [P]
200 kW
AC-3Motor rating [P]660 V 690 V [P]
355 kW
AC-3Motor rating [P]1000 V [P]
220 kW
Rated operational current, openDC-160 V [Ie]
550 A
Rated operational current, openDC-1110 V [Ie]
550 A
Rated operational current, openDC-1220 V [Ie]
550 A
Rated operational current, openDC-1440 V [Ie]
450 A
Rated operational current, openDC-360 V [Ie]
450 A
Rated operational current, openDC-3110 V [Ie]
450 A
Rated operational current, openDC-3220 V [Ie]
450 A
Rated operational current, openDC-3440 V [Ie]
450 A
Rated operational current, openDC-560 V [Ie]
450 A
Rated operational current, openDC-5110 V [Ie]
450 A
Rated operational current, openDC-5220 V [Ie]
450 A
Rated operational current, openDC-5440 V [Ie]
450 A
Voltage toleranceAC operated [Pick-up]Min. pick-up voltage, AC operated
0.85 x Uc
Voltage toleranceAC operated [Pick-up]Pick-up voltage AC operated, max.
1.1 x Uc
Power consumption of the coil in a cold state and 1.0 x USDual-frequency coil 50/60 Hz [Pick-up]
3500 VA
Power consumption of the coil in a cold state and 1.0 x USDual-frequency coil 60 Hz [Sealing]
140 VA
Power consumption of the coil in a cold state and 1.0 x USDual-frequency coil 50/60 Hz [Sealing]
60 W
Changeover time at 100 % US(recommended value)Main contactsAC operatedClosing delaySwitching times of main contacts AC operated Closing delay, min.
30 ms
Changeover time at 100 % US(recommended value)Main contactsAC operatedClosing delaySwitching times of main contacts AC operated Closing delay, max.
60 ms
Changeover time at 100 % US(recommended value)Main contactsAC operatedOpening delaySwitching times of main contacts AC operated Opening delay, min.
10 ms
Changeover time at 100 % US(recommended value)Main contactsAC operatedOpening delaySwitching times of main contacts AC operated Opening delay, max.
20 ms