Standards
IEC/EN 60947, VDE 0660, UL, CSA
Lifespan, mechanicalAC operated [Operations]
10 x 106
Lifespan, mechanicalDC operated [Operations]
10 x 106
Operating frequency, mechanicalAC operated [Operations/h]
5000
Operating frequency, mechanicalDC operated [Operations/h]
5000
Climatic proofing
Damp heat, constant, to IEC 60068-2-3
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperatureOpen
-25 - +60 °C
Ambient temperatureEnclosed
- 25 - 40 °C
Ambient temperatureStorage
- 40 - 80 °C
Mounting positionMounting position
Mechanical shock resistance (IEC/EN 60068-2-27)Half-sinusoidal shock, 10 msMain contactsN/O contact
10 g
Mechanical shock resistance (IEC/EN 60068-2-27)Half-sinusoidal shock, 10 msAuxiliary contactsN/O contact
7 g
Mechanical shock resistance (IEC/EN 60068-2-27)Half-sinusoidal shock, 10 msAuxiliary contactsN/C contact
5 g
Degree of Protection
IP00
Protection against direct contact when actuated from front (EN 50274)
Finger and back-of-hand proof
Terminal capacity main cableSolid
1 x (0.75 - 16)
2 x (0.75 - 10) mm2
Terminal capacity main cableFlexible with ferrule
1 x (0.75 - 16)
2 x (0.75 - 10) mm2
Terminal capacity main cableStranded
1 x 16 mm2
Terminal capacity main cableSolid or stranded
18 - 6 AWG
Terminal capacity main cableTerminal screw
M5
Terminal capacity main cableTightening torque
3 Nm
Terminal capacity main cableStripping length
10 mm
Terminal capacity control circuit cablesSolid
1 x (0.75 - 4)
2 x (0.75 - 2.5) mm2
Terminal capacity control circuit cablesFlexible with ferrule
1 x (0.75 - 2.5)
2 x (0.75 - 2.5) mm2
Terminal capacity control circuit cablesSolid or stranded
18 - 14 AWG
Terminal capacity control circuit cablesStripping length
10 mm
Terminal capacity control circuit cablesTerminal screw
M3.5
Terminal capacity control circuit cablesTightening torque
1.2 Nm
ToolMain cablePozidriv screwdriver
2 Size
ToolMain cableStandard screwdriver
0.8 x 5.5
1 x 6 mm
ToolControl circuit cablesPozidriv screwdriver
2 Size
ToolControl circuit cablesStandard screwdriver
0.8 x 5.5
1 x 6 mm
Rated impulse withstand voltage [Uimp]
8000 V AC
Overvoltage category/pollution degree
III/3
Rated insulation voltage [Ui]
690 V AC
Rated operational voltage [Ue]
690 V AC
Safe isolation to EN 61140between coil and contacts
440 V AC
Safe isolation to EN 61140between the contacts
440 V AC
Making capacity (cos ϕ) [Up to 690 V]
350
According to IEC/EN 60947 A
Breaking capacity220 V 230 V
250 A
Breaking capacity380 V 400 V
250 A
Breaking capacity500 V
250 A
Breaking capacity660 V 690 V
144 A
Short-circuit ratingShort-circuit protection maximum fuseType “2” coordination400 V [gG/gL 500 V]
35 A
Short-circuit ratingShort-circuit protection maximum fuseType “2” coordination690 V [gG/gL 690 V]
35 A
Short-circuit ratingShort-circuit protection maximum fuseType “1” coordination400 V [gG/gL 500 V]
100 A
Short-circuit ratingShort-circuit protection maximum fuseType “1” coordination690 V [gG/gL 690 V]
50 A
AC-1Rated operational currentConventional free air thermal current, 3 pole, 50 - 60 HzOpenat 40 °C [Ith=Ie]
45 A
AC-1Rated operational currentConventional free air thermal current, 3 pole, 50 - 60 HzOpenat 50 °C [Ith=Ie]
41 A
AC-1Rated operational currentConventional free air thermal current, 3 pole, 50 - 60 HzOpenat 55 °C [Ith=Ie]
40 A
AC-1Rated operational currentConventional free air thermal current, 3 pole, 50 - 60 HzOpenat 60 °C [Ith=Ie]
39 A
AC-1Rated operational currentConventional free air thermal current, 3 pole, 50 - 60 Hzenclosed [Ith]
36 A
AC-1Rated operational currentConventional free air thermal current, 1 poleopen [Ith]
117 A
AC-1Rated operational currentConventional free air thermal current, 1 poleenclosed [Ith]
105 A
AC-1Motor rating [P]220/230 V [P]
16 kW
AC-1Motor rating [P]240 V [P]
18 kW
AC-1Motor rating [P]380/400 V [P]
28 kW
AC-1Motor rating [P]415 V [P]
31 kW
AC-1Motor rating [P]440 V [P]
33 kW
AC-1Motor rating [P]500 V [P]
37 kW
AC-1Motor rating [P]690 V [P]
49 kW
AC-3Rated operational currentOpen, 3-pole: 50 – 60 HzNotes
At maximum permissible ambient temperature (open.)
AC-3Rated operational currentOpen, 3-pole: 50 – 60 Hz220 V 230 V [Ie]
25 A
AC-3Rated operational currentOpen, 3-pole: 50 – 60 Hz240 V [Ie]
25 A
AC-3Rated operational currentOpen, 3-pole: 50 – 60 Hz380 V 400 V [Ie]
25 A
AC-3Rated operational currentOpen, 3-pole: 50 – 60 Hz415 V [Ie]
25 A
AC-3Rated operational currentOpen, 3-pole: 50 – 60 Hz440V [Ie]
25 A
AC-3Rated operational currentOpen, 3-pole: 50 – 60 Hz500 V [Ie]
25 A
AC-3Rated operational currentOpen, 3-pole: 50 – 60 Hz660 V 690 V [Ie]
15 A
AC-3Motor rating [P]220 V 230 V [P]
7.5 kW
AC-3Motor rating [P]240V [P]
8.5 kW
AC-3Motor rating [P]380 V 400 V [P]
11 kW
AC-3Motor rating [P]415 V [P]
14.5 kW
AC-3Motor rating [P]440 V [P]
15.5 kW
AC-3Motor rating [P]500 V [P]
17.5 kW
AC-3Motor rating [P]660 V 690 V [P]
14 kW
Rated operational current, openDC-160 V [Ie]
45 A
Rated operational current, openDC-1110 V [Ie]
45 A
Rated operational current, openDC-1220 V [Ie]
45 A
3 pole, at Ith(60°)
13.2 W
Impedance per pole
2.7 mΩ
Voltage toleranceAC operated 50 Hz [Pick-up]
0.8 - 1.1 x Uc
Voltage toleranceAC operated 50/60 Hz
0.85 - 1.1 x Uc
Voltage toleranceDrop-out voltage AC operated [Drop-out]
0.4 - 0.6 x Uc
Power consumption of the coil in a cold state and 1.0 x USAC operated 50/60 Hz [Pick-up]
50 VA
Power consumption of the coil in a cold state and 1.0 x USAC operated 50/60 Hz [Pick-up]
40 W
Power consumption of the coil in a cold state and 1.0 x USAC operated 50/60 Hz [Sealing]
8 VA
Power consumption of the coil in a cold state and 1.0 x USAC operated 50/60 Hz [Sealing]
2.1 W
Changeover time at 100 % US(recommended value)Main contactsAC operatedClosing delay
16 - 22 ms
Changeover time at 100 % US(recommended value)Main contactsAC operatedOpening delay
8 - 14 ms
Changeover time at 100 % US(recommended value)Permissible residual current with actuation of A1 - A2 by the electronics (with 0 signal).
≦ 1 mA
Rating data for approved types
Switching capacityMaximum motor ratingThree-phase200 V
208 V
7.5 HP
Switching capacityMaximum motor ratingThree-phase230 V
240 V
10 HP
Switching capacityMaximum motor ratingThree-phase460 V
480 V
15 HP
Switching capacityMaximum motor ratingThree-phase575 V
600 V
20 HP
Switching capacityMaximum motor ratingSingle-phase115 V
120 V
2 HP
Switching capacityMaximum motor ratingSingle-phase230 V
240 V
5 HP
Switching capacityGeneral use
40 A
Auxiliary contactsPilot DutyAC operated
A600
Auxiliary contactsPilot DutyDC operated
P300
Auxiliary contactsGeneral UseAC
600 V
Auxiliary contactsGeneral UseAC
10 A
Auxiliary contactsGeneral UseDC
250 V
Auxiliary contactsGeneral UseDC
1 A
Short Circuit Current RatingBasic RatingSCCR
5 kA
Short Circuit Current RatingBasic Ratingmax. Fuse
125 A
Short Circuit Current RatingBasic Ratingmax. CB
125 A
Short Circuit Current Rating480 V High FaultSCCR (fuse)
10/100 kA
Short Circuit Current Rating480 V High Faultmax. Fuse
125/70 Class J A
Short Circuit Current Rating480 V High FaultSCCR (CB)
10/65 kA
Short Circuit Current Rating480 V High Faultmax. CB
50/32 A
Short Circuit Current Rating600 V High FaultSCCR (fuse)
10/100 kA
Short Circuit Current Rating600 V High Faultmax. Fuse
125/100 Class J A
Short Circuit Current Rating600 V High FaultSCCR (CB)
10/22 kA
Short Circuit Current Rating600 V High Faultmax. CB
50/32 A
Special Purpose RatingsElectrical Discharge Lamps (Ballast)480V 60Hz 3phase, 277V 60Hz 1phase
40 A
Special Purpose RatingsElectrical Discharge Lamps (Ballast)600V 60Hz 3phase, 347V 60Hz 1phase
40 A
Special Purpose RatingsIncandescent Lamps (Tungsten)480V 60Hz 3phase, 277V 60Hz 1phase
40 A
Special Purpose RatingsIncandescent Lamps (Tungsten)600V 60Hz 3phase, 347V 60Hz 1phase
40 A
Special Purpose RatingsResistance Air Heating480V 60Hz 3phase, 277V 60Hz 1phase
40 A
Special Purpose RatingsResistance Air Heating600V 60Hz 3phase, 347V 60Hz 1phase
40 A
Special Purpose RatingsRefrigeration Control (CSA only)LRA 480V 60Hz 3phase
240 A
Special Purpose RatingsRefrigeration Control (CSA only)FLA 480V 60Hz 3phase
40 A
Special Purpose RatingsRefrigeration Control (CSA only)LRA 600V 60Hz 3phase
180 A
Special Purpose RatingsRefrigeration Control (CSA only)FLA 600V 60Hz 3phase
30 A
Special Purpose RatingsDefinite Purpose Ratings (100,000 cycles acc. to UL 1995)LRA 480V 60Hz 3phase
150 A
Special Purpose RatingsDefinite Purpose Ratings (100,000 cycles acc. to UL 1995)FLA 480V 60Hz 3phase
25 A
Special Purpose RatingsElevator Control200V 60Hz 3phase
3 HP
Special Purpose RatingsElevator Control200V 60Hz 3phase
11 A
Special Purpose RatingsElevator Control240V 60Hz 3phase
5 HP
Special Purpose RatingsElevator Control240V 60Hz 3phase
15.2 A
Special Purpose RatingsElevator Control480V 60Hz 3phase
10 HP
Special Purpose RatingsElevator Control480V 60Hz 3phase
14 A
Special Purpose RatingsElevator Control600V 60Hz 3phase
15 HP
Special Purpose RatingsElevator Control600V 60Hz 3phase
17 A