DILH2200/22(RAW250) 111793 XTCEC22R22B EATON ELECTRIC Contactor, 3p+2N/O+2N/C, 2200A/AC1 View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

DILH2200/22(RAW250) 111793 XTCEC22R22B EATON ELECTRIC Contactor, 3p+2N/O+2N/C, 2200A/AC1

DILH2200/22(RAW250)

111793

XTCEC22R22B

EATON-MOELLER

Contactor, 3p+2N/O+2N/C, 2200A/AC1

DILH2200/22(RAW250)

Contactor, Ith =Ie: 2700 A, RAW 250: 230 - 250 V 50 - 60 Hz/230 - 350 V DC, AC and DC operation, Screw connection

More details


Low-voltage industrial components > Power contactor, AC switching

Contactors more than 170 A

* Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

Total price: $20,999.82
Unit price: $20,999.82

*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Contactor, Ith =Ie: 2700 A, RAW 250: 230 - 250 V 50 - 60 Hz/230 - 350 V DC, AC and DC operation, Screw connection
Contactor, Application: Mains contactors for resistive loads from 1000 A, AC -1 contactors greater than 1000 A, Utilization category: AC-1: Non-inductive or slightly inductive loads, resistance furnaces, Connection technique: Screw connection, Rated operational current AC-1 Conventional free air thermal current, 3 pole, 50 - 60 Hz Open at 40 °C: Ith =Ie= 2700 A, Rated operational current AC-1 Conventional free air thermal current, 1 pole open: Ith= 5500 A, For use with: DILM820-XHI…, Instructions: integrated suppressor circuit in actuating electronics, 660 V, 690 V or 1000 V: not directly reversing, Voltage AC/DC: AC and DC operation

Delivery program

Product range
Contactors
Application
Mains contactors for resistive loads from 1000 A
Subrange
AC -1 contactors greater than 1000 A
Utilization category
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
Connection technique
Screw connection
Rated operational current
AC-1Conventional free air thermal current, 3 pole, 50 - 60 HzOpenat 40 °C [Ith=Ie]
2700 A
AC-1Conventional free air thermal current, 1 poleopen [Ith]
5500 A
Contact sequence
210S058
For use with
DILM820-XHI…
Actuating voltage
RAW 250: 230 - 250 V 50 - 60 Hz/230 - 350 V DC
Voltage AC/DC
AC and DC operation
Auxiliary contacts
possible variants at auxiliary contact module fitting options
on the side: 2 x DILM820-XHI11(V)-SI; 2 x DILM820-XHI11-SA
Side mounting auxiliary contacts
2100DRW-97
Instructions
Interlocked opposing contacts according to IEC/EN 60947-5-1 Appendix L, inside the auxiliary contact module
Auxiliary contacts used as mirror contacts according to IEC/EN 60947-4-1 Appendix F (not N/C late open)
Instructions
integrated suppressor circuit in actuating electronics
660 V, 690 V or 1000 V: not directly reversing
Note concerning the product
Classic DILM1600, DILH2000, DILH2200
A1/A2 werden wie bisher gewohnt an Spannung gelegt
Direct from the PLC
An die Anschlüsse A3/A4 kann direkt ein 24-V-Ausgang der SPS angeschlossen werden.
From a low-power actuating device
Gering belastbare Befehlsgeber wie Leiterplattenrelais, Befehlsgeräte oder Positionsschalter können direkt an A10/A11 angeschlossen werden.

① Stopping in the event of an emergency (emergency switching off)

② max. Cable capacitance 6 nF

Technical data

General
Standards
IEC/EN 60947, VDE 0660, UL, CSA, CCC
Lifespan, mechanicalAC operated [Operations]
5 x 106
Lifespan, mechanicalDC operated [Operations]
5 x 106
Operating frequency, mechanicalAC operated [Operations/h]
1000
Operating frequency, mechanicalDC operated [Operations/h]
1000
Climatic proofing
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperatureOpen
-40 - +60 °C
Ambient temperatureStorage
- 40 - + 80 °C
Mounting position
210N017210N018
Mechanical shock resistance (IEC/EN 60068-2-27)Half-sinusoidal shock, 10 msMain contactsN/O contact
10 g
Mechanical shock resistance (IEC/EN 60068-2-27)Half-sinusoidal shock, 10 msAuxiliary contactsN/O contact
10 g
Mechanical shock resistance (IEC/EN 60068-2-27)Half-sinusoidal shock, 10 msAuxiliary contactsN/C contact
8 g
Degree of Protection
IP00
Altitude
Max. 2000 m
Weight
32 kg
Terminal capacity main cableBusbar [Width]
100 mm
Main cable connection screw/bolt
M12
Tightening torque
35 Nm
Terminal capacity control circuit cablesSolid
1 x (0.75 - 2.5)
2 x (0.75 - 2.5) mm2
Terminal capacity control circuit cablesFlexible with ferrule
1 x (0.75 - 2.5)
2 x (0.75 - 2.5) mm2
Terminal capacity control circuit cablesSolid or stranded
18 - 14 AWG
Stripping length
10 mm
Control circuit cable connection screw/bolt
M3.5
Tightening torque
1.2 Nm
ToolMain cableWidth across flats
18 mm
ToolControl circuit cablesPozidriv screwdriver
2 Size
ToolControl circuit cablesStandard screwdriver
0.8 x 5.5/1 x 6 mm
Main conducting paths
Rated impulse withstand voltage [Uimp]
8000 V AC
Overvoltage category/pollution degree
III/3
Rated insulation voltage [Ui]
1000 V AC
Rated operational voltage [Ue]
1000 V AC
Safe isolation to EN 61140between coil and contacts
500 V AC
Safe isolation to EN 61140between the contacts
500 V AC
Making capacity (p.f. to IEC/EN 60947)
9840 A
Breaking capacity220 V 230 V
8200 A
Breaking capacity380 V 400 V
8200 A
Breaking capacity500 V
8200 A
Breaking capacity660 V 690 V
8200 A
Breaking capacity1000 V
5800 A
Component lifespan
AC1: See → Engineering, characteristic curves
AC
AC-1Rated operational currentConventional free air thermal current, 3 pole, 50 - 60 HzOpenat 40 °C [Ith=Ie]
2700 A
AC-1Rated operational currentConventional free air thermal current, 3 pole, 50 - 60 HzOpenat 50 °C [Ith=Ie]
2400 A
AC-1Rated operational currentConventional free air thermal current, 3 pole, 50 - 60 HzOpenat 55 °C [Ith=Ie]
2300 A
AC-1Rated operational currentConventional free air thermal current, 3 pole, 50 - 60 HzOpenat 60 °C [Ith=Ie]
2200 A
AC-1Rated operational currentConventional free air thermal current, 1 poleNote
at maximum permissible ambient air temperature
AC-1Rated operational currentConventional free air thermal current, 1 poleopen [Ith]
5500 A
Current heat loss
3 pole, at Ith(60°)
231 W
Magnet systems
Voltage toleranceUS
230 - 250 V 50/60 Hz
230 - 350 V DC
Voltage toleranceAC operated [Pick-up]
0.7 x US min- 1.15 x US maxx US
Voltage toleranceDC operated [Pick-up]
0.7 x US min- 1.15 x US maxx US
Voltage toleranceAC operated [Drop-out]
0.2 x US max- 0.6 x US minx US
Voltage toleranceDC operated [Drop-out]
0.2 x US max- 0.6 x US minx US
Power consumption of the coil in a cold state and 1.0 x USNote on power consumption
Control transformer with uk≦ 7%
Power consumption of the coil in a cold state and 1.0 x USPull-in power [Pick-up]
1600 VA
Power consumption of the coil in a cold state and 1.0 x USPull-in power [Pick-up]
1400 W
Power consumption of the coil in a cold state and 1.0 x USSealing power [Sealing]
36.5 VA
Power consumption of the coil in a cold state and 1.0 x USSealing power [Sealing]
17.3 W
Duty factor
100 % DF
Changeover time at 100 % US(recommended value)Main contactsClosing delay
70 ms
Changeover time at 100 % US(recommended value)Main contactsOpening delay
40 ms
Behaviour in marginal and transitional conditionsSealingVoltage interruptions(0 … 0.2 x Uc min) ≦ 10 ms
Time is bridged successfully
Behaviour in marginal and transitional conditionsSealingVoltage interruptions(0 … 0.2 x Uc min) > 10 ms
Drop-out of the contactor
Behaviour in marginal and transitional conditionsSealingVoltage drops(0.2 … 0.6 x Uc min) ≦ 12 ms
Time is bridged successfully
Behaviour in marginal and transitional conditionsSealingVoltage drops(0.2 … 0.6 x Uc min) > 12 ms
Drop-out of the contactor
Behaviour in marginal and transitional conditionsSealingVoltage drops(0.6 … 0.7 x Uc min)
Contactor remains switched on
Behaviour in marginal and transitional conditionsSealingExcess voltage(1.15 … 1.3 x Uc max)
Contactor remains switched on
Behaviour in marginal and transitional conditionsSealingPick-up phase(0 … 0.7 x Uc min)
Contactor does not switch on
Behaviour in marginal and transitional conditionsSealingPick-up phase(0.7 x Uc min… 1.15 x Uc max)
Contactor switches on with certainty
Admissible transitional contact resistance(of the external control circuit device when actuating A11)
≦ 500 mΩ
PLC signal level (A3 - A4) to IEC/EN 61131-2 (type 2)High
15 V
PLC signal level (A3 - A4) to IEC/EN 61131-2 (type 2)Low
5 V
Electromagnetic compatibility (EMC)
Electromagnetic compatibility
This product is designed for operation in industrial environments (environment A). Its use in residential environments (environment B) may cause radio-frequency interference, requiring additional noise suppression measures.
Rating data for approved types
Switching capacityGeneral use
2200 A
Auxiliary contactsPilot DutyAC operated
A600
Auxiliary contactsPilot DutyDC operated
P300
Auxiliary contactsGeneral UseAC
600 V
Auxiliary contactsGeneral UseAC
15 A
Auxiliary contactsGeneral UseDC
250 V
Auxiliary contactsGeneral UseDC
1 A
Special Purpose RatingsResistance Air Heating480V 60Hz 3phase, 277V 60Hz 1phase
2200 A
Special Purpose RatingsResistance Air Heating600V 60Hz 3phase, 347V 60Hz 1phase
2200 A

Design verification as per IEC/EN 61439

Technical data for design verification
Rated operational current for specified heat dissipation [In]
2200 A
Heat dissipation per pole, current-dependent [Pvid]
77 W
Equipment heat dissipation, current-dependent [Pvid]
0 W
Static heat dissipation, non-current-dependent [Pvs]
13 W
Heat dissipation capacity [Pdiss]
0 W
Operating ambient temperature min.
-40 °C
Operating ambient temperature max.
+60 °C
IEC/EN 61439 design verification
10.2 Strength of materials and parts10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9 Insulation properties10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9 Insulation properties10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 7.0

Low-voltage industrial components (EG000017) / Power contactor, AC switching (EC000066)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Contactor (LV) / Power contactor, AC switching ([email protected] [AAB718015])
Rated control supply voltage Us at AC 50HZ
230 - 250 V
Rated control supply voltage Us at AC 60HZ
230 - 250 V
Rated control supply voltage Us at DC
230 - 250 V
Voltage type for actuating
AC/DC
Rated operation current Ie at AC-1, 400 V
2700 A
Rated operation current Ie at AC-3, 400 V
0 A
Rated operation power at AC-3, 400 V
0 kW
Rated operation current Ie at AC-4, 400 V
0 A
Rated operation power at AC-4, 400 V
0 kW
Rated operation power NEMA
0 kW
Modular version
No
Number of auxiliary contacts as normally open contact
2
Number of auxiliary contacts as normally closed contact
2
Type of electrical connection of main circuit
Rail connection
Number of normally closed contacts as main contact
0
Number of main contacts as normally open contact
3

Approvals

Product Standards
IEC/EN 60947-4-1; UL 60947-4-1; CSA - C22.2 No. 60947-4-1-14; CE marking
UL File No.
E29096
UL Category Control No.
NLDX
CSA File No.
012528
CSA Class No.
3211-04
North America Certification
UL listed, CSA certified
Specially designed for North America
No

Characteristics

Side mounting auxiliary contacts
2100DRW-97
possible variants at auxiliary contact module fitting options
on the side: 2 x DILM820-XHI11(V)-SI; 2 x DILM820-XHI11-SA
Characteristic curve
210U038
Switching conditions for 3 pole, non-motor loads
Operating characteristics
Non inductive and slightly inductive loads
Electrical characteristics
Switch on: 1 x rated operational current
Switch off: 1 x rated operational current
Utilization category
100 % AC-1
Typical examples of application
Electric heat
Characteristic curve
210U040
Short-time loading, 3-pole
Time interval between two loading cycles: 15 minutes

Dimensions

2100DIM-67
210W060
DILM1600
DILH2000, DILH2200

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.