DILMC17-01(230V50HZ,240V60HZ) 277611 EATON MOELLER Contactor, 3p+1N/C, 7.5kW/400V/AC3 View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

DILMC17-01(230V50HZ,240V60HZ) 277611 EATON MOELLER Contactor, 3p+1N/C, 7.5kW/400V/AC3

DILMC17-01(230V50HZ,240V60HZ)

277611

EATON - MOELLER

Available

Ship on today

Contactor, 3p+1N/C, 7.5kW/400V/AC3

More details


Contactor Relays

DIL Contactors - EATON - MOELLER

DIL Contactors up to 170A - EATON - MOELLER

* Brand new produt in its original packing covered by the warranties and certifications provided by EATON - MOELLER

QuantityPrice
1+$31.29
4+$29.31
8+$28.59
12+$28.23
16+$28.02
*This price is per unit and is the net value (not including taxes if applicable).

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Delivery programme
Product range
  Contactors
Application
  Contactors for Motors
Subrange
  Contactors up to 170 A, 3 pole
Utilization category
  AC-1: Non-inductive or slightly inductive loads, resistance furnaces
NAC-3: Normal AC induction motors: starting, switch off during running
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
 
  >
Notes
  Also suitable for motors with efficiency class IE3.
IE3-ready devices are identified by the logo on their packaging.
Connection technique
  Spring-loaded terminals
Description
  Spring-cage terminals on auxiliary and control circuit terminals
Pole
  3 pole
Rated operational current
   
AC-3
   
380 V 400 V
IeA18
AC-1
   
Conventional free air thermal current, 3 pole, 50 - 60 Hz
   
Open
   
at 40 °C
Ith =IeA40
enclosed
IthA32
Conventional free air thermal current, 1 pole
   
open
IthA88
enclosed
IthA80
Max. rating for three-phase motors, 50 - 60 Hz
   
AC-3
   
220 V 230 V
PkW5
380 V 400 V
PkW7.5
660 V 690 V
PkW11
AC-4
   
220 V 230 V
PkW2.5
380 V 400 V
PkW4.5
660 V 690 V
PkW6.5
Contacts
   
N/C = Normally closed
  1 NC
Contact sequence
  >
Instructions
  Contacts to EN 50 012.
Auxiliary current, coil connections with spring-cage connection technology.
Main current connections with screw terminals.
with mirror contact.
Can be combined with auxiliary contact
  DILA-XHIC(V)..
Voltage AC/DC
  AC operation
Technical data
General
Standards
  IEC/EN 60947, VDE 0660, UL, CSA
Lifespan, mechanical
   
AC operated
Operationsx 10610
DC operated
Operationsx 10610
Operating frequency, mechanical
   
AC operated
Operations/h 5000
DC operated
Operations/h 5000
Climatic proofing
  Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature
   
Open
 °C-25 - +60
Enclosed
 °C- 25 - 40
Storage
 °C- 40 - 80
Mounting position
  >>
Mechanical shock resistance (IEC/EN 60068-2-27)
   
Half-sinusoidal shock, 10 ms
   
Main contacts
   
N/O contact
 g10
Auxiliary contacts
   
N/O contact
 g7
N/C contact
 g5
Mechanical shock resistance (IEC/EN 60068-2-27) when tabletop-mounted
   
Half-sinusoidal shock, 10 ms
   
Main contacts
   
N/O contact
 g6.9
Auxiliary contacts
   
N/O contact
 g5.3
N/C contact
 g3.5
Degree of Protection
  IP00
Protection against direct contact when actuated from front (EN 50274)
  Finger and back-of-hand proof
Weight
   
AC operated
 kg0.42
DC operated
 kg0.48
Terminal capacity main cable
   
Solid
 mm21 x (0.75 - 16)
2 x (0.75 - 10)
Flexible with ferrule
 mm21 x (0.75 - 16)
2 x (0.75 - 10)
Stranded
 mm21 x 16
Solid or stranded
 AWG18 - 6
Main cable connection screw/bolt
  M5
Tightening torque
 Nm3.2
Tool
   
Main cable
   
Pozidriv screwdriver
 Size2
Standard screwdriver
 mm0.8 x 5.5
1 x 6
Terminal capacity control circuit cables
   
Solid
 mm21 x (0.75 - 2.5)
2 x (0.75 - 2.5)
Flexible
 mm21 x (0.75 - 2.5)
2 x (0.75 - 2.5)
Flexible with ferrule
 mm21 x (0.75 - 1.5)
2 x (0.75 - 1.5)
Solid or stranded
 AWG18 - 14
Tool
   
Stripping length
 mm10
Screwdriver blade width
 mm3.5
Main conducting paths
Rated impulse withstand voltage
UimpV AC8000
Overvoltage category/pollution degree
  III/3
Rated insulation voltage
UiV AC690
Rated operational voltage
UeV AC690
Safe isolation to EN 61140
   
between coil and contacts
 V AC440
between the contacts
 V AC440
Making capacity (p.f. to IEC/EN 60947)
   
 
Up to 690 VA238
Breaking capacity
   
220 V 230 V
 A170
380 V 400 V
 A170
500 V
 A170
660 V 690 V
 A120
Short-circuit rating
   
Short-circuit protection maximum fuse
   
Type “2” coordination
   
400 V
gG/gL 500 VA35
690 V
gG/gL 690 VA35
Type “1” coordination
   
400 V
gG/gL 500 VA63
690 V
gG/gL 690 VA50
AC
AC-1
   
Rated operational current
   
Conventional free air thermal current, 3 pole, 50 - 60 Hz
   
Open
   
at 40 °C
Ith =IeA40
at 50 °C
Ith =IeA38
at 55 °C
Ith =IeA37
at 60 °C
Ith =IeA35
enclosed
IthA32
Conventional free air thermal current, 1 pole
   
open
IthA88
enclosed
IthA80
AC-3
   
Rated operational current
   
Open, 3-pole: 50 – 60 Hz
   
220 V 230 V
IeA18
240 V
IeA18
380 V 400 V
IeA18
415 V
IeA18
440V
IeA18
500 V
IeA18
660 V 690 V
IeA12
380 V 400 V
IeA18
Motor rating
PkWh 
220 V 230 V
PkW5
240V
PkW5.5
380 V 400 V
PkW7.5
415 V
PkW10
440 V
PkW10.5
500 V
PkW12
660 V 690 V
PkW11
AC-4
   
Open, 3-pole: 50 – 60 Hz
   
220 V 230 V
IeA10
240 V
IeA10
380 V 400 V
IeA10
415 V
IeA10
440 V
IeA10
500 V
IeA10
660 V 690 V
IeA8
Motor rating
PkWh 
220 V 230 V
PkW2.5
240 V
PkW3
380 V 400 V
PkW4.5
415 V
PkW5
440 V
PkW5.5
500 V
PkW6
660 V 690 V
PkW6.5
DC
Rated operational current, open
   
DC-1
   
60 V
IeA35
110 V
IeA35
220 V
IeA35
440 V
IeA2.9
DC-3
   
60 V
IeA35
110 V
IeA35
220 V
IeA10
440 V
IeA0.6
DC-5
   
60 V
IeA35
110 V
IeA35
220 V
IeA10
440 V
IeA0.6
Current heat loss
3-pole at Ith
 W8.7
Current heat loss at Ie to AC-3/400 V
 W2.1
Impedance per pole
 mΩ2.7
Magnet systems
Voltage tolerance
 x Uc 
AC operated
Pick-upx Uc0.8 - 1.1
Drop-out voltage AC operated
Drop-outx Uc0.3 - 0.6
DC operated
Pick-upx Uc0.7 - 1.2
DC operated
Drop-outx Uc0.15 - 0.6
Notes
  at least smoothed two-phase bridge rectifier or three-phase rectifier
Power consumption of the coil in a cold state and 1.0 x Uc
   
50 Hz
Pick-upVA52
50 Hz
SealingVA7.1
50 Hz
SealingW2.1
60 Hz
Pick-upVA67
60 Hz
SealingVA8.7
60 Hz
SealingW2.6
50/60 Hz
Pick-upVA62
58
50/60 Hz
SealingVA9.1
6.5
50/60 Hz
SealingW2.5
2
DC operated
Pick-upW

Datasheet - PDF

Title:Language:Size:Type:
pdf-XTCEC018C01F Contactor, 3p1N/C, 7.5kW/400V/AC3 - EATON - DILMC17-01230V50HZ,240V60HZ - 277611English601 Kbytespdf-XTCEC018C01F Contactor, 3p1N/C, 7.5kW/400V/AC3 - EATON - DILMC17-01230V50HZ,240V60HZ - 277611

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review