DILMC17-01(230V50HZ,240V60HZ) 277611 EATON MOELLER Contactor, 3p+1N/C, 7.5kW/400V/AC3 View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

DILMC17-01(230V50HZ,240V60HZ) 277611 EATON MOELLER Contactor, 3p+1N/C, 7.5kW/400V/AC3

DILMC17-01(230V50HZ,240V60HZ)

277611

EATON - MOELLER

Available

Ship on today

Contactor, 3p+1N/C, 7.5kW/400V/AC3

More details


Contactor Relays

DIL Contactors - EATON - MOELLER

DIL Contactors up to 170A - EATON - MOELLER

* Brand new produt in its original packing covered by the warranties and certifications provided by EATON - MOELLER

QuantityPrice
1+$30.91
4+$28.95
8+$28.23
12+$27.88
16+$27.65
*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Delivery programme
Product range
  Contactors
Application
  Contactors for Motors
Subrange
  Contactors up to 170 A, 3 pole
Utilization category
  AC-1: Non-inductive or slightly inductive loads, resistance furnaces
NAC-3: Normal AC induction motors: starting, switch off during running
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
 
  >
Notes
  Also suitable for motors with efficiency class IE3.
IE3-ready devices are identified by the logo on their packaging.
Connection technique
  Spring-loaded terminals
Description
  Spring-cage terminals on auxiliary and control circuit terminals
Pole
  3 pole
Rated operational current
   
AC-3
   
380 V 400 V
IeA18
AC-1
   
Conventional free air thermal current, 3 pole, 50 - 60 Hz
   
Open
   
at 40 °C
Ith =IeA40
enclosed
IthA32
Conventional free air thermal current, 1 pole
   
open
IthA88
enclosed
IthA80
Max. rating for three-phase motors, 50 - 60 Hz
   
AC-3
   
220 V 230 V
PkW5
380 V 400 V
PkW7.5
660 V 690 V
PkW11
AC-4
   
220 V 230 V
PkW2.5
380 V 400 V
PkW4.5
660 V 690 V
PkW6.5
Contacts
   
N/C = Normally closed
  1 NC
Contact sequence
  >
Instructions
  Contacts to EN 50 012.
Auxiliary current, coil connections with spring-cage connection technology.
Main current connections with screw terminals.
with mirror contact.
Can be combined with auxiliary contact
  DILA-XHIC(V)..
Voltage AC/DC
  AC operation
Technical data
General
Standards
  IEC/EN 60947, VDE 0660, UL, CSA
Lifespan, mechanical
   
AC operated
Operationsx 10610
DC operated
Operationsx 10610
Operating frequency, mechanical
   
AC operated
Operations/h 5000
DC operated
Operations/h 5000
Climatic proofing
  Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature
   
Open
 °C-25 - +60
Enclosed
 °C- 25 - 40
Storage
 °C- 40 - 80
Mounting position
  >>
Mechanical shock resistance (IEC/EN 60068-2-27)
   
Half-sinusoidal shock, 10 ms
   
Main contacts
   
N/O contact
 g10
Auxiliary contacts
   
N/O contact
 g7
N/C contact
 g5
Mechanical shock resistance (IEC/EN 60068-2-27) when tabletop-mounted
   
Half-sinusoidal shock, 10 ms
   
Main contacts
   
N/O contact
 g6.9
Auxiliary contacts
   
N/O contact
 g5.3
N/C contact
 g3.5
Degree of Protection
  IP00
Protection against direct contact when actuated from front (EN 50274)
  Finger and back-of-hand proof
Weight
   
AC operated
 kg0.42
DC operated
 kg0.48
Terminal capacity main cable
   
Solid
 mm21 x (0.75 - 16)
2 x (0.75 - 10)
Flexible with ferrule
 mm21 x (0.75 - 16)
2 x (0.75 - 10)
Stranded
 mm21 x 16
Solid or stranded
 AWG18 - 6
Main cable connection screw/bolt
  M5
Tightening torque
 Nm3.2
Tool
   
Main cable
   
Pozidriv screwdriver
 Size2
Standard screwdriver
 mm0.8 x 5.5
1 x 6
Terminal capacity control circuit cables
   
Solid
 mm21 x (0.75 - 2.5)
2 x (0.75 - 2.5)
Flexible
 mm21 x (0.75 - 2.5)
2 x (0.75 - 2.5)
Flexible with ferrule
 mm21 x (0.75 - 1.5)
2 x (0.75 - 1.5)
Solid or stranded
 AWG18 - 14
Tool
   
Stripping length
 mm10
Screwdriver blade width
 mm3.5
Main conducting paths
Rated impulse withstand voltage
UimpV AC8000
Overvoltage category/pollution degree
  III/3
Rated insulation voltage
UiV AC690
Rated operational voltage
UeV AC690
Safe isolation to EN 61140
   
between coil and contacts
 V AC440
between the contacts
 V AC440
Making capacity (p.f. to IEC/EN 60947)
   
 
Up to 690 VA238
Breaking capacity
   
220 V 230 V
 A170
380 V 400 V
 A170
500 V
 A170
660 V 690 V
 A120
Short-circuit rating
   
Short-circuit protection maximum fuse
   
Type “2” coordination
   
400 V
gG/gL 500 VA35
690 V
gG/gL 690 VA35
Type “1” coordination
   
400 V
gG/gL 500 VA63
690 V
gG/gL 690 VA50
AC
AC-1
   
Rated operational current
   
Conventional free air thermal current, 3 pole, 50 - 60 Hz
   
Open
   
at 40 °C
Ith =IeA40
at 50 °C
Ith =IeA38
at 55 °C
Ith =IeA37
at 60 °C
Ith =IeA35
enclosed
IthA32
Conventional free air thermal current, 1 pole
   
open
IthA88
enclosed
IthA80
AC-3
   
Rated operational current
   
Open, 3-pole: 50 – 60 Hz
   
220 V 230 V
IeA18
240 V
IeA18
380 V 400 V
IeA18
415 V
IeA18
440V
IeA18
500 V
IeA18
660 V 690 V
IeA12
380 V 400 V
IeA18
Motor rating
PkWh 
220 V 230 V
PkW5
240V
PkW5.5
380 V 400 V
PkW7.5
415 V
PkW10
440 V
PkW10.5
500 V
PkW12
660 V 690 V
PkW11
AC-4
   
Open, 3-pole: 50 – 60 Hz
   
220 V 230 V
IeA10
240 V
IeA10
380 V 400 V
IeA10
415 V
IeA10
440 V
IeA10
500 V
IeA10
660 V 690 V
IeA8
Motor rating
PkWh 
220 V 230 V
PkW2.5
240 V
PkW3
380 V 400 V
PkW4.5
415 V
PkW5
440 V
PkW5.5
500 V
PkW6
660 V 690 V
PkW6.5
DC
Rated operational current, open
   
DC-1
   
60 V
IeA35
110 V
IeA35
220 V
IeA35
440 V
IeA2.9
DC-3
   
60 V
IeA35
110 V
IeA35
220 V
IeA10
440 V
IeA0.6
DC-5
   
60 V
IeA35
110 V
IeA35
220 V
IeA10
440 V
IeA0.6
Current heat loss
3-pole at Ith
 W8.7
Current heat loss at Ie to AC-3/400 V
 W2.1
Impedance per pole
 mΩ2.7
Magnet systems
Voltage tolerance
 x Uc 
AC operated
Pick-upx Uc0.8 - 1.1
Drop-out voltage AC operated
Drop-outx Uc0.3 - 0.6
DC operated
Pick-upx Uc0.7 - 1.2
DC operated
Drop-outx Uc0.15 - 0.6
Notes
  at least smoothed two-phase bridge rectifier or three-phase rectifier
Power consumption of the coil in a cold state and 1.0 x Uc
   
50 Hz
Pick-upVA52
50 Hz
SealingVA7.1
50 Hz
SealingW2.1
60 Hz
Pick-upVA67
60 Hz
SealingVA8.7
60 Hz
SealingW2.6
50/60 Hz
Pick-upVA62
58
50/60 Hz
SealingVA9.1
6.5
50/60 Hz
SealingW2.5
2
DC operated
Pick-upW12
DC operated
SealingW0.5
Duty factor
  % DF100
Switching times at 100 % Uc (approximate values)
   
Main contacts
   
AC operated
   
Closing delay
 ms16 - 22
Opening delay
 ms8 - 14
DC operated
 ms 
Closing delay
 ms47
Opening delay
 ms30
Arcing time
 ms10
Lifespan, mechanical; Coil 50/60 Hz
 x 106Mechanical lifespan at 50 Hz approx. 30% lower than under “Technical data, general”
Electromagnetic compatibility (EMC)
Emitted interference
  to EN 60947-1
Interference immunity
  to EN 60947-1
Design verification as per IEC/EN 61439(Show features)(Hide features)
Technical data for design verification
   
Rated operational current for specified heat dissipation
InA18
Heat dissipation per pole, current-dependent
PvidW0.7
Equipment heat dissipation, current-dependent
PvidW2.1
Static heat dissipation, non-current-dependent
PvsW2.1
Heat dissipation capacity
PdissW0
Operating ambient temperature min.
 °C-25
Operating ambient temperature max.
 °C60
IEC/EN 61439 design verification
   
10.2 Strength of materials and parts
   
10.2.2 Corrosion resistance
  Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
  Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
  Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
  Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
  Meets the product standard's requirements.
10.2.5 Lifting
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
  Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
  Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
  Meets the product standard's requirements.
10.5 Protection against electric shock
  Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
  Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
  Is the panel builder's responsibility.
10.8 Connections for external conductors
  Is the panel builder's responsibility.
10.9 Insulation properties
   
10.9.2 Power-frequency electric strength
  Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
  Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
  Is the panel builder's responsibility.
10.10 Temperature rise
  The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
  Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
  Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
  The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Technical data ETIM 6.0(Show features)(Hide features)
Low-voltage industrial components (EG000017) / Power contactor, AC switching (EC000066)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Contactor (LV) / Power contactor, AC switching ([email protected] [AAB718012])
Rated control supply voltage Us at AC 50HZ
 V230 - 230
Rated control supply voltage Us at AC 60HZ
 V240 - 240
Rated control supply voltage Us at DC
 V0 - 0
Voltage type for actuating
  AC
Rated operation current Ie at AC-1, 400 V
 A40
Rated operation current Ie at AC-3, 400 V
 A18
Rated operation power at AC-3, 400 V
 kW7.5
Rated operation current Ie at AC-4, 400 V
 A10
Rated operation power Ie at AC-4, 400 V
 kW4.5
Modular version
  No
Number of auxiliary contacts as normally open contact
  0
Number of auxiliary contacts as normally closed contact
  1
Type of electrical connection of main circuit
  Spring clamp connection
Number of normally closed contacts as main contact
  0
Number of main contacts as normally open contact
  3
Approvals
Product Standards  IEC/EN 60947-4-1; UL 508; CSA-C22.2 No. 14-05; CE marking
UL File No.  E29096
UL Category Control No.  NLDX
CSA File No.  012528
CSA Class No.  2411-03, 3211-04
North America Certification  UL listed, CSA certified
Specially designed for North America  No
Characteristics
>
1: Overload relay
2: Suppressor
3: Auxiliary contact modules
>
Squirrel-cage motor
Operating characteristics
Starting:from rest
Stopping:after attaining full running speed
Electrical characteristics
Make: up to 6 x rated motor current
Break: up to 1 x rated motor current
Utilization category
100 % AC-3
Typical applications
Compressors
Lifts
Mixers
Pumps
Escalators
Agitators
Fans
Conveyor belts
Centrifuges
Hinged flaps
Bucket-elevators
Air conditioning system
General drives in manufacturing and processing machines
>
Extreme switching duty
Squirrel-cage motor
Operating characteristics
Inching, plugging, reversing
Electrical characteristics
Make: up to 6 x rated motor current
Break: up to 6 x rated motor current
Utilization category
100 % AC-4
Typical applications
Printing presses
Wire-drawing machines
Centrifuges
Special drives for manufacturing and processing machines
Dimensions
>
Contactor with auxiliary contact module
>
Lateral clearance to earthed parts: 6 mm
CAD data
>Product-specific CAD data
>3D Preview

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields

or