Dimensions (W x H x D)
107.5 x 90 x 72 without/79 with adapter for MCC (6 SU) mm
Mounting
Top-hat rail IEC/EN 60715, 35 mm or screw fixing using 3 fixing brackets ZB4-101-GF1 (accessories)
Solid
0.2/4 (AWG 22 - 12) mm2
Flexible with ferrule
0.2/2.5 (AWG 22 - 12) mm2
Standard screwdriver
0.8 x 3.5 mm
Max. tightening torque
0.6 Nm
Climatic environmental conditions
Operating ambient temperature
-25 to 55, cold as per IEC 60068-2-1, heat as per IEC 60068-2-2 °C
Condensation
Take appropriate measures to prevent condensation
LCD display (clearly legible)
0 - 55 °C
Relative humidity, non-condensing (IEC/EN 60068-2-30)
5 - 95 %
Air pressure (operation)
1080 - 1080 hPa
Ambient conditions, mechanical
Protection type (IEC/EN 60529, EN50178, VBG 4)
IP20
Vibrations (IEC/EN 60068-2-6)Constant amplitude 0.15 mm
10 - 57 Hz
Vibrations (IEC/EN 60068-2-6)Constant acceleration 2 g
57 - 150 Hz
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15 g/11 ms
18 Impacts
Drop to IEC/EN 60068-2-31 [Drop height]
50 mm
Free fall, packaged (IEC/EN 60068-2-32)
1 m
Mounting position
Vertical or horizontal
Electromagnetic compatibility (EMC)
Overvoltage category/pollution degree
II/2
Electrostatic discharge (ESD)applied standard
IEC/EN 61000-4-2, Level 3
Electrostatic discharge (ESD)Air discharge
8 kV
Electrostatic discharge (ESD)Contact discharge
6 kV
Electromagnetic fields (RFI) to IEC EN 61000-4-3
10 V/m
Radio interference suppression
EN 55011 Class B, EN 55022 Class B
Burst
IEC/EN 61000-4-4, level 3 kV
power pulses (Surge)
2 kV (supply cables, symmetrical, EASY...AC)
0.5 kV (supply cables, symmetrical, easy-DC)
according to IEC/EN 61000-4-5
Immunity to line-conducted interference to (IEC/EN 61000-4-6)
10 V
Clearance in air and creepage distances
EN 50178, UL 508, CSA C22.2, No. 142
Insulation resistance
EN 50178
Back-up of real-time clock
Back-up of real-time clock
① Backup time (hours) with fully charged double layer capacitor
② Service life (years)
Accuracy of the real-time clock
part no. ± 5 (± 0.5 h⁄Year) s/day
Write cycles of the retentive memory
10000000000 (10¹⁰) (Read-write cycles)
Rated operational voltage [Ue]
24 DC (-15/+20%) V
Permissible range [Ue]
20.4 - 28.8 V DC
Input current
normally 140 mA at Ue
Voltage dips
≤ 10
(IEC/EN 61131-2) ms
Heat dissipation [P]
Normally 3.4 W
MemoryProgram code/data
256/14 segments of 16 KB each kByte
MemoryMarker/retentive data
16/4/4/8 KByte
Cycle time for 1 k of instructions (Bit, Byte)
< 0.3 ms
PRG interface RS232Data transfer rate
4.8, 9.6, 19.2, 38.4, 57.6, 115.2 (character format: 8 bit data, no parity, 1 stop bit) kBit/s
PRG interface RS232Connection types
RJ45-bus
PRG interface RS232Potential isolation
none
PRG interface RS232Master modeData transfer rate
0.3, 0.6, 1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6 kbit/s
PRG interface RS232Master modeCharacter formats
8E1, 8O1, 8N1, 8N2, 7E2, 7O2, 7N2, 7E1
PRG interface RS232Master modeNumber of transmission bytes in a block
190 bytes
PRG interface RS232Master modeNumber of received bytes in a block
190 bytes
EthernetData transfer rate
10 MBit/s, 100 m Mbit/s
EthernetConnection types
RJ45
EthernetPotential isolation
No
CANopen®Data transfer rate
500 kBit/s, 25 m250 kBit/s, 60m125 kBit/s, 125 m50 kBit/s, 300 m20 kBit/s, 700 m10 kBit/s, 1000 m
CANopen®Bus termination (first and last station)
EASY-NT-R plug (incl. bus terminating resistor 120 Ω)
CANopen®Connection types
2 x RJ45, 8 pole
Mode slaveStations
max. 126 Number
Mode slavePDO type
Asynchronous, cyclic, acyclic
Mode slaveControl contact rated current
To DS 301 V4
Inputs can be used as analog inputs
4 (I7, I8, I11, I12)
Status Display
LCD-Display
Potential isolation
from the outputs: yes
to network easyNet, easyLink
Rated operational voltage [Ue]
24 V DC
Input voltage
< 5 (I1 - I6, I9 - I10) < 8 (I7, I8, I11, I12) at signal "0"
> 15.0 (I1 - I6, I9, I10) > 8.0 (I7, I8, I11, I12) at signal "1" V DC
Input current on 1 signalInput current at signal 1
3.3 (I1 to I6)
2.2 (I7, I8)
3.3 (I9, I10)
2.2 (I11, I12) mA
Deceleration time
normally 0.02 (I1 - I4), normally 0.25 (I5 - I12) (from ''0'' to "1")
normally 0.02 (I1 - I4), normally 0.25 (I5 - I12) (from ''0'' to "1") ms
Cable length
100 (unshielded) m
Incremental counterNumber of counter inputs
1 (I1, I2, I3, I4)
Incremental counterValue range
32 Bit
Incremental counterCounter frequency
≦ 40 kHz
Incremental counterPulse shape
Square
Incremental counterCounter inputs
I1, I2
Incremental counterReference input
I3
Incremental counterInput for reference switch
I4
Incremental counterCounter inputs I1 and I2, I3 and I4
1
Incremental counterSignal offset
90°
Rapid counter inputsNumber
2 (I1, I2) at 16 Bit or 1 (I1) at 32 Bit
Rapid counter inputsValue range
16/32 Bit
Rapid counter inputsCable length
≦ 20 (screened) m
Rapid counter inputsCounter frequency
≦ 50 kHz
Rapid counter inputsPulse shape
Square
Number
4 (I7, I8, I11, I12)
Potential isolation
from the outputs: yes
to interface/memory card: no
Resolution
0.01 V analog
0.01 V digital
10 Bit (value 0 - 1023)
Accuracy of actual valueWithin a single device
± 2, (I7, I8, I11, I12) ± 0.12 V %
Conversion time, analog/digital
each CPU cycle ms
Cable length
≦ 30, screened m
Rated operational voltage [Ue]
24 V DC
Permissible range [Ue]
20.4 - 28.8 V DC
Supply current
Norm./max. 18/32 at signal 0
24/44 at signal 1 mA
Protection against polarity reversal
yes (Caution: A short circuit will result if 0 V or earth is applied to the outputs in the event that the supply voltage is connected to the wrong poles.)
Potential isolation
from power supply, inputs
to the memory card: yes
From the inputs: yes
Rated operational current at signal „1” DC per channel [Ie]
Max. 0.5 A
Lamp load without Rvper channel
5 W
Residual current on 0 signal per channel
< 0.1 mA
Max. output voltage
2.5 (signal 0 at external load < 10 MΩ)
U = Ue- 1 V (signal 1 at Ie= 0.5 A) V
Short-circuit protection
Yes, electronic (Q1 - Q4), thermal (Q5 - Q8), (analysis via diagnostics input I16, I15)
Short-circuit tripping current for Ra≦ 10 mΩ
0.7 ≦ Ie≦ 2 per output A
Total short-circuit current
16 A
Peak short-circuit current
32 A
Max. operating frequency with constant resistive load
40000 Operations/h
Parallel connection of outputsWith resistive load, inductive load with external suppressor circuit, combination within a group
Group 1: Q1 - Q4
Group 2: Q5 - Q8
Parallel connection of outputsNumber of outputs [max.]
4
Parallel connection of outputsMax. total current
2 (Caution! Outputs must be actuated simultaneously and for the same length of time.) A
Output status indication
LCD-display
Inductive load to EN 60947-5-1Without external suppressor circuitT0.95 = 1 ms, R = 48 Ω, L = 16 mHUtilization factor
0.25 g
Inductive load to EN 60947-5-1Without external suppressor circuitT0.95 = 1 ms, R = 48 Ω, L = 16 mHDuty factor
100 % DF
Inductive load to EN 60947-5-1Without external suppressor circuitT0.95 = 1 ms, R = 48 Ω, L = 16 mHMax. switching frequency f = 0.5 Hz (max. DF = 50 %)
1500 Operations
Inductive load to EN 60947-5-1Without external suppressor circuitDC-13, T0.95 = 72 ms, R = 48 Ω, L = 1.15 HUtilization factor
0.25 g
Inductive load to EN 60947-5-1Without external suppressor circuitDC-13, T0.95 = 72 ms, R = 48 Ω, L = 1.15 HDuty factor
100 % DF
Inductive load to EN 60947-5-1Without external suppressor circuitDC-13, T0.95 = 72 ms, R = 48 Ω, L = 1.15 HMax. switching frequency f = 0.5 Hz (max. DF = 50 %)
1500 Operations
Inductive load to EN 60947-5-1Without external suppressor circuitT0.95 = 15 ms, R = 48 Ω, L = 0.24 HUtilization factor
0.25 g
Inductive load to EN 60947-5-1Without external suppressor circuitT0.95 = 15 ms, R = 48 Ω, L = 0.24 HDuty factor
100 % DF
Inductive load to EN 60947-5-1Without external suppressor circuitT0.95 = 15 ms, R = 48 Ω, L = 0.24 HMax. switching frequency f = 0.5 Hz (max. DF = 50 %)
1500 Operations
Inductive load to EN 60947-5-1With external suppressor circuitUtilization factor
1 g
Inductive load to EN 60947-5-1With external suppressor circuitDuty factor
100 % DF
Inductive load to EN 60947-5-1With external suppressor circuitMax. switching frequency, max. duty factor
Depending on the suppressor circuit Operations
Protection against polarity reversal
yes (Caution: A short circuit will result if 0 V or earth is applied to the outputs in the event that the supply voltage is connected to the wrong poles.)
Bus termination (first and last station)
EASY-NT-R plug (incl. bus terminating resistor 120 Ω)