NZMB2-AF90-NA 269163 EATON MOELLER Circuit-breaker, 3p, 90A View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

NZMB2-AF90-NA 269163 EATON MOELLER Circuit-breaker, 3p, 90A

NZMB2-AF90-NA

269163

EATON - MOELLER

Available

Ship on today

Circuit-breaker, 3p, 90A

More details


Circuit Breakers Electrical Power

Circuit-breakers NZM - EATON - MOELLER

Compact circuit-breaker, up to 160A - EATON - MOELLER

* Brand new produt in its original packing covered by the warranties and certifications provided by EATON - MOELLER

QuantityPrice
1+$274.75
2+$269.64
*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Delivery programme
Product range
  Circuit-breaker
Protective function
  System and cable protection
Standard/Approval
  UL/CSA, IEC
Release system
  Thermomagnetic release
Installation type
  Fixed
Description
  Switches conform to UL/CSA as well as the IEC regulations. IEC switching performance values are contained on the rating plate.
Fixed overload releases Ir
Frame size
  NZM2
Number of poles
  3 pole
Standard equipment
  Screw connection
Switching capacity
   
SCCR 480Y/277 V 60 Hz
IcukA25
SCCR 480 V 60 Hz
IcukA25
SCCR 600Y/347 V 60 Hz
IcukA18
Rated current = rated uninterrupted current
   
Rated current = rated uninterrupted current
In = IuA90
Setting range
   
Overload trip
   
General
Standards
  IEC/EN 60947
Protection against direct contact
  Finger and back of hand proof to VDE 0106 Part 100
Climatic proofing
  Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature
   
Ambient temperature, storage
 °C- -25 - + 70
Operation
 °C-25 - +70
Mechanical shock resistance (10 ms half-sinusoidal shock) according to IEC 60068-2-27
 g20 (half-sinusoidal shock 20 ms)
Safe isolation to EN 61140
   
Between auxiliary contacts and main contacts
 V AC500
between the auxiliary contacts
 V AC300
Weight
 kg2.345
Mounting position
   
Mounting position
  
Vertical and 90° in all directions
 
Basic equipment        
 Box terminal  - - -
 Screw connection -   
Accessories        
 Box terminal -   -
 Screw connection  - - 
 Tunnel terminal    
 Connection on rear    
 Flat conductor terminal - - - 
Round copper conductor
   
Box terminal
   
Solid
 mm21 x (12 … 6)
Stranded
 mm21 x (4 … 350)
Tunnel terminal
   
Solid
 mm21 x 16
Stranded
 mm2 
Stranded
 mm21 x (4 … 350)
Bolt terminal and rear-side connection
   
Direct on the switch
   
Solid
 mm21 x (11 … 6)
Stranded
 mm21 x (4 … 3/0)
Al conductors, Cu cable
   
 
   
Solid
 mm21 x 16
Bolt terminal and rear-side connection
   
Flat copper strip, with holes
min.mm2 x 16 x 0.8
Flat copper strip, with holes
max.mm10 x 16 x 0.8
Cu strip (number of segments x width x segment thickness)
   
Box terminal
   
 
min.mm2 x 9 x 0.8
 
max.mm10 x 16 x 0.8
Bolt terminal and rear-side connection
   
Flat copper strip, with holes
min.mm2 x 16 x 0.8
Flat copper strip, with holes
max.mm10 x 16 x 0.8
Copper busbar (width x thickness)
mm  
Bolt terminal and rear-side connection
   
Screw connection
  M8
Direct on the switch
   
 
min.mm16 x 5
 
max.mm20 x 5
Control cables
   
 
 mm21 x (18 … 14)
2 x (18 … 16)
Design verification as per IEC/EN 61439(Show features)(Hide features)
Technical data for design verification
   
Rated operational current for specified heat dissipation
InA90
Equipment heat dissipation, current-dependent
PvidW20.78
Operating ambient temperature min.
 °C-25
Operating ambient temperature max.
 °C70
IEC/EN 61439 design verification
   
10.2 Strength of materials and parts
   
10.2.2 Corrosion resistance
  Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
  Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
  Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
  Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
  Meets the product standard's requirements.
10.2.5 Lifting
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
  Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
  Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
  Meets the product standard's requirements.
10.5 Protection against electric shock
  Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
  Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
  Is the panel builder's responsibility.
10.8 Connections for external conductors
  Is the panel builder's responsibility.
10.9 Insulation properties
   
10.9.2 Power-frequency electric strength
  Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
  Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
  Is the panel builder's responsibility.
10.10 Temperature rise
  The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
  Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
  Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
  The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Technical data ETIM 6.0
Low-voltage industrial components (EG000017) / Power circuit-breaker for trafo/generator/installation prot. (EC000228)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Circuit breaker (LV < 1 kV) / Circuit breaker for power transformer, generator and system protection ([email protected] [AJZ716010])
Rated permanent current Iu
 A90
Rated voltage
 V440 - 440
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
 kA25
Overload release current setting
 A90 - 90
Adjustment range short-term delayed short-circuit release
 A0 - 0
Adjustment range undelayed short-circuit release
 A600 - 1000
Integrated earth fault protection
  No
Type of electrical connection of main circuit
  Screw connection
Device construction
  Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
  No
DIN rail (top hat rail) mounting optional
  Yes
Number of auxiliary contacts as normally closed contact
  0
Number of auxiliary contacts as normally open contact
  0
Number of auxiliary contacts as change-over contact
  0
Switched-off indicator available
  No
With under voltage release
  No
Number of poles
  3
Position of connection for main current circuit
  Front side
Type of control element
  Rocker lever
Complete device with protection unit
  Yes
Motor drive integrated
  No
Motor drive optional
  Yes
Degree of protection (IP)
  IP20
Approvals
Product Standards  UL 489; CSA-C22.2 No. 5-09; IEC 60947-2; CE marking
UL File No.  E31593
UL Category Control No.  DIVQ
CSA File No.  022086
CSA Class No.  1432-01
North America Certification  UL listed, CSA certified
Specially designed for North America  Yes
Suitable for  Feeder circuits, branch circuits
Current Limiting Circuit-Breaker  Yes
Max. Voltage Rating  600Y/347 V, 480 V
Degree of Protection  IEC: IP20; UL/CSA Type: -
Characteristics
IL01206006Z (AWA1230-1916) Circuit-Breaker, basic unit
 
>>

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields

or