Rated surge voltage invariability [Uimp]Main contacts
8000 V
Rated surge voltage invariability [Uimp]Auxiliary contacts
6000 V
Rated operational voltage [Ue]
1000 V AC
Rated current = rated uninterrupted current [In= Iu]
450 A
Overvoltage category/pollution degree
III/3
Rated insulation voltage [Ui]
1000 V
Ambient temperatureAmbient temperature, storage
- 40 - + 70 °C
Ambient temperatureOperation
-25 - +70 °C
Rated short-circuit making capacity [Icm]
240 V 50/60 Hz [Icm]
330 kA
400/415 V 50/60 Hz [Icm]
330 kA
440 V 50/60 Hz [Icm]
286 kA
525 V 50/60 Hz [Icm]
143 kA
1000 V 50/60 Hz [Icm]
17 kA
Rated short-circuit breaking capacity Icn[Icn]
Icu to IEC/EN 60947 test cycle O-t-CO [Icu]240 V 50/60 Hz [Icu]
150 kA
Icu to IEC/EN 60947 test cycle O-t-CO [Icu]400/415 V 50 Hz [Icu]
150 kA
Icu to IEC/EN 60947 test cycle O-t-CO [Icu]440 V 50/60 Hz [Icu]
130 kA
Icu to IEC/EN 60947 test cycle O-t-CO [Icu]525 V 50/60 Hz [Icu]
65 kA
Icu to IEC/EN 60947 test cycle O-t-CO [Icu]690 V 50/60 Hz [Icu]
35 kA
Icu to IEC/EN 60947 test cycle O-t-CO [Icu]1000 V 50/60 Hz [Icu]
15 kA
Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics]230 V 50/60 Hz [Ics]
150 kA
Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics]400/415 V 50/60 Hz [Ics]
150 kA
Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics]440 V 50/60 Hz [Ics]
130 kA
Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics]525 V 50/60 Hz [Ics]
33 kA
Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics]690 V 50/60 Hz [Ics]
9 kA
Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics]1000 V AC [Ics]
10 kA
Rated short-time withstand current
Lifespan, mechanical [Operations]
15000
Max. operating frequency
60 Ops/h
Lifespan, mechanical: of which max. 50 % trip by shunt/undervoltage release
1000 V 50/60 Hz [Operations]
1000
Standard equipment
Screw connection
Round copper conductorBox terminalSolid
2 x 16 mm2
Round copper conductorBox terminalStranded
1 x (35 - 240)
2 x (25 - 120) mm2
Round copper conductorTunnel terminalStrandedStranded
1 x (25 - 185) mm2
Round copper conductorTunnel terminalStrandedDouble hole
1 x (50 - 240)
2 x (50 - 240) mm2
Round copper conductorBolt terminal and rear-side connectionDirect on the switchSolid
1 x 16
2 x (10 - 16 mm2
Round copper conductorBolt terminal and rear-side connectionDirect on the switchStranded
1 x (25 - 120)
2 x (25 - 120) mm2
Al conductors, Cu cableTunnel terminalSolid
1 x 16 mm2
Al conductors, Cu cableTunnel terminalStrandedStranded
1 x (25 - 185)2)mm2
Al conductors, Cu cableTunnel terminalStranded
2)Up to 240 mm² can be connected depending on the cable manufacturer.
Al conductors, Cu cableTunnel terminalStrandedDouble hole
1 x (50 - 240)
2 x (50 - 240) mm2
Cu strip (number of segments x width x segment thickness)Box terminal [min.]
6 x 16 x 0.8 mm
Cu strip (number of segments x width x segment thickness)Box terminal [max.]
10 x 24 x 1.0
+ 5 x 24 x 1.0
(2 x) 8 x 24 x 1.0 mm
Cu strip (number of segments x width x segment thickness)Bolt terminal and rear-side connectionFlat copper strip, with holes [min.]
6 x 16 x 0.8 mm
Cu strip (number of segments x width x segment thickness)Bolt terminal and rear-side connectionFlat copper strip, with holes [max.]
10 x 32 x 1.0 + 5 x 32 x 1.0 mm
Cu strip (number of segments x width x segment thickness)Bolt terminal and rear-side connectionConnection width extension
(2 x) 10 x 50 x 1.0 mm
Copper busbar (width x thickness) [mm]Bolt terminal and rear-side connectionScrew connection
M10
Copper busbar (width x thickness) [mm]Bolt terminal and rear-side connectionDirect on the switch [min.]
20 x 5 mm
Copper busbar (width x thickness) [mm]Bolt terminal and rear-side connectionDirect on the switch [max.]
30 x 10
+ 30 x 5 mm
Copper busbar (width x thickness) [mm]Bolt terminal and rear-side connectionConnection width extensionConnection width extension [max.]
2 x (10 x 50) mm
Control cables
1 x (0.75 - 2.5)
2 x (0.75 - 1.5) mm2