IZMX40B3-V40F 149676 EATON ELECTRIC Circuit-breaker, 3p, 4000 A, fixed View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

IZMX40B3-V40F 149676 EATON ELECTRIC Circuit-breaker, 3p, 4000 A, fixed

IZMX40B3-V40F

149676

EATON-MOELLER

Circuit-breaker, 3p, 4000 A, fixed

More details


Home > EATON - MOELLER

* Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Delivery program
Product range
Air circuit-breakers/switch-disconnectors
Product range
Open circuit-breakers
Current Range
Up to 4000 A
Protective function
Selective operation
Installation type
Fixed
Main terminals must be separately ordered.
Construction size
IZMX40
Release system
Electronic release
Standard/Approval
IEC
Number of poles
3 pole
Degree of Protection
IP20, IP55 with protective cover, IP41 door sealing frame
suitable for zone selectivity
optionally fittable by user with comprehensive accessories
Rated current = rated uninterrupted current
In= Iu A 4000
up to 440 V 50/60 Hz
Icu kA 66
up to 440 V 50/60 Hz
Ics kA 66
Overload release, min.
Ir A 2000
Overload release, max.
Ir A 4000
Non-delayed
Ii= Inx … 2 - 12, OFF
Delayed
Isd= Irx … 2 - 10
Technical data
General
Standards
IEC/EN 60947
Ambient temperature
Storage
ϑ °C -40 - +70
Ambient temperature
°C -25 - +70
Mounting position
Utilization category
B
Degree of Protection
IP20, IP55 with protective cover, IP41 door sealing frame
Direction of incoming supply
as required
Main conducting paths
Rated current = rated uninterrupted current
In= Iu A 4000
Rated uninterrupted current at 50 °C
Iu A 4000
Rated uninterrupted current at 60 °C
Iu A 3650
Rated uninterrupted current at 70 °C
Iu A 3500
Rated impulse withstand voltage
Uimp V AC 12000
Rated operational voltage
Ue V AC 690
Use in IT electrical power networks up to U = 440 V
IIT kA 57.6
Overvoltage category/pollution degree
III/3
Rated insulation voltage
Ui V 1000
Switching capacity
Rated short-circuit making capacity
Icm
up to 440 V 50/60 Hz
Icm kA 145
up to 690 V 50/60 Hz
Icm kA 145
Rated short-time withstand current 50/60 Hz
t = 1 s
Icw kA 66
t = 3 s
Icw kA 53
Rated short-circuit breaking capacity Icn
Icn
IEC/EN 60947 operating sequence IcuO-t-CO
up to 240 V 50/60 Hz
Icu kA 66
up to 440 V 50/60 Hz
Icu kA 66
up to 690 V 50/60 Hz
Icu kA 66
IEC/EN 60947 operating sequence IcsO-t-CO-t-CO
up to 240 V 50/60 Hz
Ics kA 66
up to 440 V 50/60 Hz
Ics kA 66
up to 690 V 50/60 Hz
Ics kA 66
Operating times
Closing delay via spring release
ms 35
Total opening delay via shunt release
ms 22
Total opening delay via undervoltage release
ms 37
Total opening delay on non-delayed short-circuit release (up to complete arc quenching)
ms 45
Maximum operating frequency
Operations/h 60
Heat dissipation at rated current In
Fixed mounting
W 600
Weight
Fixed mounting
3-pole
kg 43
4-pole
kg 56
Terminal capacities
Copper bar
Fixed mounting
Black
mm 4 x 100 x 10
These are values used in separate switchgear. The actual values will depend on the temperature around the circuit-breaker, which is influenced by the ambient temperature, the degree of protection (IP), the mounting height, the partitions, and any external ventilation. Depending on the specific switchgear design, this may result in derating, which can then be compensated for by increasing the cross-sectional area. Temperature rise tests in the specific switchgear can provide specific and detailed information.


Permissible continuous current for circuit‐breakers operating in switchboards at various internal ambient temperatures. The switchboard’s internal ambient temperature should be estimated using the calculation methods of IEC regulation.

With vertical universal connection.

Technical data ETIM 7.0
Low-voltage industrial components (EG000017) / Power circuit-breaker for trafo/generator/installation protection (EC000228)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Circuit breaker (LV < 1 kV) / Circuit breaker for power transformer, generator and system protection ([email protected] [AJZ716013])
Rated permanent current Iu
A 4000
Rated voltage
V 690 - 690
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
kA 66
Overload release current setting
A 2000 - 4000
Adjustment range short-term delayed short-circuit release
A 8000 - 40000
Adjustment range undelayed short-circuit release
A 8000 - 48000
Integrated earth fault protection
No
Type of electrical connection of main circuit
Rail connection
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
2
With switched-off indicator
Yes
With under voltage release
No
Number of poles
3
Position of connection for main current circuit
Back side
Position of connection for main current circuit
Rear
Type of control element
Push button
Complete device with protection unit
Yes
Motor drive integrated
No
Motor drive optional
Yes
Degree of protection (IP)
IP20

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.