Product name
Eaton xEnergy Safety Ci empty enclosure base
Product Length/Depth
150 millimetre
Product height
250 millimetre
Product width
375 millimetre
Product weight
1.168 kilogram
Certifications
EN 61439-2
EN 62208
Product Tradename
xEnergy Safety Ci
Product Type
Empty enclosure
Type
Basic enclosureEnclosure basesxEnergy Safety Ci
Accessory/spare part type
Bases for panel enclosures
Technical Data - Electrical
Technical Data - Mechanical
Base type
Closed, with full area knockout
Enclosure material
Plastic
Width in number of modular spacings
15
Mounting method
Surface mounted (plaster)
Degree of protection
IK10
Other
IP65
Number of conduit inlets
76
Number of openings (flange plates)
4
Cable entry type
FL4... flange
FL3... flange
Transverse
Top and bottom
Cover/door type
Optional
None
Plate thickness (cabinet)
6 mm
Plate thickness (cover/door)
6 mm
Temperature-rise verification as per IEC 60890
Heat diss. ambient 35°C delta T: 20°C wall mount middle encl. top (IEC 60890)
17 W
Heat diss. ambient 35°C delta T: 35°C wall mount middle encl. top (IEC 60890)
34 W
Heat diss. ambient 35°C delta T:20°C wall mount individ. encl. top (IEC 60890)
19 W
Heat diss. ambient 35°C delta T:20°C wall mount starting encl. top (IEC 60890)
18 W
Heat diss. ambient 35°C delta T:35°C wall mount individ. encl. top (IEC 60890)
38 W
Heat diss. ambient 35°C delta T:35°C wall mount starting encl. top (IEC 60890)
36 W
Design verification as per IEC/EN 61439
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
960 °C
10.2.4 Resistance to ultra-violet (UV) radiation
Not relevant to indoor installations.
10.2.5 Lifting
10 kg per enclosure with support frame and lifting aid met; assembled and secured as per the latest applicable instruction leaflet.
10.2.6 Mechanical impact
IK10
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
IP65, with cover
10.4 Clearances and creepage distances
Is the panel builder's responsibility.
10.5 Protection against electric shock
Protection class 2, therefore not applicable.
10.6 Incorporation of switching devices and components
Is the panel builder's responsibility.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Ui = 1000 V AC
10.9.3 Impulse withstand voltage
8 kV
10.9.4 Testing of enclosures made of insulating material
Meets the product standard's requirements.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
Meets the product standard's requirements.
Features
Cover with overpressure release
Functions
Extension possible
Special features
Flanges →#024355Distance frame for CI45... →#110103Sides closed, but with full area knockoutOpen tip and bottom
Suitable for
Lightning protection
Outdoor use