Product name
Eaton Moeller® series M22 Accessory AS-Interface connection
Product Length/Depth
40 millimetre
Product height
30 millimetre
Product width
40 millimetre
Product weight
0.017 kilogram
Certifications
CSA-C22.2 No. 14-05
CSA Class No.: 3211-03
CSA-C22.2 No. 94-91
CSA File No.: 012528
UL Category Control No.: NKCR
EN 50295_x
EN 50178
CSA
UL
UL File No.: E29184
CE
UL 508
IEC/EN 60947-5
Product Sub Type
AS-Interface connection
Catalog Notes
Adapter element for RMQ-Titan or FAK
AS-Interface information:
AS-Interface slave
for the following RMQ-Titan contact and LED elements:
Power supply completely via AS interface cable (26.5 - 31.6 V DC)
Current consumption
45 mA, max. total current, Emergency-Stop circuits
Input
Inputs for 2 contact elements (M22-K01 (N/C), M22-K01 (N/O))
2-channel inputs (22 V/5 mA, AS-Interface, moduled by code sequence, 2 break contact sets RMQ-Titan M22-K01)
1 dual-channel input
Output
Output for 1 LED element: M22-LED-...
1 Output (19 V/8 mA), Emergency-Stop circuits, Short-circuit proof
1 Output
Product category
Accessories
Protocol
AS-Interface (S-7.B.E)
Ambient conditions, mechanical
Mounting position
As required
Shock resistance
Mechanical, According to IEC/EN 60068-2-27
30 g, Mechanical, According to IEC/EN 60068-2-27, Shock duration 11 ms
Climatic environmental conditions
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
70 °C
Climatic proofing
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78
Addressing
Address set via connection to AS-Interface cable
Connection to SmartWire-DT
No
Connection type
Base fixing for RMQ-Titan
LED indicator
Status indication of Power AS-Interface cable: Green LED on the back
Status indication of Error AS-Interface, failure of AS-Interface master: Red LED on the back
Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
1.5 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.