CARLO GAVAZZI

Selected parameters SYSTEM System HOUSING Rectangular SENSING FUNCTION Filling CONNECTION Plug and socket OUTPUT Relay DPDT MATERIAL Plastic Others HOUSING 80 x 75 x 35 mm SENSING FUNCTION VR or VRY sensors MATERIAL NORYL

Amplifier for Vr and VRY level sensor, max./min fill control, 24 Vdc power supply

More details


Home > CARLO GAVAZZI

* Brand new product in its original packaging covered by the warranties and certifications provided by CARLO GAVAZZI

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Level Sensors
Amplifier, Capacitive
TypesSV 150/250, SV 160/260
• Level control for solid, fluid, or granulated substances
• SV 150/250: Max./min. control of DISCHARGING
• SV 160/260: Max./min. control of CHARGING
• Factory-set sensitivity
• For capacitive sensors VR.. and VRY..
• 10 A SPDT or 8 A DPDT output relay
• LED-indication: SV 150/250: Power supply and relay ON
• SV 160/260: Relay ON
• AC or DC power supply
SV 150/250
SV 160/260
Product DescriptionOrdering KeySV 150 024
Level control relays for capacitive sensors, types VR and VRY. The relays can con-
trol one or two levels of charging (SV 160/260) or dis- charging (SV 150/250).
Housing
Output
Power supply
TypeSelection
PlugOutputFunctionSupply: 24 VAC Supply: 115 VACSupply: 230 VAC Supply: 24 VDC
CircularSPDTDischargingSV 150 024SV 150 115SV 150 230 SV 150 724
DPDTDischargingSV 250 024SV 250 115SV 250 230 SV 250 724
SPDTCharging SV 160 024SV 160 115SV 160 230 SV 160 724
DPDTCharging SV 260 024SV 260 115SV 260 230 SV 260 724
InputSpecifications
SensitivityDepends on sensor type and material
Sensor voltageMax. 24 VDC
Terminal 6 is negative
Sensor currentActivated Min. 15 mA, max. 20 mA Not activated Max. < 5 mA
Sensor short-circuit currentMax. 45 mA
General Specifications
Indication for
Output ONLED, red
Power supplyLED, green
(only SV 150/250)
Supply Specifications
Power supply AC-types Overvoltage cat. II (IEC 60664) Rated operational voltage
through pin 2 & 10230 230 VAC ± 15%
115 115 VAC ± 15%
024 24 VAC ± 15% Rated insulation voltage ³ 2.0 kVAC (rms) Rated impulse withstand
voltage4 kV (1.2/50 µs) (line/neutral)
Power supply DC-types Installation cat. II (IEC 60664) Rated operational voltage724 24 VDC ±15% (pin 2 pos.) Rated insulation voltage None
Rated transient protection volt. 800 V (1.2/50 µs)
Environment
Degree of protection IP 20 B Pollution degree 3 (IEC 60664)
Operating temperature -20° to +50°C (-4° to +122°F) Storage temperature-50° to +85°C (-58° to +185°F)
ApprovalsUL, CSA
CE-marking Yes
Specifications are subject to change without notice (11.06.03) 1

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.