CLD2EB1BU24 CARLO GAVAZZI Selected parameters SYSTEM System HOUSING 1-DIN SENSING FUNCTION Filling or Emptyi.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

CLD2EB1BU24 CARLO GAVAZZI Selected parameters SYSTEM System HOUSING 1-DIN SENSING FUNCTION Filling or Emptyi..

CLD2EB1BU24

CLD2EB1BU24

CARLO GAVAZZI

Available

Ship on today

Selected parameters SYSTEM System HOUSING 1-DIN SENSING FUNCTION Filling or Emptying CONNECTION Terminals OUTPUT Relay SPDT MATERIAL PA66 Others HOUSING 17.5 x 90 x 67.2 mm SENSING FUNCTION 250 oHm to 500 koHm MATERIAL PA66

More details


Level Sensors Detectors Measurement

Sensors

Conductive Level Sensors

* Brand new produt in its original packing covered by the warranties and certifications provided by CARLO GAVAZZI

QuantityPrice
1+$60.79
4+$57.08
7+$55.97
10+$55.35
14+$54.87
*This price is per unit and is the net value (not including taxes if applicable).

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Conductive Sensors
2-point level controller
Type CL with potentiometer
• Conductive level controller
• Sensitivity adjustment from 250 Ω to 500 KΩ
• For filling or emptying applications
• Low-voltage AC electrodes
• Easy installation on DIN rails
• Rated operational voltage:
24 to 240 VAC/DC
• Output 1 x 8 A / 250 VAC SPDT relay
• LED indication for: Output ON and Power ON
Product Description
Ordering Key
CLD2EB1BU24
µ-Processor based level controller for liquids with a wide sensitivity range (like sewage water, chemicals, salt water etc.).
Max./min. control of charging/ discharging. The sensitivity is adjustable by means of the potentiometer.
1 x 8 A SPDT relay output.
Conductive level
DIN rail
No of inputs
Charge/discharge
Basic with potentiometer
1 relay output Relay SPDT Power supply
Type Selection
MountingRelay Ordering no.
Supply: 24-240 VAC/DC
DIN-railSPDT CLD2EB1BU24
Specifications
Rated operational voltage (UB)
Pin 2 & 10 20 to 265 VAC/DC, 45 to 65 Hz
Rated insulation voltage <2.0 kVAC (rms) Rated impulse withstand
voltage4 kV (1.2/50 µs) (line/neutral)
Rated operational power
230 VAC/DC supply2 W
24 VAC/DC supply1 W Delay on operate (tV) < 2 s Outputs
Rated insulation voltage 250 VAC (rms) (cont./elec.)
Relay Rating (AgCdO) µ (micro gap)
Resistive loads AC1 8 A / 250 VAC (2500 VA) DC1 1 A / 250 VDC (250 W)
or 10 A / 25 VDC (250 W) Small induc. LoadsAC15 0,4 A / 250 VAC
DC13 0,4 A / 30 VDC Mechanical life (typical)≥30 x 106 operations
@ 18’000 imp/h
Electrical life (typical) AC1 > 250’000 operations
Level probe supply Max. 5 VAC Level probe current Max. 2 mA Sensitivity250Ω to 500KΩ
Factory settings standard
range “S” 100KΩ
Ranges L (Low sensitivity)250 Ω to 5 KΩ, CF* = 4.7 nF Ranges S (Standard sensitivity) 5 KΩ to 100 KΩ, CF* = 2.2 nF Ranges H (High sensitivity) 50 KΩ to 500 KΩ, CF* = 1.0 nF
Dielectric voltage>2.0 KVAC (rms) (contacts / electronics)
Rated impulse withstand volt. 4 kV (1.2/50 µS) (contacts /
electronics) (IEC 664)
Operating frequency (f)
Relay output1 Hz
Response time
OFF-ON (ton)1 s
ON-OFF (toff)1 s
Environment
Overvoltage category III (IEC 60664)
Degree of protection IP 20 (IEC 60529, 60947-1) Pollution degree 2 (IEC 60664/60664A,
60947-1)
Temperature
Operating-20º to +50ºC (-4º to + 122ºF) Storage -40º to +85ºC (-40º to +185ºF)
Housing material PA66, light grey
Weight
AC/DC supply 125 g
UL Approvals cULus UL508
CE markingYes
*CF = maximum Cable Capacitance
Specifications are subject to change without notice (30.07.2014) 1

Datasheet - PDF

Title:Language:Size:Type:
pdf1-mostradoSelected parameters SYSTEM System HOUSING 1-DIN SENSING FUNCTION Filling or Emptying - CARLO GAVAEnglish268 Kbytespdf1-mostradoSelected parameters SYSTEM System HOUSING 1-DIN SENSING FUNCTION Filling or Emptying - CARLO GAVA
pdf1-Selected parameters SYSTEM System HOUSING 1-DIN SENSING FUNCTION Filling or Emptying - CARLO GAEnglish12 Mbytespdf1-mostradoSelected parameters SYSTEM System HOUSING 1-DIN SENSING FUNCTION Filling or Emptying - CARLO GAVA
pdf2-mostradoSelected parameters SYSTEM System HOUSING 1-DIN SENSING FUNCTION Filling or Emptying - CARLO GAVAEnglish200 Kbytespdf1-mostradoSelected parameters SYSTEM System HOUSING 1-DIN SENSING FUNCTION Filling or Emptying - CARLO GAVA

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review