MP3100 CARLO GAVAZZI Selected parameters PRIMARY CURRENT VALUE 100 A SECONDARY CURRENT / OUTPUT SIGNAL 4 Vp .. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

MP3100 CARLO GAVAZZI Selected parameters PRIMARY CURRENT VALUE 100 A SECONDARY CURRENT / OUTPUT SIGNAL 4 Vp ..

MP3100

MP3100

CARLO GAVAZZI

Available

Ship on today

Selected parameters PRIMARY CURRENT VALUE 100 A SECONDARY CURRENT / OUTPUT SIGNAL 4 Vp Others SYSTEM 3-phase MOUNTING Panel HOUSING Solid-core

More details


Energy Meters Control Analizers

Controls

Monitoring Relays and Measurement Current Transformers

* Brand new produt in its original packing covered by the warranties and certifications provided by CARLO GAVAZZI

QuantityPrice
1+$181.11
2+$176.54
3+$174.28
4+$172.83
5+$172.47
*This price is per unit and is the net value (not including taxes if applicable).

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Current and VoltageControls
Current Transformer, 3-Phase
Types MP 3005, MP 3020, MP 3100, MP 3500
• 4 types of input:
0.5 - 5 A
2- 20 A
10- 100 A
50- 500 A
• For use in connection with control relays types e.g. DIB02, PIB02, DUA01, PUA01
Product Description
Ordering Key
MP 3005
3-phase current transformers for5, 20, 100 or500 AAC.
Type Selection
Output voltage (0.4 - 4 Vp) is proportional to measured cur- rent.
Type
Input current
Input currentType no.
5 A MP 3005
20 A MP 3020
100 A MP 3100
500 A MP 3500
InputSpecifications
MP 3005 MP 3020MP 3100 MP 3500
Current range0.5 - 5 AAC2 - 20 AAC 10 - 100 AAC50 - 500 AAC Max. current (continuously)20 AAC50 AAC150 AAC500 AAC Rated insulation voltage
Input-output1000 VACrms1000 VACrms1000 VACrms1000 VACrms
Overvoltage category IV (IEC 60664) IV (IEC 60664)IV (IEC 60664) IV (IEC 60664) Pollution degree 3 (IEC 60664)3 (IEC 60664) 3 (IEC 60664)3 (IEC 60664) Dielectric strength
Dielectric voltage6 kVACrms 6 kVACrms 6 kVACrms 6 kVACrms
Rated impulse withstand volt.12 kV (1.2/50 µs) 12 kV (1.2/50 µs)12 kV (1.2/50 µs) 12 kV (1.2/50 µs)
Power consumption< 300 mW @ 5 A< 300 mW @ 20 A < 2 W @ 100 A < 21 W @ 500 A
Output Specifications
MP 3005 MP 3020MP 3100 MP 3500
Output voltage
(in connection with SM 115) 0.4 - 4 Vp0.4 - 4 Vp0.4 - 4 Vp0.4 - 4 Vp
Rated insulation voltage (cable) 250 VACrms 250 VACrms 250 VACrms 250 VACrms
Specifications are subject to change without notice (28.10.03)1

Datasheet - PDF

Title:Language:Size:Type:
pdf1-mostradoSelected parameters PRIMARY CURRENT VALUE 100 A SECONDARY CURRENT / OUTPUT SIGNAL 4 Vp Othe - CAREnglish105 Kbytespdf1-mostradoSelected parameters PRIMARY CURRENT VALUE 100 A SECONDARY CURRENT / OUTPUT SIGNAL 4 Vp Othe - CAR